Tense TPM-04 User manual

Supports 3P4W connections.
Measures up to voltage harmonics 31st.
Measures up to current harmonics 31st.
RS485 Modbus RTU
It shows the powers of each phase (P1, P2, P3).
It shows the apparent powers of each phase (S1, S2, S3).
It shows the reactive powers of each phase (Q1, Q2, Q3 inductive and capacitive).
It shows power factors (PF) and cosφ values of each phases.
It shows the min., max. and ave. values of the phase-to-phase and phase-neutral voltages.
It shows the values of each phase (I1, I2, I3).
It shows total import and export active (ΣkWh) energy.
It shows total inductive and capacitive reactive (ΣkVArh) energy.
2x relay outputs (adjustable), 1x Digital Input
It shows voltage and current irregularity.
It show demands.
You can delete energies and demands.
The menu is password protected.
TPM-04
USER MANUAL
Tense Electric - Electronic MADE IN TURKEY
Document Number: DK-088-2
71.5 x 61.5 Custom Design Glass LCD

Figure-1: Connection Type of 3P4W: 3 Phase current and 3 phase voltage. Neutrality.
Figure-2: 3 Phase current and 3 phase voltage. Neutrality.
It is suitable for medium voltage with voltage transformer.
1 - Connection Diagrams:
-1-
N
2A
L1
L2
L3
Load
Figure-1
18
17
16
15
19
20
21
22
23
24
25
3
2
1
26
27
28
4
5
6
7
8
9
10
11
12
14
13
A1
A2
N
L1
L2
L3
Max. 5A AC
I1I2
I3
I3
k3
I2
k2
I1
k1
Ct3
S1
P1
S2
P2
Ct2
S1
P1
S2
P2
Ct1
S1
P1
S2
P2
RS485
A
B
DIN+
DIN-
Out1
Out2
N
2A
L1
L2
L3
Load
Figure-2
18
17
16
15
19
20
21
22
23
24
25
3
2
1
26
27
28
4
5
6
7
8
9
10
11
12
14
13
A1
A2
N
L1
L2
L3
Max. 5A AC
I1I2
I3
I3
k3
I2
k2
I1
k1
2A
V.T.1
V.T.2
V.T.3
220V AC
50/60Hz.
Ct3
S1
P1
S2
P2
Ct2
S1
P1
S2
P2
Ct1
S1
P1
S2
P2
RS485
A
B
DIN+
DIN-
Out1
Out2
2 - Matters to be considered in current transformer selection and connection
To avoid the complexity when connecting the current transformer output terminal use different colour
cables or give cable numbers.
Please spread the cables which are connected to current transformer output terminal from remote
high voltage lines.
Please fix current transformers to bara, cable or rail to avoid rattling.
Note that the value of current transformer is higher than the maximum current drawn from the system.
It is advisible that the class of the current transformer (it can be written class, klas, cl, kl) is 0.5.
3 - Warnings:
Please use the device properly according to our directions.
Please protect LCD screen from sun light.
Please take 5 cm. space behind the device after the device installation.
Please fix the device front cover panel with the apparatus that comes with it.
Please not use device in the damp board.
Please keep key or circuit breaker close the device or in an easily accessible location by the operator.
Please add a key or circuit breaker to assembly.
There should be no electricity in the connection cables when assembling device.
There should be used shielded or twisted cord cable at the non-network-connected input and output.
lines. These cables should not be passed near the high power lines and the device.
Assembling and electrical connections must be done by technical staff according to instruction manuel.
The feed cables should be suitable for IEC 60227 or IEC 60245 requirements.
Please read the warnings before powering the device. Make connections of the device according to the
connection scheme. When the device is first powered up figure-3 displayed on the screen. Firstly enter the
current transformer ratio from the settings menu and if the voltage transformer medium voltage is being
measured), enter the voltage transformer ratios.
6 - First Operation of the Device:
5 - General:
TPM-04 Energy analyzer measures load or voltage, current, cosφ, active power, reactive power, minimum
and maximum values of the load and also measures demands. This analyzer measures current harmonics
and voltage harmonics up to 31. harmonics.
4 - Device Maintenance :
Turn off energy of the device and disconnect from connections. Clean the device body by using slightly
moist or dry cloth. Do not use conductor or other chemical as a cleaning agent matter which is harmful to
device. Make connections after the cleaning of device and give energy to device and make sure that device
works properly.
-2-

Figure-1: Connection Type of 3P4W: 3 Phase current and 3 phase voltage. Neutrality.
Figure-2: 3 Phase current and 3 phase voltage. Neutrality.
It is suitable for medium voltage with voltage transformer.
1 - Connection Diagrams:
-1-
N
2A
L1
L2
L3
Load
Figure-1
18
17
16
15
19
20
21
22
23
24
25
3
2
1
26
27
28
4
5
6
7
8
9
10
11
12
14
13
A1
A2
N
L1
L2
L3
Max. 5A AC
I1I2
I3
I3
k3
I2
k2
I1
k1
Ct3
S1
P1
S2
P2
Ct2
S1
P1
S2
P2
Ct1
S1
P1
S2
P2
RS485
A
B
DIN+
DIN-
Out1
Out2
N
2A
L1
L2
L3
Load
Figure-2
18
17
16
15
19
20
21
22
23
24
25
3
2
1
26
27
28
4
5
6
7
8
9
10
11
12
14
13
A1
A2
N
L1
L2
L3
Max. 5A AC
I1I2
I3
I3
k3
I2
k2
I1
k1
2A
V.T.1
V.T.2
V.T.3
220V AC
50/60Hz.
Ct3
S1
P1
S2
P2
Ct2
S1
P1
S2
P2
Ct1
S1
P1
S2
P2
RS485
A
B
DIN+
DIN-
Out1
Out2
2 - Matters to be considered in current transformer selection and connection
To avoid the complexity when connecting the current transformer output terminal use different colour
cables or give cable numbers.
Please spread the cables which are connected to current transformer output terminal from remote
high voltage lines.
Please fix current transformers to bara, cable or rail to avoid rattling.
Note that the value of current transformer is higher than the maximum current drawn from the system.
It is advisible that the class of the current transformer (it can be written class, klas, cl, kl) is 0.5.
3 - Warnings:
Please use the device properly according to our directions.
Please protect LCD screen from sun light.
Please take 5 cm. space behind the device after the device installation.
Please fix the device front cover panel with the apparatus that comes with it.
Please not use device in the damp board.
Please keep key or circuit breaker close the device or in an easily accessible location by the operator.
Please add a key or circuit breaker to assembly.
There should be no electricity in the connection cables when assembling device.
