TIS RLY-8CH-16A User manual

RELAY 8 CHANNELS 16 AMPS
INSTALLATION MANUAL
This device is used to control ON/OFF for lights
and other devices, electrical locks, 3rd-party curtain
motors, shutters, and oor heaters.
Automation Made Easy
Model: RLY-8CH-16A
6 58921 79817 1
BARCODE (UPC-A)
PRODUCT INFORMATION
PRODUCT SPECIFICATIONS
Output switching voltage
Number of channels 8
Nominal voltage 0 – 230 V AC 50/60 Hz
Max. switching Voltage: 440VAC
Output switching current
Nominal current per channel 16 A
Maximum total channel load 128 A
Max switching current 50A Resistive
20A Florescent
Max continuous current 20A VAC
TIS Bus
Number of devices on 1 line Max. 64
Bus voltage 12-32 V DC
Current consumption (Normal) <12 mA / 24 V DC
Current consumption (operation) <35 mA / 24 V DC
Protection Reverse Polarity Protection
Operating and display
elements
Programming button/LED (PRG) For assignment of the physical address
1-8 buttons Manual ON/OFF and Programming
Mechanical Switch Relay emergency operator
Functions
Lighting control ON/OFF 8 channels controlled separately
Curtain motor control Can set 4 group of curtains (open/close) option
Scenes 8 different scenarios
Sequences 8 different sequences
Dimensions Width × Length × Height 145mm × 75mm × 91mm
Housing
Materials ABS fire proof
Casing color Black Gray
Button color Silver
IP rating IP 20

RELAY 8 CHANNELS 16 AMPS
INSTALLATION MANUAL
MODEL: RLY-8CH-16A
TIS CONTROL LIMITED
RM 1502-p9 Easey CommBldg
253-261 Hennessy Rd Wanchai
Hong Kong
TEXAS INTELLIGENT SYSTEM LLC
SUITE# 610. 860 NORTH DOROTHY DR
RICHARDSON
TX 75081.USA
Copyright © 2020 TIS, All Rights Reserved
TIS Logo is a Registered Trademark of Texas Intelligent System LLC in the
United States of America. This company takes TIS Control Ltd. in other
countries. All of the Specifications are subject to change without notice.
www.tiscontrol.com
Data Cable
Use screened stranded RS485 data cable
with four twisted pairs. Congure devices in
a “Daisy Chain.”
Do not cut or terminate live data cables.
Electrical Wires
The installer should adequately consider
the total current consumption when
selecting the wires.
Recommended wire size for load (light
channels) and input wires is 2.5 -4 mm.
Warranty
We provide a warranty as required by law.
A hologram warranty seal and product
serial number are provided on each device.
Please send the description of the defect
with Product S/N to our dealer network.
Read Instructions
We recommend that you read this
Instruction Manual before installation.
Safety instructions
Electrical equipment should only be
installed and tted by electrically skilled
persons.
Failure to observe the instructions may
cause damage to the device and other
hazards.
These instructions are an integral part of
the product and must remain with the end
customer.
Programming
This device can be tested and programmed
manually. Advanced programming requires
TIS Device Search software. Advanced
software programming knowledge should
be obtained in the advanced training
courses.
Simple Installation
DIN Rail mount facilitates installation.
Fixing points are provided for installation
without the use of DIN rail.
Mounting Location
Install in a dry, well-ventilated location.
Controllers may emit some mechanical
noise. Take this into account when deciding
on a mounting location.

RELAY 8 CHANNELS 16 AMPS
INSTALLATION MANUAL
MODEL: RLY-8CH-16A
TIS CONTROL LIMITED
RM 1502-p9 Easey CommBldg
253-261 Hennessy Rd Wanchai
Hong Kong
TEXAS INTELLIGENT SYSTEM LLC
SUITE# 610. 860 NORTH DOROTHY DR
RICHARDSON
TX 75081.USA
Copyright © 2020 TIS, All Rights Reserved
TIS Logo is a Registered Trademark of Texas Intelligent System LLC in the
United States of America. This company takes TIS Control Ltd. in other
countries. All of the Specifications are subject to change without notice.
www.tiscontrol.com
Turn off the main electrical source before
installation.
1WARNING! HIGH VOLTAGE
INSTALLATION STEPS
Mount the device on a DIN Rail inside an
approved enclosure. The device can also
be installed without the use of DIN Rail
by two mounting screw holes.
2
+24D+D-GND+24D+D-GND
Connect RS485 data cable to the TIS-
BUS port as per the connection diagram.
No need to loop the TIS-bus cable if 2
DIN Rail modules are connected together
from the side bus train terminal.
3
GND(white-orange)&(white-brown)
D-(white-green)&(white-blue)
D+(blue-green)
+24V(brown-orange)
Cat5e connection
1 2 3 4 5 678
1 2
TIS-BUS
34 5 678PRG
1
000
1 1
0
1
0
1
0
1
0
1
0
1
GND D- D+ +24V
RLY-8CH-16A WARNING! HIGH VOLTAGE!
!
To the TIS BUS Network
Cat5e
Complete the load connection, light, oor
heating, and shutter as per the following
steps:
LIGHTS / APPLIANCES /
FLOOR-HEATING CONNECTION
Connect the load electrical wires to
outputs 1-8. Each channel can control
a maximum of 16A loads. The installer
should make sure not to overload the
channels.
Load neutral wire should be linked to the
neutral connection in DB enclosure.
4
GND(white-orange)&(white-brown)
D-(white-green)&(white-blue)
D+(blue-green)
+24V(brown-orange)
Cat5e connection
1.5 mm Electric Cable
1.5 mm Electric Cable
2.5 mm Electric Cable
Connect To L
Connect To N
To the TIS BUS Network
Cat5e
1 2 3 4 5 678
1 2
TIS-BUS
34 5 678PRG
1
000
1 1
0
1
0
1
0
1
0
1
0
1
RLY-8CH-16A WARNING! HIGH VOLTAGE!
GND D- D+ +24V
!

