Terex T120P User manual

Service Manual
Serial numbers
T7009-000101
T9009-000101
T12009-000101
and above
T70C
T70P
T90C
T90P
T120C
T120P
Part No. 134277
Rev A
November 2008
with
Maintenance
Information

November 2008
T70, T90 & T120 Super Quiet Generator Part No. 134277
ii
Important
Read, understand and obey the safety rules and
operating instructions in the appropriate Operator's
Manual on your machine before attempting any
maintenance procedure.
Basic mechanical, hydraulic and electrical
skills are required to perform most procedures.
However, several procedures require specialized
skills, tools, lifting equipment and a suitable
workshop. In these instances, we strongly
recommend that maintenance and repair be
performed at an authorized TEREX dealer
service center.
Technical Publications
TEREX Corporation has endeavored to deliver the
highest degree of accuracy possible. However,
continuous improvement of our products is a
TEREX policy. Therefore, product specifications
are subject to change without notice.
Readers are encouraged to notify TEREX of errors
and send in suggestions for improvement. All
communications will be carefully considered for
future printings of this and all other manuals.
Copyright © 2008 by TEREX Corporation
134277 Rev A November 2008
First Edition, First Printing
"TEREX" is a registered trademark of TEREX
Corporation in the USA and many other countries.
"Super Quiet" is a trademark of TEREX
Corporation.
Printed on recycled paper
Printed in U.S.A.
Contact Us:
www.TEREX.com
Serial Number Information
TEREX Corporation offers the following manuals
for these models:
Title Part No.
TEREX T70, T90 & T120 Operator's Manual, .... 134207
First Edition
TEREX T70, T90 & T120 Service Manual, ......... 134277
First Edition
TEREX T70, T90 & T120 Parts Manual, ............. 134234
First Edition
Newage Generator Manual ................................. 836430
Cummins Engine Manual .................................... 839059
Cummins Engine Manual .................................... 839060
Perkins Engine Manual ....................................... 839019
Cascade Controller Manual ................................ 833011
Cummins Controller Manual ............................ 900-0661
Dexter Axle Manual ............................................. 833014
Introduction

November 2008
Part No. 134277 T70, T90 & T120 Super Quiet Generator
Serial Number Legend
The serial number plate on your T70, T90 & T120
Super Quiet Generator is located on the twist lock
area of the lower control panel.
iii
How to Read Your Serial Number

November 2008
T70, T90 & T120 Super Quiet Generator Part No. 134277
This page intentionally left blank.
iv

November 2008
Part No. 134277 T70, T90 & T120 Super Quiet Generator v
Danger
Failure to obey the instructions and safety rules
in this manual and the appropriate Operator's
Manual on your machine will result in death or
serious injury.
Many of the hazards identified in the
operator’s manual are also safety hazards
when maintenance and repair procedures
are performed.
Do Not Perform Maintenance
Unless:
You are trained and qualified to perform
maintenance on this machine.
You read, understand and obey:
- manufacturer’s instructions and safety rules
- employer’s safety rules and worksite
regulations
- applicable governmental regulations
You have the appropriate tools, lifting
equipment and a suitable workshop.
Safety Rules
Section 1 • Safety Rules

November 2008
T70, T90 & T120 Super Quiet Generator Part No. 134277
SAFETY RULES
vi
Section 1 • Safety Rules
Personal Safety
Any person working on or around a machine must
be aware of all known safety hazards. Personal
safety and the continued safe operation of the
machine should be your top priority.
Read each procedure thoroughly. This
manual and the decals on the machine,
use signal words to identify the following:
Safety alert symbol—used to alert
personnel to potential personal
injury hazards. Obey all safety
messages that follow this symbol
to avoid possible injury or death.
Indicates an imminently hazardous
situation which, if not avoided, will
result in death or serious injury.
Indicates a potentially hazardous
situation which, if not avoided,
could result in death or serious
injury.
Indicates a potentially hazardous
situation which, if not avoided,
may cause minor or moderate
injury.
Indicates a property damage
message.
Be sure to wear protective eye wear and
other protective clothing if the situation
warrants it.
Be aware of potential crushing hazards
such as moving parts, free swinging or
unsecured components when lifting or
placing loads. Always wear approved steel-toed
shoes.
Workplace Safety
Be sure to keep sparks, flames and
lighted tobacco away from flammable and
combustible materials like battery gases
and engine fuels. Always have an approved fire
extinguisher within easy reach.
Be sure that all tools and working areas
are properly maintained and ready for
use. Keep work surfaces clean and free of
debris that could get into machine components and
cause damage.
Be sure any forklift, overhead crane or
other lifting or supporting device is fully
capable of supporting and stabilizing the
weight to be lifted. Use only chains or straps that
are in good condition and of ample capacity.
Be sure that fasteners intended for one
time use (i.e., cotter pins and self-locking
nuts) are not reused. These components
may fail if they are used a second time.
Be sure to properly dispose of old oil or
other fluids. Use an approved container.
Please be environmentally safe.
Be sure that your workshop or work area
is properly ventilated and well lit.