There should be used shielded or twisted cord cable at the non-network-connected input and output.
lines. These cables should not be passed near the high power lines and the device.
Assembling and electrical connections must be done by technical staff according to instruction manuel.
The feed cables should be suitable for IEC 60227 or IEC 60245 requirements.
Please read the warnings before powering the device. Make connections of the device according to the
connection scheme. When the device is first powered up figure-3 displayed on the screen. Firstly enter the
current transformer ratio from the settings menu and if the voltage transformer medium voltage is being
measured), enter the voltage transformer ratios.
6 - First Operation of the Device:
5 - General:
TPM-04 Energy analyzer measures load or voltage, current, cosφ, active power, reactive power, minimum
and maximum values of the load and also measures demands. This analyzer measures current harmonics
and voltage harmonics up to 31. harmonics.
4 - Device Maintenance :
Turn off energy of the device and disconnect from connections. Clean the device body by using slightly
moist or dry cloth. Do not use conductor or other chemical as a cleaning agent matter which is harmful to
device. Make connections after the cleaning of device and give energy to device and make sure that device
works properly.
-2-

-4-
7- Introduction of Screen:
1 - Indicates the unit of the value.
2 - Indicates which phase the value belongs to .
Indicates that the values shown are minimum.
(Period: 2 seconds.)
Indicates that the values shown are average.
(Period: 5 minutes.)
Specified that the indicated active energies are imported.
Specified that the indicated active energies are exported.
Specified that the indicated reactive energies are inductive.
3 - Indicates displayed values. V-voltage, I-current, F-frequency, S-apparent power, P-active power,
PF-power factor, FI-cosine phi, THD-I-total current harmonics, THD-V- total voltage harmonics,
Q- reactive power.
Specified that the indicated reactive energies are capacitive.
Specified that the indicated reactive energies are inductive.
Specified that the indicated reactive power are capacitive.
Out2: Relay 2 is pulled.
(Short circuit)
Out1: Relay 1 is pulled.
(Short circuit)
Out1: Relay 1 is released.
(Spen circuit)
Out2: Relay 2 is released.
(Open circuit)
-3-
1
2
3
2
L1
3
L2
1
L3
THD-IP F IQ
S
kW h
VAk h
Hz
kW h
VA rk h
Hz
kW h
VA rk h
Hz %
kA
%
kA
%
kA
ΣP
Σ
+Q
Σ
-Q
Indicates that the values shown are maximum.
(Period: 2 seconds.)
Indicates that the values shown are demand.
(Period: 15 minutes.)
r
Out1
Din1
-P
-P
-Q
-Q
+Q
+Q
+P
+P
Out2
2
2
Out1
Out1
Out2
Out2
Total active energy.
ΣP
Total inductive reactive energy.
Σ
+Q
Total capacitive reactive energy.
Σ
-Q
New
Pass
Time
CTR VTR
kV THD-V
Din1: There is voltage(1).
Din1: There is no voltage(0).
Din1
Din1
This button enters menu/parameter. It records the changes of parameters and remove
from parameter.
ESC:
SET:
DOWN:
RIGHT:
Press this button while in menu to exit the menu without saving the values.
When this key is pressed while not in the menu, the screen always shows figure-3.
This button enables to fast progress between the values that are measured out of menu.
Changes the value while inside the parameters in the menu.
This button allows to progress by displaying the measured values outside the menu together
with the details. It allows navigation between parameters when pressed in menu.
In the parameter, it allows to transition between steps and parameters.
8- Introduction of Buttons:

-4-
7- Introduction of Screen:
1 - Indicates the unit of the value.
2 - Indicates which phase the value belongs to .
Indicates that the values shown are minimum.
(Period: 2 seconds.)
Indicates that the values shown are average.
(Period: 5 minutes.)
Specified that the indicated active energies are imported.
Specified that the indicated active energies are exported.
Specified that the indicated reactive energies are inductive.
3 - Indicates displayed values. V-voltage, I-current, F-frequency, S-apparent power, P-active power,
PF-power factor, FI-cosine phi, THD-I-total current harmonics, THD-V- total voltage harmonics,
Q- reactive power.
Specified that the indicated reactive energies are capacitive.
Specified that the indicated reactive energies are inductive.
Specified that the indicated reactive power are capacitive.
Out2: Relay 2 is pulled.
(Short circuit)
Out1: Relay 1 is pulled.
(Short circuit)
Out1: Relay 1 is released.
(Spen circuit)
Out2: Relay 2 is released.
(Open circuit)
-3-
1
2
3
2
L1
3
L2
1
L3
THD-IP F IQ
S
kW h
VAk h
Hz
kW h
VA rk h
Hz
kW h
VA rk h
Hz %
kA
%
kA
%
kA
ΣP
Σ
+Q
Σ
-Q
Indicates that the values shown are maximum.
(Period: 2 seconds.)
Indicates that the values shown are demand.
(Period: 15 minutes.)
r
Out1
Din1
-P
-P
-Q
-Q
+Q
+Q
+P
+P
Out2
2
2
Out1
Out1
Out2
Out2
Total active energy.
ΣP
Total inductive reactive energy.
Σ
+Q
Total capacitive reactive energy.
Σ
-Q
New
Pass
Time
CTR VTR
kV THD-V
Din1: There is voltage(1).
Din1: There is no voltage(0).
Din1
Din1
This button enters menu/parameter. It records the changes of parameters and remove
from parameter.
ESC:
SET:
DOWN:
RIGHT:
Press this button while in menu to exit the menu without saving the values.
When this key is pressed while not in the menu, the screen always shows figure-3.
This button enables to fast progress between the values that are measured out of menu.
Changes the value while inside the parameters in the menu.
This button allows to progress by displaying the measured values outside the menu together
with the details. It allows navigation between parameters when pressed in menu.
In the parameter, it allows to transition between steps and parameters.
8- Introduction of Buttons:

Figure-3: Shows phase-neutral voltage. When you press right button, the figure-4 appears on the
screen.
Figure-4: Shows minimum(Min) voltage values of phase-neutral voltage. When you press right button,
the figure-5 appears on the screen.
Figure-5: Shows maximum(Max) voltage values of phase-neutral voltage. When you press right button,
the figure-6 appears on the screen.
Figure-6: Shows average(Ave) voltage values of phase-neutral voltage. When you press right button,
the figure-7 appears on the screen
Figure-7: Shows the phase-phase voltage values. When you press right button, the figure-8 appears
on the screen.
Figure-8: Shows the minimum(Min) values of the phase-phase voltage. When you press right button,
the figure-9 appears on the screen.
Figure-9: Shows the maximum(Max) values of the phase-phase voltage. When you press right button,
the figure-10 appears on the screen.
