
7
TECSYSTEM S.r.l ®
Side view
Place the cooling fan unit on the I-beams of the transformer track in or-
der to direct the air flow inside the coil air ducts (figure 5).
Drill two holes of at least 11 mm where the bar rests on the track and fix it
with bolts of minimum 10MA, interposing a spring washer as shown in
figure 6.
To optimize the flow direction, it is possible to adjust the flapper angle,
paying attention to respect a minimum distance flapper-coil of 8 cm.
By tightening the flapper hinge screws, it is possible to clamp the posi-
tion.
4) MOUNTING OF THE BAR ON THE TRANSFORMER
Connect the input power supply of each fan with the relevant cable as
shown in figures 8,9,10 and 11.
Each cooling fan unit is equipped with a connector block containing a ter-
minal for connection to the mains, as shown in figure 7.
N.B.: in order to assure a suitable fan protection, we suggest to
feed them with TECSYSTEM monitoring unit model VRT200.
5) ELECTRICAL CONNECTIONS
15
A-B
Figure 4: fan fixing