November 2008
Part No. 134277 T70, T90 & T120 Super Quiet Generator
Table of Contents
Introduction
Important Information - Introduction ................................................................... ii
How to Read Your Serial Number ..................................................................... iii
Parts Stocking List ............................................................................................ x
How to Order Parts ........................................................................................... xi
Service Parts Fax Order Form ......................................................................... xii
Section 1 Safety Rules
General Safety Rules ........................................................................................ v
Section 2 Rev Specifications
A T70C Specifications ..................................................................................... 2 - 1
A T70C Specifications (Continued) ................................................................. 2 - 2
A T70P Specifications ..................................................................................... 2 - 3
A T70P Specifications (Continued) .................................................................. 2 - 4
A T90C Specifications ..................................................................................... 2 - 5
A T90C Specifications (Continued) ................................................................. 2 - 6
A T90P Specifications ..................................................................................... 2 - 7
A T90P Specifications (Continued) .................................................................. 2 - 8
A T120C Specifications ................................................................................... 2 - 9
A T120C Specifications (Continued) ............................................................. 2 - 10
A T120P Specifications ................................................................................. 2 - 11
A T120P Specifications (Continued) .............................................................. 2 - 12
A Torque Specifications ................................................................................ 2 - 13
A Generator Torque Specifications ............................................................... 2 - 14
vii

November 2008
T70, T90 & T120 Super Quiet Generator Part No. 134277
TABLE OF CONTENTS
Section 3 Rev Scheduled Maintenance Procedures
Introduction .................................................................................................. 3 - 1
Pre-delivery Preparation Report................................................................... 3 - 2
AMaintenance Schedules
Cummins Lubrication and Maintenance Service Intervals ............................ 3 - 3
Perkins Lubrication and Maintenance Service Intervals ............................... 3 - 4
Newage Generators Maintenance Schedule ................................................ 3 - 5
Section 4 Rev Troubleshooting
Introduction .................................................................................................. 4 - 1
A Troubleshooting Guide................................................................................. 4 - 2
Section 5 Rev Schematics
A Introduction .................................................................................................. 5 - 1
A Electrical Schematic - Control Panel Wiring for
Murphy Cascade Controller ......................................................................... 5 - 2
A Electrical Schematic - Distribution Panel Wiring ........................................... 5 - 3
A Electrical Schematic - Stack Switch ............................................................. 5 - 4
A Electrical Schematic- Overcurrent Relay ..................................................... 5 - 5
A Electrical Schematic - Standard Generator Wiring ....................................... 5 - 6
A Electrical Schematic - Idle-Run Wiring (Cummins) ....................................... 5 - 7
viii

November 2008
Part No. 134277 T70, T90 & T120 Super Quiet Generator
Required Parts
The following parts are required to perform
maintenance procedures as outlined in the
TEREX T70, T90 and T120 Parts and Service
Manuals.
Description Part No.
Cummins QSM11G4 Models
Oil Filter .............................................................. 125550
Air Filter - Primary .............................................. 125561
Air Filter - Secondary ......................................... 125562
Fuel Filter ........................................................... 125551
Belt ..................................................................... 125552
Parts Stocking List
ix

November 2008
T70, T90 & T120 Super Quiet Generator Part No. 134277
x
This page intentionally left blank.