Figure-10: Shows the average(Ave) values of the phase-phase voltage. When you press right button,
the figure-11 appears on the screen.
9 - Progress On Screen Information:
Figure-3 Figure-4 Figure-5 Figure-6
L1
L2
L3
V
V
V
V
Out1
Din1 Out2
L1
L2
L3
V
V
V
V
Out1
Din1 Out2
L1
L2
L3
V
V
V
V
Out1
Din1 Out2
L1
L2
L3
V
V
V
V
Out1
Din1 Out2
Figure-7 Figure-8 Figure-9 Figure-10
L12
L23
L31
V
V
V
V
Out1
Din1 Out2
L12
L23
L31
V
V
V
V
Out1
Din1 Out2
L12
L23
L31
V
V
V
V
Out1
Din1 Out2
L12
L23
L31
V
V
V
V
Out1
Din1 Out2
-5-
Figure-11: Shows the current values of each phase. When you press the right button, figure-12 appears
on the screen.
Figure-12: Shows the current demand(Dmd) values for each phase. When you press the right button,
figure-13 appears on the screen.
Figure-13: Shows the active power(P) values for each phase. When you press the right button, figure-14
appears on the screen.
Figure-14: Shows the active power(P) demand(Dmd) values for each phase. When you press the right
button, figure-15 appears on the screen.
Figure-11
L1
L2
L3
I
A
A
A
Out1
Din1 Out2
Figure-12
L1
L2
L3
I
A
A
A
Out1
Din1 Out2
Figure-13
L1
L2
L3
P
kW
kW
kW
Out1
Din1 Out2
Figure-14
P
L1
L2
L3
kW
kW
kW
Out1
Din1 Out2
P
-6-
Figure-15: Shows the reactive power value(Q) values for each phase. When you press the right button,
figure-16 appears on the screen.
Figure-16: Shows the active power(Q) demand(Dmd) values for each phase. When you press the right
button, figure-17 appears on the screen.
Figure-17: Shows the apparent power(S) values for each phase. When you press the right
button, figure-18 appears on the screen.
Figure-18: Shows the apparent power(S) demand(Dmd) values for each phase. When you press the right
button, figure-19 appears on the screen.
Figure-19: Shows the power factor(PF) values for each phase. When you press the right button,
figure-20 appears on the screen.
Figure-20: Shows the cosine phi(FI) values for each phase. When you press the right button, figure-21
appears on the screen.
Figure-21: Shows the frequency(F) values for each phase. When you press the right button, figure-22
appears on the screen.
Figure-22: Shows the total voltage harmonic distortion value (THD-V) values for each phase. When you
press the right button, figure-23 appears on the screen.
Figure-23: Voltage harmonics values of up to 31st harmonics are displayed on each screen,
with 3 values per screen. When you press the right button, the values of the L2 and L3 phases are
displayed on the screen respectively. When you press the right button, figure-24 appears on the screen.
Figure-15 Figure-16
Q
L1
L2
L3
kVAr
kVAr
kVAr
Out1
Din1 Out2
Q
L1
L2
L3
Q
kVAr
kVAr
kVAr
Out1
Din1 Out2
Figure-17
L1
L2
L3
S
Var
Var
Var
Out1
Din1 Out2
Figure-18
S
L1
L2
L3
Var
Var
Var
Out1
Din1 Out2
S
Figure-19 Figure-20 Figure-21 Figure-22
L1
L2
L3
PF
Out1
Din1 Out2
L1
L2
L3
F
Out1
Din1 Out2
Hz
Hz
Hz
F
Out1
Din1 Out2
I
L1
L2
L3
Figure-23
L1
Out1
Din1 Out2
%
%
%
THD-V
L1
L2
L3
Out1
Din1 Out2
%
%
%
THD-V

Figure-3: Shows phase-neutral voltage. When you press right button, the figure-4 appears on the
screen.
Figure-4: Shows minimum(Min) voltage values of phase-neutral voltage. When you press right button,
the figure-5 appears on the screen.
Figure-5: Shows maximum(Max) voltage values of phase-neutral voltage. When you press right button,
the figure-6 appears on the screen.
Figure-6: Shows average(Ave) voltage values of phase-neutral voltage. When you press right button,
the figure-7 appears on the screen
Figure-7: Shows the phase-phase voltage values. When you press right button, the figure-8 appears
on the screen.
Figure-8: Shows the minimum(Min) values of the phase-phase voltage. When you press right button,
the figure-9 appears on the screen.
Figure-9: Shows the maximum(Max) values of the phase-phase voltage. When you press right button,
the figure-10 appears on the screen.
Figure-10: Shows the average(Ave) values of the phase-phase voltage. When you press right button,
the figure-11 appears on the screen.
9 - Progress On Screen Information:
Figure-3 Figure-4 Figure-5 Figure-6
L1
L2
L3
V
V
V
V
Out1
Din1 Out2
L1
L2
L3
V
V
V
V
Out1
Din1 Out2
L1
L2
L3
V
V
V
V
Out1
Din1 Out2
L1
L2
L3
V
V
V
V
Out1
Din1 Out2
Figure-7 Figure-8 Figure-9 Figure-10
L12
L23
L31
V
V
V
V
Out1
Din1 Out2
L12
L23
L31
V
V
V
V
Out1
Din1 Out2
L12
L23
L31
V
V
V
V
Out1
Din1 Out2
L12
L23
L31
V
V
V
V
Out1
Din1 Out2
-5-
Figure-11: Shows the current values of each phase. When you press the right button, figure-12 appears
on the screen.
Figure-12: Shows the current demand(Dmd) values for each phase. When you press the right button,
figure-13 appears on the screen.
Figure-13: Shows the active power(P) values for each phase. When you press the right button, figure-14
appears on the screen.
Figure-14: Shows the active power(P) demand(Dmd) values for each phase. When you press the right
button, figure-15 appears on the screen.
Figure-11
L1
L2
L3
I
A
A
A
Out1
Din1 Out2
Figure-12
L1
L2
L3
I
A
A
A
Out1
Din1 Out2
Figure-13
L1
L2
L3
P
kW
kW
kW
Out1
Din1 Out2
Figure-14
P
L1
L2
L3
kW
kW
kW
Out1
Din1 Out2
P
-6-
Figure-15: Shows the reactive power value(Q) values for each phase. When you press the right button,
figure-16 appears on the screen.
Figure-16: Shows the active power(Q) demand(Dmd) values for each phase. When you press the right
button, figure-17 appears on the screen.
Figure-17: Shows the apparent power(S) values for each phase. When you press the right
button, figure-18 appears on the screen.
