PDXC2 ORIC® Piezo Stage Controller Chapter 3: Software
Page 16 CTN015391-D02
3.4.5 Performance Optimize
The PDXC2 controller has a performance optimization function. If the user changes the load on the stage, the
original parameters may not be optimal, which may result in poor stage operation. The performance optimization
function can then be used to try to get a better set of parameters to improve operation.
Performance optimization steps:
1. Click button to start performance optimization.
2. Click OK in the pop-up box.
3. Wait about 1-2 minutes, the performance optimization will finish and LED light up.
3.4.6 Setting Move Sequences
The Kinesis software allows move sequences to be programmed, allowing several positions to be visited without
user intervention. For more details and instructions on setting move sequences, please see the Kinesis Helpfile.
3.4.7 Changing and Saving Parameter Settings
During operation, certain settings (e.g. max speed, jog step size, etc.) can be changed as required. When the
Kinesis Server is running and the stage association made, suitable default settings are loaded, and these values
have been chosen to provide safe performance in the majority of applications. However, for applications where
these settings need to be changed, a new set of ‘Device Start Up settings', must be created which can then be
applied and/or uploaded on subsequent start up. See the Kinesis Helpfile for more details.
3.4.8 External Trigging
In the Setting Panel of the GUI, the user can toggle between manual and trigger mode. When switched to trigger
mode, the I/O port on the front panel is enabled to allow users to remotely control the PDXC2. For the electrical
characteristics and pin distribution of the I/O port, please refer to Table 3.
An I/O cable is also provided to breakout the pins of the I/O port into BNC connectors.
Open loop mode:
PDXC2 only supports analog rising and falling edge modes while operating in open loop mode. The “Analog In” pin
works with the “Trigger In” pin on the I/0 port to define the movement amplitude and type of trigger signal (rising
or falling edge) to initiate motion. When trigger mode is enabled, the output amplitude for driving the stage will
be adjusted based on the input voltage to the “Analog In” pin. For example, a +10 V input voltage gives 100%
forward output amplitude, and a -10 V input voltage gives 100% backward output amplitude. Please note that,
the output amplitude will be decreased when the absolute value of Analog In is decreased; however, the
relationship between the output amplitude and the Analog In is not proportional, and different stages have
different characteristics.
Closed loop mode:
The PDXC2 supports all external trigging modes for closed loop mode, including Analog, Fixed Step, and Fixed
Positions.
Analog In
In this sub-mode, the user can make use of the “Analog In” pin of I/O port to set the Target Position,
use the “Trigger In” pin to initiate a movement towards the target position. The type of trigger edge
to start a movement can also be defined here.