November 2008
Part No. 134277 T70, T90 & T120 Super Quiet Generator
Machine Information
Model
Serial Number
Date of Purchase
Authorized TEREX Distributor
Phone Number
Please be prepared with the following information
when ordering replacement parts for your TEREX
product:
Machine model number
Machine serial number
Terex part number
Part description and quantity
Purchase order number
"Ship to" address
Desired method of shipment
Name and telephone number of the
authorized TEREX Distributor in your area
Use the Service Parts Fax Order Form on the
next page and fax your order to our Parts
Department.
If you don't know the name of your authorized
distributor, or if your area is not currently serviced
by an authorized distributor, please call TEREX
Corporation.
How To Order Parts
TEREX North America
Telephone (803) 324-3011
Toll Free (800) 433-3026 in U.S.A. and Canada
Fax (803) 366-1101
xi

November 2008
T70, T90 & T120 Super Quiet Generator Part No. 134277
Part Number Description Quantity Price
All backordered parts will be shipped when available via the same ship method as the original order
unless noted below:
oShip complete order only - no backorders
oShip all available parts and contact customer on disposition of backordered parts
oOther (please specify)
Please fill out completely
Date _________________________________ Account Number _______________________________
Your Name ______________________________ Your Fax Number _____________________________
_________________________________ Your Phone Number ____________________________
Bill To _________________________________ Ship To ___________________________________
_________________________________ ___________________________________
_________________________________ ___________________________________
_________________________________ ___________________________________
Purchase Order Number ____________________ Ship Via ___________________________________
Model(s) ______________________________________________________ Serial No.(s) _________________
Optional Equipment __________________________________________________________________________
FOR TEREX USE ONLY
Order Number ______________ Origin Code ________________ Comments _________________________
Date Scheduled ____________ Ship Condition ______________ __________________________________
Order Total ________________ Terms Code ________________ __________________________________
remove this page and make copies remove this page and make copies
Service Parts fax Order Form
FAX TO: (800) 633-5534 OR TOLL FREE: 800-433-3026

REV A
Part No. 134277 T70, T90 & T120 Super Quiet Generator 2 - 1
Section 2 • Specifications
November 2008
Specifications
T70C Specifications
System power output
Prime 3 phase power 69 kVA / 55 kW
Standby 3 phase power 75 kVA / 60 kW
Available 3 phase voltage 208 / 220 / 240 / 440 / 480
Associated 3 phase amps 191 / 181 / 166 / 90 / 83
(0.8 power factor)
Prime 1 phase power 42 kW
Prime 1 phase kVA 42 kVA
Available 1 phase voltage 120 / 240
Associated 1 phase amps 350 / 175
(1.0 power factor)
Max amp rating (main breaker size) 225 A
Engine specifications
Manufacturer Cummins
Model QSB5-G1 NR3
Horsepower - prime (1,800 rpm) 91 hp (68 kWm)
Description 4 cylinder, 4-cycle, water cooled,
OHV, in-line, direct injection,
turbocharged and charge air cooled
Bore & stroke 4.21 x 4.88 in / 107 x 124 mm
Piston displacement 275 in3/ 4.5 L
Compression ratio 17.3 : 1
Monitoring gauges oil pressure, water temperature,
fuel level, battery voltage, hours
Coolant capacity - engine only 9.6 qts / 9.0 L
Cooling system liquid cooled - rated
to 105° F (41° C) ambient
Continuous improvement of our products is a Terex
policy. Product specifications are subject to change
without notice or obligation.
Fuel system
Specification #2 diesel
Filter fuel / water separator
Capacity 160 gal / 606 L
Tank and containment internal fuel tank with 110%
fluid spill containment
Fuel consumption (run time)
Full load 5.6 gal per hr / 21.0 L per hr 28 hr
¾ load 4.5 gal per hr / 17.0 L per hr 35 hr
Half load 3.0 gal per hr / 11.0 L per hr 53 hr
System Controls and Distribution
Engine governor electronic (+/- 0.5%)
Protection low oil pressure, high water temp.,
(safety shutdowns) overcrank, overspeed
& underspeed
Generator gauges voltmeter, ammeter,
Hz meter
Receptacles, 120 V 2 Each 20 Amp GFCI Duplex
Receptacles, 240 V 3 Each 50 Amp Tempower T/L
Primary Distribution 5 lug terminals with
mainline circuit breaker
Generator specifications
Manuafacturer Stamford
Model UCI224FIL73D
Rating 60 kW 3 Phase @ 480 / 240 V
(0.8 power factor)
Description brushless, 4 pole, synchronous,
single bearing
Insulation Class H
Temperature rating 125° C rise over 40° C ambient
Automatic voltage regulator external, solid state,
adjustable
Voltage regulation +/- 1%
Frequency (speed) 60 Hz / 1,800 RPM