Figure-18: Shows the apparent power(S) demand(Dmd) values for each phase. When you press the right
button, figure-19 appears on the screen.
Figure-19: Shows the power factor(PF) values for each phase. When you press the right button,
figure-20 appears on the screen.
Figure-20: Shows the cosine phi(FI) values for each phase. When you press the right button, figure-21
appears on the screen.
Figure-21: Shows the frequency(F) values for each phase. When you press the right button, figure-22
appears on the screen.
Figure-22: Shows the total voltage harmonic distortion value (THD-V) values for each phase. When you
press the right button, figure-23 appears on the screen.
Figure-23: Voltage harmonics values of up to 31st harmonics are displayed on each screen,
with 3 values per screen. When you press the right button, the values of the L2 and L3 phases are
displayed on the screen respectively. When you press the right button, figure-24 appears on the screen.
Figure-15 Figure-16
Q
L1
L2
L3
kVAr
kVAr
kVAr
Out1
Din1 Out2
Q
L1
L2
L3
Q
kVAr
kVAr
kVAr
Out1
Din1 Out2
Figure-17
L1
L2
L3
S
Var
Var
Var
Out1
Din1 Out2
Figure-18
S
L1
L2
L3
Var
Var
Var
Out1
Din1 Out2
S
Figure-19 Figure-20 Figure-21 Figure-22
L1
L2
L3
PF
Out1
Din1 Out2
L1
L2
L3
F
Out1
Din1 Out2
Hz
Hz
Hz
F
Out1
Din1 Out2
I
L1
L2
L3
Figure-23
L1
Out1
Din1 Out2
%
%
%
THD-V
L1
L2
L3
Out1
Din1 Out2
%
%
%
THD-V

-7-
Figure-24: Shows the total current harmonic distortion value(THD-I) values for each phase. When you
press the right button, figure-25 appears on the screen.
Figure-25: Current harmonics values of up to 31st harmonics are displayed on each screen,
with 3 values per screen. When you press the right button, the values of the L2 and L3 phases are
displayed on the screen respectively. When you press the right button, figure-26 appears on the screen.
Figure-26: Shows the total import active, total inductive reactive and total capacitive reactive
energy values. When you press the right button, figure-27 appears on the screen.
Figure-27: Shows the import active energy values for each phase. When you press the right button,
figure-28 appears on the screen.
Figure-28: Shows the export active energy values for each phase. When you press the right button,
figure-29 appears on the screen.
Figure-29: Shows the inductive reactive energy values for each phase. When you press the right button,
figure-30 appears on the screen.
Figure-30: Shows the capacitive reactive energy values for each phase. When you press the right button,
figure-31 appears on the screen.
Figure-31: Shows current and voltage irregularity. When you press the right button, figure-32 appears
on the screen.
Figure-32: Used to enter the menu to make settings related to the device. When you press the
right button again on this screen, the password screen for entering the menu is displayed.
Figure-25 Figure-26
THD-I
Out1
Din1 Out2 Out1
Din1 Out2
kWh
kVArh
kVArh
ΣP
Σ
+Q
Σ
-Q
Figure-24
THD-I
Out1
Din1 Out2
L1
%
%
%
L1
L2
L3
%
%
%
Out1
Din1 Out2
kWh
kWh
kWh
Out1
Din1 Out2
kVArh
kVArh
kVArh
Out1
Din1 Out2
kVArh
kVArh
kVArh
Out1
Din1 Out2
kWh
kWh
kWh
Figure-27 Figure-28 Figure-29 Figure-30
-P
L1
L2
L3
+P
L1
L2
L3
+Q
L1
L2
L3
-Q
L1
L2
L3
Out1
Din1 Out2
Figure-32Figure-31
Out1
Din1 Out2
%
%
When the device is energised, figure-3 is displayed.
When you press the down button, figure-7 is displayed.
When you press the down button, figure-11 is displayed.
When you press the down button, figure-13 is displayed.
When you press the down button, figure-15 is displayed.
When you press the down button, figure-17 is displayed.
When you press the down button, figure-19 is displayed.
When you press the down button, figure-20 is displayed.
When you press the down button, figure-21 is displayed.
When you press the down button, figure-22 is displayed.
When you press the down button, figure-24 is displayed.
When you press the down button, figure-26 is displayed.
When you press the down button, figure-31 is displayed.
When you press the down button, figure-32 is displayed.
When you press the down button, figure-3 is displayed.
10 - Fast Forwarding of Screen Information:
Figure-11 Figure-13
Figure-3
L1
L2
L3
V
V
V
V
Out1
Din1 Out2
Figure-7
L12
L23
L31
V
V
V
V
Out1
Din1 Out2
Figure-15
Figure-17
Figure-19
Out1
Din1 Out2
Figure-32
Figure-3: Shows the phase-neutral voltage(V) values.
Figure-7: Shows the phase-phase voltage(V) values.
Figure-11: Shows the current (I) values.
Figure-13: Shows the active power(P) values.
Figure-15: Shows the reactive power(Q) values
Figure-17: Shows the apparent power(S) values
Figure-19: Shows the power factor(PF) values
Figure-20: Shows the cosine phi(FI) values
Figure-21: Shows the frequency(F) values
Figure-22: Shows the total voltage harmonic distortion values.
Figure-24: Shows the total current harmonic distortion values.
Figure-26: Shows the total energy (active & reactive) values.
Figure-31: Shows the current and voltage irregularity values.
Figure-32: Used to enter the menu to make settings related
to the device.
Figure-26
Figure-31
Figure-21
L1
L2
L3
F
Out1
Din1 Out2
Hz
Hz
Hz
Figure-22Figure-24 Figure-20
L1
L2
L3
PF
Out1
Din1 Out2
Din2
-8-
Out1
Din1 Out2
%
%
THD-I
Out1
Din1 Out2
L1
L2
L3
%
%
%
Out1
Din1 Out2
kWh
kVArh
kVArh
ΣP
Σ
+Q
Σ
-Q
L1
L2
L3
Out1
Din1 Out2
%
%
%
THD-V
L1
L2
L3
PF
Out1
Din1 Out2
F
Out1
Din1 Out2
I
L1
L2
L3
L1
L2
L3
S
Var
Var
Var
Out1
Din1 Out2
L1
L2
L3
Q
kVAr
kVAr
kVAr
Out1
Din1 Out2
L1
L2
L3
I
A
A
A
Out1
Din1 Out2
L1
L2
L3
P
kW
kW
kW
Out1
Din1 Out2

-7-
Figure-24: Shows the total current harmonic distortion value(THD-I) values for each phase. When you
press the right button, figure-25 appears on the screen.
