GENERAL INFORMATION
SensoIRIS GAS is addressable gas, LPG and CH4 (Methane), leakage detector.
When flammable gas is present in concentrations, higher than the dangerous,
threshold alarm level is activated. Red indicator lights on and buzzer is turned on.
SensoIRIS GAS features a button with the following functions:
- If short pressed “SILENCING” mode is activated. Green LED flashes, buzzer
and panel activation are disabled for 5min;
- If pressed for more than 5 seconds “TEST” mode is activated. In this case
green, red and yellow LED’s are activated. Panel and buzzer are activated, too.
After 6 seconds gas detector emits 2 short sounds and leaves “TEST” mode.
Gas detector has auto diagnostic function. It continuously checks sensor and
electronics status. If problem with sensor or electronics yellow LED is activated,
green LED blinks and sound signal is activated.
TECHNICAL DATA
Power supply
Power consumption
Protection against electric shock:
Power connection
Sensor type
Sensor lifetime
Detected gases
Alarm threshold
Indicators:
Normal operation
Alarm
Fault
Heating-up time
Working temperature
Humidity limits
Alarms sound level
Size
Weight
Enclosure material
Enclosure color
24 VDC
<3W
Class III
hard wired
catalytic
5 years
LPG/CH4 (Methane)
10% LEL
Green LED
Red LED/Sound
Yellow LED/Sound
30 sec
о
0 - 40 С
20 - 80% RH
>85 dB
130х96х38mm
0,200kg
ABS
White (RAL 9003)
SensoIRIS GAS
GAS DETECTOR
Type: LPG/CH4
!ATTENTION: The SensoIRIS GAS detector must be connected only to fire panels,
which support TTE communication protocol!
This manual is subject to change without notice!
Teletek Electronics JSC
Address: 14A Srebarna Str,
1407 Sofia, Bulgaria
Ceiling
Floor
Detector
Gas source:
gas oven
0.3 - 1.0m
0.3 - 1.0m
- The LPG is heavier than air
and the detector should be
placed at height from the
room floor between 0.3 -
1.0m.
- The CH4 (Methane) is
lighter than air and the
detector should be placed at
height from the room ceiling
between 0.3 - 1.0m.
- The distance from the
detector to the gas source
for the both mentioned
above cases should not
exceed 1.5m.
Choosing the mounting place
18020995, RevA, 10/2018
1 2 3 4 5
24VDC
External power supply
INSTRUCTIONS FOR USE
Choosing the mounting place - continue
Avoid to install gas detector in the position in which its normal operation
could be compromised:
- directly over the cooking stoves;
- areas where the temperature may drop under -10°C or exceed + 40°C;
- directly above a sink;
- in an enclosed space (e.g. in a cupboard or behind a curtain);
- next to a door or window;
- next to an extractor fan;
- where dirt and dust may block the sensor;
- in a damp or humid location.
Do not use the following substances near to the device:
- solvents and diluents;
- alcohol, fuels;
- silicones products and colors;
- perfumes;
- cleaning detergents;
- spray products.
To mount gas detector
- Open the enclosure by pressing of the opening pin and lifting the
cover.
Press the opening pin
Connection
Connect the Positive loop wire to “+” terminal of the SensoIRIS MINP M
module, and the Negative loop wire to “-” terminal of the module. Set the
address of SensoIRIS MINP M module using SensoIRIS Programmer.
For detailed description of SensoIRIS MINP M module refer to its
installation manual available at www.teletek-electronics.com.
WARNING:
- Installation and wiring of gas detector must be made by qualified
technician with compliance with the current standards.
- Before wiring this gas detector turn mains power off.
- To ensure correct operation periodic functional check is advisable.
In order to check the proper efficiency of the device sensor a
specific test gas bottle must be used. Any other method for testing,
such as the use of cigarette lighters or flammable substances can
lead to wrong conclusions and damage the sensor.
WARNING in case of alarm:
- Extinguish all fire sources.
- Stop gas supply by closing main gas valve.
- Do not turn on or off any electrical devices.
- Open doors and windows to increase ventilation.
When alarm stops it is necessary to find gas leaking cause. If alarm
persists and the leak can not be found, vacate the premise and
immediately inform the gas emergency service.
In the view of a constant development of their products, the manufacturer
reserves the right for changing technical data and features without prior notice.
The consumer is guaranteed against any lack of conformity according to the
European Directive 1999/44/EC as well as to the manufacturer’s document about
the warranty policy.
The full text of warranty is available on request from the seller.
red
black
SensoIRIS
Programmer
SensoIRIS
MINP M +Line
-Line
SensoIRIS GAS
Terminals
Address
Programming
SensoIRIS
MINP M

Popular Gas Detector manuals by other brands

GST I-9602LW Installation and operation manual

GST

GST I-9602LW Installation and operation manual

Elektrotechnik Schabus GX-B1pro operating instructions

Elektrotechnik Schabus

Elektrotechnik Schabus GX-B1pro operating instructions

QED Geotech SEM5000 operating manual

QED

QED Geotech SEM5000 operating manual

BW Technologies GasAlertMicro 5 user manual

BW Technologies

BW Technologies GasAlertMicro 5 user manual

Trotec BG40 operating manual

Trotec

Trotec BG40 operating manual

S+S Regeltechnik AERASGARD ALQ-C02 Operating Instructions, Mounting & Installation

S+S Regeltechnik

S+S Regeltechnik AERASGARD ALQ-C02 Operating Instructions, Mounting & Installation

TELEDYNE OLDHAM SIMTRONICS Everywhereyoulook GD10-P00 operating manual

TELEDYNE OLDHAM SIMTRONICS

TELEDYNE OLDHAM SIMTRONICS Everywhereyoulook GD10-P00 operating manual

Rae FMC-40 Operating handbook

Rae

Rae FMC-40 Operating handbook

GST C-9602LW Installation and operation manual

GST

GST C-9602LW Installation and operation manual

PNI SafeHouse HS110 user manual

PNI

PNI SafeHouse HS110 user manual

Emerson MRLDS-450 Installing and operating instructions

Emerson

Emerson MRLDS-450 Installing and operating instructions

Honeywell Home SiXCOMBO-CN Installation and setup guide

Honeywell Home

Honeywell Home SiXCOMBO-CN Installation and setup guide

Kidde KN-COP-DP-10YL-AQ-WF-CA user guide

Kidde

Kidde KN-COP-DP-10YL-AQ-WF-CA user guide

DOEATOOW CO-3 Operation manual

DOEATOOW

DOEATOOW CO-3 Operation manual

LEGRAND 6827 01 quick start guide

LEGRAND

LEGRAND 6827 01 quick start guide

Elektrotechnik Schabus GX-B3 operating instructions

Elektrotechnik Schabus

Elektrotechnik Schabus GX-B3 operating instructions

RKI Instruments GX-2003 Quick reference guide

RKI Instruments

RKI Instruments GX-2003 Quick reference guide

RS PRO RS GD-38 instruction manual

RS PRO

RS PRO RS GD-38 instruction manual

manuals.online logo
manuals.online logoBrands
  • About & Mission
  • Contact us
  • Privacy Policy
  • Terms and Conditions

Copyright 2025 Manuals.Online. All Rights Reserved.