REV A
2 - 2 T70, T90 & T120 Super Quiet Generator Part No. 134277
Section 2 • Specifications November 2008
SPECIFICATIONS
Packaging
Enclosure sound attenuated, weatherproof
with lockable doors
Sound levels 66 dBA at 23 ft / 7 meters
Lifting system roof mounted, single point
Weight (no trailer) empty 5,390 lbs / 2,445 kg
full 6,782 lbs / 3,076 kg
Dimensions - L x W x H 110 x 47 x 64 in
(no trailer) 279 x 119 x 162 cm
Weight (with trailer) empty 6,887 lbs / 3,124 kg
full 8,279 lbs / 3,755 kg
Dimensions - L x W x H 171 x 75 x 82 in
(with trailer) 434 x 190 x 208 cm
T70 Trailer
Tire 225/75R15
Tongue weight electric brakes - 884 lbs / 401 kg
hydraulic brakes - 631 lbs / 286.2 kg
Trailer weight electric brakes - 1023 lbs / 464 kg
hydraulic brakes - 1110 lbs / 503.5 kg
T70C SPECIFICATIONS CONTINUED

REV A
Part No. 134277 T70, T90 & T120 Super Quiet Generator 2 - 3
Section 2 • Specifications
November 2008
SPECIFICATIONS
T70P Specifications
System power output
Prime 3 phase power 70 kVA / 54 kW
Standby 3 phase power 74 kVA / 59 kVA
Available 3 phase voltage 208 / 220 / 240 / 440 / 480
Associated 3 phase amps 188 / 177 / 163 / 89 / 81
(0.8 power factor)
Prime 1 phase power 42 kW
Prime 1 phase kVA 42 kVA
Available 1 phase voltage 120 / 240
Associated 1 phase amps 350 / 175
(1.0 power factor)
Max amp rating (main breaker size) 225 A
Engine specifications
Manufacturer Perkins
Model 1104DE-44TG1
Horsepower - prime (1,800 rpm) 78 hp (58 kWm)
Description 4 cylinder, 4-cycle, water cooled,
OHV, in-line, direct injection,
turbocharged
Bore & stroke 4.13 x 5.00 in / 105 x 127 mm
Piston displacement 269 in3/ 4.41 L
Compression ratio 18.2 : 1
Monitoring gauges oil pressure, water temperature,
fuel level, battery voltage, hours
Coolant capacity - engine only 7.4 qts / 7.0 L
Cooling system liquid cooled - rated
to 105° F (41° C) ambient
Fuel system
Specification #2 diesel
Filter fuel / water separator
Capacity 160 gal / 606 L
Tank and containment internal fuel tank with 110%
fluid spill containment
Fuel consumption (run time)
Full load 4.4 gal per hr / 16.6 L per hr 36 hr
¾ load 3.4 gal per hr / 12.8 L per hr 47 hr
Half load 2.4 gal per hr / 9.0 L per hr 67 hr
System Controls and Distribution
Engine governor electronic (+/- 0.5%)
Protection low oil pressure, high water temp.,
(safety shutdowns) overcrank, overspeed
& underspeed
Generator gauges voltmeter, ammeter,
Hz meter
Receptacles, 120 V 2 Each 20 Amp GFCI Duplex
Receptacles, 240 V 3 Each 50 Amp Tempower T/L
Primary Distribution 5 lug terminals with
mainline circuit breaker
Generator specifications
Manufacturer Stamford
Model UCI224EIL73D
Rating 60 kW 3 Phase @ 480 / 240 V
(0.8 power factor)
Description brushless, 4 pole, synchronous,
single bearing
Insulation Class H
Temperature rating 125° C rise over 40° C ambient
Automatic voltage regulator external, solid state,
adjustable
Voltage regulation +/- 1%
Frequency (speed) 60 Hz / 1,800 RPM
Continuous improvement of our products is a Terex
policy. Product specifications are subject to change
without notice or obligation.