Figure-25: Current harmonics values of up to 31st harmonics are displayed on each screen,
with 3 values per screen. When you press the right button, the values of the L2 and L3 phases are
displayed on the screen respectively. When you press the right button, figure-26 appears on the screen.
Figure-26: Shows the total import active, total inductive reactive and total capacitive reactive
energy values. When you press the right button, figure-27 appears on the screen.
Figure-27: Shows the import active energy values for each phase. When you press the right button,
figure-28 appears on the screen.
Figure-28: Shows the export active energy values for each phase. When you press the right button,
figure-29 appears on the screen.
Figure-29: Shows the inductive reactive energy values for each phase. When you press the right button,
figure-30 appears on the screen.
Figure-30: Shows the capacitive reactive energy values for each phase. When you press the right button,
figure-31 appears on the screen.
Figure-31: Shows current and voltage irregularity. When you press the right button, figure-32 appears
on the screen.
Figure-32: Used to enter the menu to make settings related to the device. When you press the
right button again on this screen, the password screen for entering the menu is displayed.
Figure-25 Figure-26
THD-I
Out1
Din1 Out2 Out1
Din1 Out2
kWh
kVArh
kVArh
ΣP
Σ
+Q
Σ
-Q
Figure-24
THD-I
Out1
Din1 Out2
L1
%
%
%
L1
L2
L3
%
%
%
Out1
Din1 Out2
kWh
kWh
kWh
Out1
Din1 Out2
kVArh
kVArh
kVArh
Out1
Din1 Out2
kVArh
kVArh
kVArh
Out1
Din1 Out2
kWh
kWh
kWh
Figure-27 Figure-28 Figure-29 Figure-30
-P
L1
L2
L3
+P
L1
L2
L3
+Q
L1
L2
L3
-Q
L1
L2
L3
Out1
Din1 Out2
Figure-32Figure-31
Out1
Din1 Out2
%
%
When the device is energised, figure-3 is displayed.
When you press the down button, figure-7 is displayed.
When you press the down button, figure-11 is displayed.
When you press the down button, figure-13 is displayed.
When you press the down button, figure-15 is displayed.
When you press the down button, figure-17 is displayed.
When you press the down button, figure-19 is displayed.
When you press the down button, figure-20 is displayed.
When you press the down button, figure-21 is displayed.
When you press the down button, figure-22 is displayed.
When you press the down button, figure-24 is displayed.
When you press the down button, figure-26 is displayed.
When you press the down button, figure-31 is displayed.
When you press the down button, figure-32 is displayed.
When you press the down button, figure-3 is displayed.
10 - Fast Forwarding of Screen Information:
Figure-11 Figure-13
Figure-3
L1
L2
L3
V
V
V
V
Out1
Din1 Out2
Figure-7
L12
L23
L31
V
V
V
V
Out1
Din1 Out2
Figure-15
Figure-17
Figure-19
Out1
Din1 Out2
Figure-32
Figure-3: Shows the phase-neutral voltage(V) values.
Figure-7: Shows the phase-phase voltage(V) values.
Figure-11: Shows the current (I) values.
Figure-13: Shows the active power(P) values.
Figure-15: Shows the reactive power(Q) values
Figure-17: Shows the apparent power(S) values
Figure-19: Shows the power factor(PF) values
Figure-20: Shows the cosine phi(FI) values
Figure-21: Shows the frequency(F) values
Figure-22: Shows the total voltage harmonic distortion values.
Figure-24: Shows the total current harmonic distortion values.
Figure-26: Shows the total energy (active & reactive) values.
Figure-31: Shows the current and voltage irregularity values.
Figure-32: Used to enter the menu to make settings related
to the device.
Figure-26
Figure-31
Figure-21
L1
L2
L3
F
Out1
Din1 Out2
Hz
Hz
Hz
Figure-22Figure-24 Figure-20
L1
L2
L3
PF
Out1
Din1 Out2
Din2
-8-
Out1
Din1 Out2
%
%
THD-I
Out1
Din1 Out2
L1
L2
L3
%
%
%
Out1
Din1 Out2
kWh
kVArh
kVArh
ΣP
Σ
+Q
Σ
-Q
L1
L2
L3
Out1
Din1 Out2
%
%
%
THD-V
L1
L2
L3
PF
Out1
Din1 Out2
F
Out1
Din1 Out2
I
L1
L2
L3
L1
L2
L3
S
Var
Var
Var
Out1
Din1 Out2
L1
L2
L3
Q
kVAr
kVAr
kVAr
Out1
Din1 Out2
L1
L2
L3
I
A
A
A
Out1
Din1 Out2
L1
L2
L3
P
kW
kW
kW
Out1
Din1 Out2

Figure-34: It is used to enter the current transformer ratio.
Figure-35: It is used to enter the voltage transformer ratio.
Figure-36: It is used to make communication settings.
Figure-37: It is used to delete Energy and Demand records.
Figure-38: It is used to set the password.
Figure-39: It is used to assign Relay 1.
Figure-40: It is used to assign Relay 2.
When you press the right button while the figure-32
is on screen, figure-33 password inquiry is displayed
on the screen. If a password has been created, enter
the password and press the set key.
If password is not created before, when you press
set button while password value is "0000", you can enter
menu and Figure-34 comes to the screen.
By pressing the right button in the menu, you can scroll
through the parameters. Press the set key to set the
parameters. Press the Esc key to exit the menu.
-9-
Figure-39
Out1
Din1 Out2
Figure-40
Out1
Din1 Out2
Figure-35
Out1
Din1 Out2
Figure-34
Out1
Din1 Out2
Out1
Din1 Out2
Figure-32
Out1
Din1 Out2
Figure-33
11 - Menu Structure:
Figure-36
Out1
Din1 Out2
Figure-37
Out1
Din1 Out2
Figure-38
Out1
Din1 Out2
13 - Setting the Voltage Transformer Ratio:
Figure-41
Figure-34
To change the current transformer ratio, press the set
button while the figure-34 is on the screen. Figure-41
comes to the screen. Press right button to move between
digits. Press the down key to change the value of the digit.
You can change the digit value which is the underline.
When you press the set button after entering the ratio,
the current transformer ratio is recorded and the screen
shows figure-34. You can scroll through the parameters
in the menu by pressing the right button or you can exit the menu by pressing the Esc key.
To change the voltage transformer ratio, press the set
button while the figure-35 is on the screen. Figure-42
comes to the screen. Press right button to move between
digits. Press the down key to change the value of the digit.
You can change the digit value which is the underline.
When you press the set button after entering the ratio,
the voltage transformer ratio is recorded and the screen
shows figure-35 You can scroll through the parameters
in the menu by pressing the right button or you can exit the menu by pressing the Esc key.
