MEC 310 APPLICATION NOTES - External I/O Modules
PM104 R0 09/08/20 Page 13 THOMSON TECHNOLOGY
Diagnostic LEDs
The Beckhoff controllers have LEDs for display of status. They can be used for fault finding.
CAN ERR blink code
CAN ERR Meaning
Off CANbus has no errors.
Fast blinking
(Approx. 50ms on, approx. 50ms off;
alternating with RUN LED).
Automatic Baud rate detection has not yet
found a valid Baud rate. Not enough
telegrams on the bus yet.
1 x flash
(Approx. 200ms on, 1s off).
CAN warning limit exceeded.There are too
many error frames on the bus. Please check
the wiring (e.g. termination resistors, screens,
conductor length, stubs). Other possible
causes for exceeding the warning limit: There
are no other participating devices in the
network (occurs e.g. when the first node is
started).
2 x blinking
(Each approx. 200ms on, 200ms off, followed
by a 1s pause).
The guarding or heartbeat monitor has
alerted, because neither guarding telegrams
nor heartbeat telegrams are received.
Precondition for guarding monitoring: Guard
time and life time factors are > 0.
Precondition for heartbeat monitoring:
Consumer heartbeat > 0).
The bus coupler is pre-operational (PDOs
switched off), and the outputs are in the error
state.
3 x blinking
(Each approx. 200ms on, 200ms off, followed
by a 1s pause).
A synchronisation error has occurred. No
sync. telegrams have been received during the
set monitoring time (object 0x1006 x 1.5). The
bus node is pre-operational (PDOs switched
off), and the outputs are in the error state.
4 x blinking
(Each approx. 200ms on, 200ms off, followed
by a 1s pause).
Event timer error: The bus coupler has not
received an RxPDO within the set event time
(0x1400ff sub-index 5). The bus node is pre-
operational (PDOs switched off), and the
outputs are in the error state.
RUN blink code
RUN Meaning
Off Firmware status < C0: Bus node is in stopped
state. No communication is possible with SDO
or PDO.
Fast blinking
(Approx. 50ms on, approx. 50ms off;
alternating with CAN ERR LED).
Automatic Baud rate detection has not yet
found a valid Baud rate. Not enough
telegrams on the bus yet.
1 x blinking
(Approx. 200ms on, 1s off).
Bus node is in stopped state. No
communication is possible with SDO or PDO.
Blinking cyclically
(Approx. 200ms on, 200ms off).
Bus node is in pre-operational state. The
node has not yet started.
On Bus node is in operational state.