REV A
2 - 4 T70, T90 & T120 Super Quiet Generator Part No. 134277
Section 2 • Specifications November 2008
SPECIFICATIONS
Packaging
Enclosure sound attenuated, weatherproof
with lockable doors
Sound levels 66 dBA at 23 ft / 7 meters
Lifting system roof mounted, single point
Weight (no trailer) empty 5,390 lbs / 2,445 kg
full 6,782 lbs / 3,076 kg
Dimensions - L x W x H 110 x 47 x 64 in
(no trailer) 279 x 119 x 162 cm
Weight (with trailer) empty 6,887 lbs / 3,124 kg
full 8,279 lbs / 3,755 kg
Dimensions - L x W x H 171 x 75 x 82 in
(with trailer) 434 x 190 x 208 cm
T70 Trailer
Tire 225/75R15
Tongue weight electric brakes - 884 lbs / 401 kg
hydraulic brakes - 631 lbs / 286.2 kg
Trailer weight electric brakes - 1023 lbs / 464 kg
hydraulic brakes - 1110 lbs / 503.5 kg
T70P SPECIFICATIONS CONTINUED

REV A
Part No. 134277 T70, T90 & T120 Super Quiet Generator 2 - 5
Section 2 • Specifications
November 2008
SPECIFICATIONS
T90C Specifications
System power output
Prime 3 phase power 90 kVA / 72 kW
Standby 3 phase power 100 kVA / 80 kW
Available 3 phase voltage 208 / 220 / 240 / 440 / 480
Associated 3 phase amps 250 / 236 / 217 / 118 / 108
(0.8 power factor)
Prime 1 phase power 59 kW
Prime 1 phase kVA 59 kVA
Available 1 phase voltage 120 / 240
Associated 1 phase amps 492 / 246
(1.0 power factor)
Max amp rating (main breaker size) 300 A
Engine specifications
Manufacturer Cummins
Model QSB5-G2 NR3
Horsepower - prime (1,800 rpm) 103 hp (77 kWm)
Description 4 cylinder, 4-cycle, water cooled,
OHV, in-line, direct injection,
turbocharged and charge air cooled
Bore & stroke 4.21 x 4.88 in / 107 x 124 mm
Piston displacement 275 in3/ 4.5 L
Compression ratio 17.2 : 1
Monitoring gauges oil pressure, water temperature,
fuel level, battery voltage, hours
Coolant capacity - engine only 10.0 qts / 9.5 L
Cooling system liquid cooled - rated
to 105° F (41° C) ambient
Fuel system
Specification #2 diesel
Filter fuel / water separator
Capacity 160 gal / 606 L
Tank and containment internal fuel tank with 110%
fluid spill containment
Fuel consumption (run time)
Full load 6.0 gal per hr / 23.0 L per hr 26 hr
¾ load 5.0 gal per hr / 19.0 L per hr 32 hr
Half load 3.4 gal per hr / 13.0 L per hr 47 hr
System Controls and Distribution
Engine governor electronic (+/- 0.5%)
Protection low oil pressure, high water temp.,
(safety shutdowns) overcrank, overspeed
& underspeed
Generator gauges voltmeter, ammeter,
Hz meter
Receptacles, 120 V 2 Each 20 Amp GFCI Duplex
Receptacles, 240 V 3 Each 50 Amp Tempower T/L
Primary Distribution 5 lug terminals with
mainline circuit breaker
Generator specifications
Manuafacturer Stamford
Model UCI274CIL32D
Rating 60 kW 3 Phase @ 480 / 240 V
(0.8 power factor)
Description brushless, 4 pole, synchronous,
single bearing
Insulation Class H
Temperature rating 125° C rise over 40° C ambient
Automatic voltage regulator external, solid state,
adjustable
Voltage regulation +/- 1%
Frequency (speed) 60 Hz / 1,800 RPM
Continuous improvement of our products is a Terex
policy. Product specifications are subject to change
without notice or obligation.

REV A
2 - 6 T70, T90 & T120 Super Quiet Generator Part No. 134277
Section 2 • Specifications November 2008
SPECIFICATIONS
Packaging
Enclosure sound attenuated, weatherproof
with lockable doors
Sound levels 66 dBA at 23 ft / 7 meters
Lifting system roof mounted, single point
Weight (no trailer) empty 5,390 lbs / 2,445 kg
full 6,782 lbs / 3,076 kg
Dimensions - L x W x H 110 x 47 x 64 in
(no trailer) 279 x 119 x 162 cm
Weight (with trailer) empty 6,887 lbs / 3,124 kg
full 8,279 lbs / 3,755 kg
Dimensions - L x W x H 171 x 75 x 82 in
(with trailer) 434 x 190 x 208 cm
T90 Trailer
Tire 225/75R15
Tongue weight electric brakes - 903 lbs / 410 kg
hydraulic brakes - 645 lbs / 293 kg
Trailer weight electric brakes - 1023 lbs / 464 kg
hydraulic brakes - 1110 lbs / 503.5 kg
T90C SPECIFICATIONS CONTINUED