Example: 100 / 5A current transformer ratio (multiplier value) is 20. The CTR value needs to be set to 0020.
Figure-42Figure-35
Example: Medium voltage (M.V.) = Enter the ratio of the voltage transformer that converts 34.500V to 110V.
The ratio (multiplier) is calculated as 34,500 / 110 = 313,6 voltage transformer ratio. The VTR value must be
set to 313.6.
-10-
12 - Setting the Current Transformer Ratio:
Out1
Din1 Out2
Out1
Din1 Out2
Out1
Din1 Out2 Out1
Din1 Out2
14 - RS485 Remote Communication Settings:
Figure-43
To change the RS-485 remote communication settings,
press the set button while figure-36 is on the screen.
Figure-43 comes to the screen. Two parameters can be
set here. Baudrate (br -communication speed) and
Modbus ID (Id - the number that identifies the device on
the RS 485 line). Press the right button to move the point
(.) to the parameter you want to set.
Then change the parameter value by pressing the down key. When you press the Set button, the changes
that you made are saved and Figure-36 comes to the screen. You can scroll through the parameters in the
menu by pressing the right button or you can exit the menu by pressing the Esc key.
Modbus ID (MBID) value; when more than one communication devices connect to a modem, Serial
number or ModBus address must be different. In such cases, enter a different value from other devices.
Baudrate(br): 1200 - 38400 bps, ModBus ID(Id): 1 - 247 Stop bits: 1-2, Party : Even, Odd, None.
Figure-36
Out1
Din1 Out2 Out1
Din1 Out2
15 - Deleting Energy and Demand Records:
To delete the records, press the set key while
figure-37 is on the screen. Figure-44 comes to the
screen. You can delete 2 records here. Energy (En) and
Demand (dE). Press the right key to move the point (.)
to the record which you want to delete. Then press the
down key to change the value to "yes". The record value
which you do not want to delete must remain in "no".
When you press the Set button, only records with the value "yes" will be deleted and the Figure-37
comes to the screen. You can scroll through the parameters in the menu by pressing the right button
or you can exit the menu by pressing the Esc key.
Figure-37
Out1
Din1 Out2
Figure-44
Out1
Din1 Out2
Note: If the cable length in the RS485 communication line is too high (>100m), connect the 120R resistor
parallel to the A-B (RS-485) terminal of the begin and end of the communication line to avoid data loss.

Figure-34: It is used to enter the current transformer ratio.
Figure-35: It is used to enter the voltage transformer ratio.
Figure-36: It is used to make communication settings.
Figure-37: It is used to delete Energy and Demand records.
Figure-38: It is used to set the password.
Figure-39: It is used to assign Relay 1.
Figure-40: It is used to assign Relay 2.
When you press the right button while the figure-32
is on screen, figure-33 password inquiry is displayed
on the screen. If a password has been created, enter
the password and press the set key.
If password is not created before, when you press
set button while password value is "0000", you can enter
menu and Figure-34 comes to the screen.
By pressing the right button in the menu, you can scroll
through the parameters. Press the set key to set the
parameters. Press the Esc key to exit the menu.
-9-
Figure-39
Out1
Din1 Out2
Figure-40
Out1
Din1 Out2
Figure-35
Out1
Din1 Out2
Figure-34
Out1
Din1 Out2
Out1
Din1 Out2
Figure-32
Out1
Din1 Out2
Figure-33
11 - Menu Structure:
Figure-36
Out1
Din1 Out2
Figure-37
Out1
Din1 Out2
Figure-38
Out1
Din1 Out2
13 - Setting the Voltage Transformer Ratio:
Figure-41
Figure-34
To change the current transformer ratio, press the set
button while the figure-34 is on the screen. Figure-41
comes to the screen. Press right button to move between
digits. Press the down key to change the value of the digit.
You can change the digit value which is the underline.
When you press the set button after entering the ratio,
the current transformer ratio is recorded and the screen
shows figure-34. You can scroll through the parameters
in the menu by pressing the right button or you can exit the menu by pressing the Esc key.
To change the voltage transformer ratio, press the set
button while the figure-35 is on the screen. Figure-42
comes to the screen. Press right button to move between
digits. Press the down key to change the value of the digit.
You can change the digit value which is the underline.
When you press the set button after entering the ratio,
the voltage transformer ratio is recorded and the screen
shows figure-35 You can scroll through the parameters
in the menu by pressing the right button or you can exit the menu by pressing the Esc key.
Example: 100 / 5A current transformer ratio (multiplier value) is 20. The CTR value needs to be set to 0020.
Figure-42Figure-35
Example: Medium voltage (M.V.) = Enter the ratio of the voltage transformer that converts 34.500V to 110V.
The ratio (multiplier) is calculated as 34,500 / 110 = 313,6 voltage transformer ratio. The VTR value must be
set to 313.6.
-10-
12 - Setting the Current Transformer Ratio:
Out1
Din1 Out2
Out1
Din1 Out2
Out1
Din1 Out2 Out1
Din1 Out2
14 - RS485 Remote Communication Settings:
Figure-43
To change the RS-485 remote communication settings,
press the set button while figure-36 is on the screen.
Figure-43 comes to the screen. Two parameters can be
set here. Baudrate (br -communication speed) and
Modbus ID (Id - the number that identifies the device on
the RS 485 line). Press the right button to move the point
(.) to the parameter you want to set.
Then change the parameter value by pressing the down key. When you press the Set button, the changes
that you made are saved and Figure-36 comes to the screen. You can scroll through the parameters in the
menu by pressing the right button or you can exit the menu by pressing the Esc key.
Modbus ID (MBID) value; when more than one communication devices connect to a modem, Serial
number or ModBus address must be different. In such cases, enter a different value from other devices.
Baudrate(br): 1200 - 38400 bps, ModBus ID(Id): 1 - 247 Stop bits: 1-2, Party : Even, Odd, None.
Figure-36
Out1
Din1 Out2 Out1
Din1 Out2
15 - Deleting Energy and Demand Records:
To delete the records, press the set key while
figure-37 is on the screen. Figure-44 comes to the
screen. You can delete 2 records here. Energy (En) and
Demand (dE). Press the right key to move the point (.)
to the record which you want to delete. Then press the
down key to change the value to "yes". The record value
which you do not want to delete must remain in "no".
When you press the Set button, only records with the value "yes" will be deleted and the Figure-37
comes to the screen. You can scroll through the parameters in the menu by pressing the right button
or you can exit the menu by pressing the Esc key.
