Loss of set points/time settings
Time, temperature, fan speed and on/off status should be retained in memory when power is
lost from external source.
‘OP' will appear on the display for a few seconds when switched on and defaults to: Monday
12am, Cool cycle, 25
°
C setpoint and low fan speed, when battery is low.
Check battery and/or battery polarity.
Check ‘Timer Active’ is being displayed. If not, then timer settings have not been activated by
the user.
Verify your settings were entered successfully and have not been miskeyed.
Fails to restart from external time clock
Time, temperature, fan speed and on/off status should be retained in memory when power is
lost from external source.
‘OP' will appear on the display for a few seconds when switched on and defaults to: Monday
12am, Cool cycle, 25
°
C setpoint and low fan speed, when battery is low.
Check battery and/or battery polarity (Note: battery life when used with an external time clock
is significantly reduced).
Disable internal time clock - turn dip switch 3 to OFF, and deactivate timer by pressing ‘Hold’
button until the words ‘Timer Active’ disappear.
Major swing in displayed temperature
Check supply air is not blowing directly or indirectly on to wall sensor/display.
Check position of Wall Display/Sensor relative to solar effect through window.
Check position of Wall Display/Sensor relative to draft from door, etc.
Check Wall Display/Sensor is not mounted on a cold/hot wall surface.
Check sensor is not pushed up inside - should be visible from underneath.
Check that a cold draft inside the wall structure is not entering the sensor area through the
electrical hole. (This is more common than you may think).
Indoor fan stops during dead zone (especially in heating mode)
Room or return air temperature has reached 18°C.
Check fresh air introduction is not too great thus influencing indoor coil sensor reading.
(TTS-10 is not really suitable for fresh air introduction above 15% of total air flow).
Check indoor coil temperature sensor is located properly in sensor pocket on coil return bend.
Check indoor coil sensor - should be in the range of 10 to 15 kohm if temperature is between
15 and 25°C. (Note: The sensor connection plug is glued to the pins on the Controller board.
To avoid damaging the pins, remove the Controller board and return it to temperzone for
testing.)
Check Wall Display/Sensor is not located such that air from a supply grille is blowing directly
or indirectly onto it. This may cause major swing of temperature at the sensor and change of
cycle from heat to cool, indoor fan stopping and long delay before restart.