REV A
Part No. 134277 T70, T90 & T120 Super Quiet Generator 2 - 7
Section 2 • Specifications
November 2008
SPECIFICATIONS
T90P Specifications
System power output
Prime 3 phase power 90 kVA / 72 kW
Standby 3 phase power 100 kVA / 80 kW
Available 3 phase voltage 208 / 220 / 240 / 440 / 480
Associated 3 phase amps 250 / 236 / 217 / 118 / 108
(0.8 power factor)
Prime 1 phase power 59 kW
Prime 1 phase kVA 59 kVA
Available 1 phase voltage 120 / 240
Associated 1 phase amps 492 / 246
(1.0 power factor)
Max amp rating (main breaker size) 300 A
Engine specifications
Manufacturer Perkins
Model 1104D-E44TAG1
Horsepower - prime (1,800 rpm) 110 hp / 82 kWm
Description 4 cylinder, 4-cycle, water cooled,
OHV, in-line, direct injection,
turbocharged and charge air cooled
Bore & stroke 4.13 x 5.00 in / 105 x 127 mm
Piston displacement 269 in3/ 4.41 L
Compression ratio 16.2 : 1
Monitoring gauges oil pressure, water temperature,
fuel level, battery voltage, hours
Coolant capacity - engine only 7.4 qts. / 7.0 L
Cooling system liquid cooled - rated
to 105° F (41° C) ambient
Fuel system
Specification #2 diesel
Filter fuel / water separator
Capacity 160 gal / 606 L
Tank and containment internal fuel tank with 110%
fluid spill containment
Fuel consumption (run time)
Full load 6.3 gal per hr / 23.7 L per hr 25 hr
¾ load 4.9 gal per hr / 18.7 L per hr 32 hr
Half load 3.5 gal per hr / 13.5 L per hr 45 hr
System Controls and Distribution
Engine governor electronic (+/- 0.5%)
Protection low oil pressure, high water temp.,
(safety shutdowns) overcrank, overspeed,
underspeed
Generator gauges voltmeter, ammeter,
Hz meter
Receptacles, 120 V 2 Each 20 Amp GFCI Duplex
Receptacles, 240 V 3 Each 50 Amp Tempower T/L
Primary Distribution 5 lug terminals with
mainline circuit breaker
Generator specifications
Manufacturer Stamford
Model UCI274CIL32D
Rating 83 kW 3 Phase @ 480 / 240 V
(0.8 power factor)
Description brushless, 4 pole, synchronous,
single bearing
Insulation Class H
Temperature rating 125° C rise over 40° C ambient
Automatic voltage regulator external, solid state,
adjustable
Voltage regulation +/- 1%
Frequency (speed) 60 Hz / 1,800 RPM
Continuous improvement of our products is a Terex
policy. Product specifications are subject to change
without notice or obligation.

REV A
2 - 8 T70, T90 & T120 Super Quiet Generator Part No. 134277
Section 2 • Specifications November 2008
SPECIFICATIONS
Packaging
Enclosure sound attenuated, weatherproof
with lockable doors
Sound levels 66 dBA at 23 ft / 7 meters
Lifting system roof mounted, single point
Weight (no trailer) empty 5,390 lbs / 2,445 kg
full 6,782 lbs / 3,076 kg
Dimensions - L x W x H 110 x 47 x 64 in
(no trailer) 279 x 119 x 162 cm
Weight (with trailer) empty 6,887 lbs / 3,124 kg
full 8,279 lbs / 3,755 kg
Dimensions - L x W x H 171 x 75 x 82 in
(with trailer) 434 x 190 x 208 cm
T90 Trailer
Tire 225/75R15
Tongue weight electric brakes - 903 lbs / 410 kg
hydraulic brakes - 645 lbs / 293 kg
Trailer weight electric brakes - 1023 lbs / 464 kg
hydraulic brakes - 1110 lbs / 503.5 kg
T90P SPECIFICATIONS CONTINUED