Figure-37
Out1
Din1 Out2
Figure-44
Out1
Din1 Out2
Note: If the cable length in the RS485 communication line is too high (>100m), connect the 120R resistor
parallel to the A-B (RS-485) terminal of the begin and end of the communication line to avoid data loss.

17 - Assigning Tasks to Relay1 and Relay2:
Parameters (Par): Voltage ( ULn ), current ( ILn ), total current ( ILt ), total harmonic distortion belong to
Voltage ( thdV ), total harmonic distortion belong to Current ( thdI ), power factor ( PF ), voltage Unbalance
( U Un ), current Unbalance ( I Un ), digital input ( dI n ) and off ( OFF ).
Function (Fun): Functions to be applied for parameters: if greater than value ( hI ) and smaller
than value ( LO ).
Value(Val): The value to be set for the parameters.
Delay Time (dLY): When the conditions set for the relay have occurred or disappeared, it is time to
wait for the relay to gets energised on or de-energised.
Hysteresis Value (HIS): The tolerance value entered for the set value for energizing or de-energizing
the relay when the condition set for the relay has disappeared.
Example: High voltage is 250V and hysteresis value is 5V. When 250V voltage is applied to the device,
the device will enter into to error. The voltage will have to drop to 245V to get out of the error.
(High Voltage Set Value - Hysteresis Value)
Note1: The task assignment of relay 2 is assigned in the same way as relay 1. While in menu for relay 2
assignment. The enterance should be done from the figure-42.
Note2: To use the digital input parameter, 9V-24DC energy should be applied from the enterance of input
to the device. In these parameters if the relay is wanted to be pulled HI function; or if it is wanted to be
pulled while the energy is not available LO function should be chosen. The change of the voltage at the data
input should be minimum at one second (1Hz)
Example: If the voltage value exceeds 250V, the relay 1 gets energised after 5 seconds. De-energised
after 5 seconds when voltage value falling to 245.
Parameter (PAr) = ULn, function (fun) = hI, value (VAL) = 250V, delay time (dLY) = 5 seconds and
hysteresis value (HIS) = 5V should be set. If the relay is set in this way, the relay 1 is gets energised after
5 seconds when the voltage rises above 250V. When the voltage drops to 245V, the relay is de-energized
after 5 seconds.
-11-
To assign the task to relay 1, press the set key, when figure-39 is on the screen. The Figure-46 comes
to the screen. There are 5 settings; these are Parameter (PAr), Function (Fun), Value (VAL), Delay Time
(dLY) and Hysteresis Value (HIS). Press the right key to move the point (.) to the parameter. Press the
down key to bring up the desired parameter. Then press the right key to move the point (.) to the
function. Press the down key to set the function to low or high set. Press the right key to move the point
(.) to value. Press the down key to enter the desired value. Press the right key to move the point (.) to
waiting time. Press the down key to enter the desired value. Press the right key to move the point (.) to
hysteresis value. Press the down key to enter the desired value. Then when you press the set key, the
task will be assigned to relay 1 and Figure-39 comes to screen. You can scroll through the parameters
in the menu by pressing the right button or you can exit the menu by pressing the Esc key.
Figure-39
Out1
Din1 Out2
Figure-46
Out1
Din1 Out2
Figure-47
Out1
Din1 Out2
Figure-39
Out1
Din1 Out2
16- Enter Password Value:
Figure-45
Out1
Din1 Out2
Figure-38
Out1
Din1 Out2
In order to change password; press set button while
Figure-38 is on the screen. The Figure-45 comes to the
screen. In order to pass through steps; press the button
on the right. In order to change the value of the step
press the ''down'' button. You can change the step
value with underline. If you press the set key after
entering the password, the password is saved and the
screen comes in figure-38. Pressing the right key;
-12-
18 - Menu Values Table:
Parameter Minimum
Value
Factory
Value
Unit Maximum
Value
Parameter
Number
5000
0.99
No
2
-
247
No
38400
High
999.0
50
50
9999
50
50
1
0.50
Yes
1
-
None, Even, Odd
1
Yes
1200
Low
0.1
1
OFF, Uln, Iln, Ilt, thdU,
thdI, PF, U Un, I Un, dI n
1
0
1
1
1
0.50
No
1
8
none
1
No
9600
High
vtr x 10 vtr x 10 vtr x 500
(ctrx10)/100
1.0
1
OFF
1
0
(ctrx3x10)/100 (ctrx3x10)/100
1
1
-
%
-
-
-
-
-
-
bps
-
Volt
Amper
-
%
-
%
-
Amper
%
%
Ctr
dE
-
-
-
Id
En
Fun
UAL
Vtr
Par
br
PASS
Current Transformer Ratio
PF (Power Factor)
Deleting Demand Values
Baudrate
I Un (Current Imbalance)
Password
Deleting Total Energy
Stop bits
Data bits
Parity
ModBus ID
Function
Uln (voltage)
Iln (Current)
Ilt (Total Current)
thdU (Total Voltage Har.)
thdl (Total Current Har.)
Voltage Transformer Ratio
U Un (Voltage imbalance)
Parameter
(ctrx10)/100 (ctrx500)/100
(ctrx3x500)/100
19- Dimensions:
97,5 mm
96,5 mm
56,75 mm
65 mm
96,5 mm
89,5 mm
12mm
5,08 mm
10001
0
second
dLY Delay Time
101
0
Volt, Amper, %
HIS Hysteresis Value
you can pass through the parameters in the menu or pressing ''Esc'' key; you can quit the menu.

17 - Assigning Tasks to Relay1 and Relay2:
Parameters (Par): Voltage ( ULn ), current ( ILn ), total current ( ILt ), total harmonic distortion belong to
Voltage ( thdV ), total harmonic distortion belong to Current ( thdI ), power factor ( PF ), voltage Unbalance
( U Un ), current Unbalance ( I Un ), digital input ( dI n ) and off ( OFF ).
Function (Fun): Functions to be applied for parameters: if greater than value ( hI ) and smaller
than value ( LO ).
Value(Val): The value to be set for the parameters.
Delay Time (dLY): When the conditions set for the relay have occurred or disappeared, it is time to
wait for the relay to gets energised on or de-energised.
Hysteresis Value (HIS): The tolerance value entered for the set value for energizing or de-energizing
the relay when the condition set for the relay has disappeared.
Example: High voltage is 250V and hysteresis value is 5V. When 250V voltage is applied to the device,
the device will enter into to error. The voltage will have to drop to 245V to get out of the error.
(High Voltage Set Value - Hysteresis Value)
Note1: The task assignment of relay 2 is assigned in the same way as relay 1. While in menu for relay 2
assignment. The enterance should be done from the figure-42.
Note2: To use the digital input parameter, 9V-24DC energy should be applied from the enterance of input
to the device. In these parameters if the relay is wanted to be pulled HI function; or if it is wanted to be
pulled while the energy is not available LO function should be chosen. The change of the voltage at the data
input should be minimum at one second (1Hz)
Example: If the voltage value exceeds 250V, the relay 1 gets energised after 5 seconds. De-energised
after 5 seconds when voltage value falling to 245.
Parameter (PAr) = ULn, function (fun) = hI, value (VAL) = 250V, delay time (dLY) = 5 seconds and
hysteresis value (HIS) = 5V should be set. If the relay is set in this way, the relay 1 is gets energised after
5 seconds when the voltage rises above 250V. When the voltage drops to 245V, the relay is de-energized
after 5 seconds.
-11-
To assign the task to relay 1, press the set key, when figure-39 is on the screen. The Figure-46 comes
to the screen. There are 5 settings; these are Parameter (PAr), Function (Fun), Value (VAL), Delay Time
(dLY) and Hysteresis Value (HIS). Press the right key to move the point (.) to the parameter. Press the
down key to bring up the desired parameter. Then press the right key to move the point (.) to the
function. Press the down key to set the function to low or high set. Press the right key to move the point
(.) to value. Press the down key to enter the desired value. Press the right key to move the point (.) to
waiting time. Press the down key to enter the desired value. Press the right key to move the point (.) to
hysteresis value. Press the down key to enter the desired value. Then when you press the set key, the
task will be assigned to relay 1 and Figure-39 comes to screen. You can scroll through the parameters
in the menu by pressing the right button or you can exit the menu by pressing the Esc key.
Figure-39
Out1
Din1 Out2
Figure-46
Out1
Din1 Out2
Figure-47
Out1
Din1 Out2
Figure-39
Out1
Din1 Out2
16- Enter Password Value:
Figure-45
Out1
Din1 Out2
Figure-38
Out1
Din1 Out2
In order to change password; press set button while
Figure-38 is on the screen. The Figure-45 comes to the
screen. In order to pass through steps; press the button
on the right. In order to change the value of the step
press the ''down'' button. You can change the step
value with underline. If you press the set key after
entering the password, the password is saved and the
screen comes in figure-38. Pressing the right key;
-12-
18 - Menu Values Table:
Parameter Minimum
Value
Factory
Value
Unit Maximum
Value
Parameter
Number
5000
0.99
No
2
-
247
No
38400
High
999.0
50
50
9999
50
50
1
0.50
Yes
1
-
None, Even, Odd
1
Yes
1200
Low
0.1
1
OFF, Uln, Iln, Ilt, thdU,
thdI, PF, U Un, I Un, dI n
1
0
1
1
1
0.50
No
1
8
none
1
No
9600
High
vtr x 10 vtr x 10 vtr x 500
(ctrx10)/100
1.0
1
OFF
1
0
(ctrx3x10)/100 (ctrx3x10)/100
1
1
-
%
-
-
-
-
-
-
bps
-
Volt
Amper
-
%
-
%
-
Amper
%
%
Ctr
dE
-
-
-
Id
En
Fun
UAL
Vtr
Par
br
PASS
Current Transformer Ratio
PF (Power Factor)
Deleting Demand Values
Baudrate
I Un (Current Imbalance)
Password
Deleting Total Energy
Stop bits
Data bits
Parity
ModBus ID
Function
Uln (voltage)
Iln (Current)
Ilt (Total Current)
thdU (Total Voltage Har.)
thdl (Total Current Har.)
Voltage Transformer Ratio
U Un (Voltage imbalance)
Parameter
(ctrx10)/100 (ctrx500)/100
(ctrx3x500)/100
19- Dimensions:
97,5 mm
96,5 mm
56,75 mm
65 mm
96,5 mm
89,5 mm
12mm
5,08 mm
10001
0
second
dLY Delay Time
101
0
Volt, Amper, %
HIS Hysteresis Value
you can pass through the parameters in the menu or pressing ''Esc'' key; you can quit the menu.

85V - 300V AC
50 / 60 Hz
<10VA
-20ºC.....55ºC
5V -330V AC
5V - 330kV
10mA - 5.5A
10mA - 5.500A
%±0.5
%±1
%±2
3P4W
1....1000
1,0....999,9
3 - 31
3 - 31
Plug-in terminal connection
2x 3A/250VAC (Resistive Load)
1x 9V - 24VDC
1.5mm²
Front panel mountings
<2000meters
<300Gr.
IP41(Front Panel), IP20(Body)
91mm x 91mm
RS485 MODBUS RTU
71.5 x 61.5mm Glass LCD
Operating Frequency
Operating Power
Operating Temperature
Voltage Inputs
Voltage Meas. Range
Current Input
Current Meas. Range
Voltage, Current Accuracy
Active Energy Accuracy
Reactive Energy Accuracy
Supported Connection
Current Transformer Ratio
Voltage Transformer Ratio
Harmonic Voltage Meas.
Harmonic Current Meas.
Connection Type
Relay Output
Digital Input
Operating Voltage
Cable Diameter
Mounting
Operating Altitude
Weight
Protection Class
Panel Hole Sizes
Communication
Display
-13-
20 - Technical Specifications:
9
13
13
13
12
12
11
10
10
10
10
8
5
4
3
2
2
2
2
2
PageSubject:
1 - Connection Diagrams:
2 - Matters to be considered in current transformer
selection and connection:
3 - Warnings:
4 - Device Maintenance:
5 - General:
6 - First Operation of the Device:
7 - Screen Presentation:
8 - Button Presentation:
9 - Progress on Screen Information:
10 - Fast Progress on Screen Infortmation:
1
11 - Menu Structure:
12 - Set up the Current Transformer Ratio :
13 - Set up the Voltage Transformer Ratio :
14 - Remote Communication Settings of RS485:
15 - Delete Energy and Demand Records:
16 - Enter Password Value:
18 - Menu Values Table:
19 - Dimensions:
20 - Technical Specifications:
21 - Index:
22 - Contact Information:
21 - Index:
Baudrate 1200bps - 38400bps
Stop Bit 1 or 2
Parity None, Even, Odd
11
17 - Assigning Tasks to Relay1 and Relay2:
|
Energy and
Compensation
Tracking System
www.tenseenerji.com
22 - Contact Information:
Muratpaşa Mah. Uluyol Cad.
İşkent Sanayi Sitesi, E-Blok, 1. Kat
GAZİOSMANPAŞA / İSTANBUL / TÜRKİYE
Tel: 0212 578 04 38 - 48 | Fax: 0212 578 04 36
|
Table of contents
Other Tense Measuring Instrument manuals