RELAY 8 CHANNELS 16 AMPS
INSTALLATION MANUAL
MODEL: RLY-8CH-16A
TIS CONTROL LIMITED
RM 1502-p9 Easey CommBldg
253-261 Hennessy Rd Wanchai
Hong Kong
TEXAS INTELLIGENT SYSTEM LLC
SUITE# 610. 860 NORTH DOROTHY DR
RICHARDSON
TX 75081.USA
Copyright © 2020 TIS, All Rights Reserved
TIS Logo is a Registered Trademark of Texas Intelligent System LLC in the
United States of America. This company takes TIS Control Ltd. in other
countries. All of the Specifications are subject to change without notice.
www.tiscontrol.com
WARNING: Do not connect curtain motor
wires before combining (interlocking) 2
relay channels together as curtain mode to
avoid causing damage to motors. Please
read about how to manually program
shutter/curtain pairing in this manual.
SHUTTER / CURTAIN CONNECTION
Once you combine any 2 channels as
shutter/curtain, then connect the shutter-
open wire to the rst channel and the
shutter-close wire to the second channel.
The shutter neutral wire should be linked
to the neutral connection in DB enclosure.
INSTALLATION STEPS
Connect To L
Connect To N
110 ~ 220 Volt
GND(white-orange)&(white-brown)
D-(white-green)&(white-blue)
D+(blue-green)
+24V(brown-orange)
Cat5e connection
1.5 mm Electric Cable
1.5 mm Electric Cable
2.5 mm Electric Cable
O-OFF
I-ON
MCB
1 2 3 4 5 678
1 2
TIS-BUS
34 5 678PRG
1
000
1 1
0
1
0
1
0
1
0
1
0
1
GND D- D+ +24V
RLY-8CH-16A WARNING! HIGH VOLTAGE!
!
To the TIS BUS Network
Cat5e
Connect the live (supply) wire to inputs.
All inputs must have an appropriate
voltage source and an MCB to protect
that load circuit.
5
GND(white-orange)&(white-brown)
D-(white-green)&(white-blue)
D+(blue-green)
+24V(brown-orange)
Cat5e connection
1.5 mm Electric Cable
1.5 mm Electric Cable
2.5 mm Electric Cable
Connect To L
Connect To N
To the TIS BUS Network
Cat5e
1 2 3 4 5 678
1 2
TIS-BUS
34 5 678PRG
1
000
1 1
0
1
0
1
0
1
0
1
0
1
RLY-8CH-16A
WARNING! HIGH VOLTAGE!
GND D- D+ +24V
!

RELAY 8 CHANNELS 16 AMPS
INSTALLATION MANUAL
MODEL: RLY-8CH-16A
TIS CONTROL LIMITED
RM 1502-p9 Easey CommBldg
253-261 Hennessy Rd Wanchai
Hong Kong
TEXAS INTELLIGENT SYSTEM LLC
SUITE# 610. 860 NORTH DOROTHY DR
RICHARDSON
TX 75081.USA
Copyright © 2020 TIS, All Rights Reserved
TIS Logo is a Registered Trademark of Texas Intelligent System LLC in the
United States of America. This company takes TIS Control Ltd. in other
countries. All of the Specifications are subject to change without notice.
www.tiscontrol.com
INSTALLATION STEPS
MECHANICAL EMERGENCY SWITCH
Turn on the power source, and then
test the loads by short pressing on the
device’s local override buttons 1-8.
6
1 2 3 4 5 678
1 2
TIS-BUS
34 5 678PRG
1
000
1 1
0
1
0
1
0
1
0
1
0
1
GND D- D+ +24V
RLY-8CH-16A WARNING! HIGH VOLTAGE!
!
WARNING!
Do not turn mechanical switch ON/OFF
if it connects to curtain to avoid causing
damage to motors.
This Relay contain 8 mechanical switches
to be used during power supplier failure.
Simply use any screw driver to put the
mechanical switch of each channel to up
position for ON, and to down position for
OFF. 1 2 3 4 5 678
1 2
TIS-BUS
34 5 678PRG
1
000
1 1
0
1
0
1
0
1
0
1
0
1
GND D- D+ +24V
RLY-8CH-16A WARNING! HIGH VOLTAGE!
!

RELAY 8 CHANNELS 16 AMPS
INSTALLATION MANUAL
MODEL: RLY-8CH-16A
TIS CONTROL LIMITED
RM 1502-p9 Easey CommBldg
253-261 Hennessy Rd Wanchai
Hong Kong
TEXAS INTELLIGENT SYSTEM LLC
SUITE# 610. 860 NORTH DOROTHY DR
RICHARDSON
TX 75081.USA
Copyright © 2020 TIS, All Rights Reserved
TIS Logo is a Registered Trademark of Texas Intelligent System LLC in the
United States of America. This company takes TIS Control Ltd. in other
countries. All of the Specifications are subject to change without notice.
www.tiscontrol.com
1 2 3 4 5 678
1 2
TIS-BUS
34 5 678PRG
1
000
1 1
0
1
0
1
0
1
0
1
0
1
GND D- D+ +24V
RLY-8CH-16A WARNING! HIGH VOLTAGE!
!
Short press on any wall lights buttons on
the Luna, Mars, Terre or others panels.
2
1
TER-4G
45mm
25mm
TER-4G
D-
24V GND
D+
45mm
221
227A
12EM4
227A
12EM4
TER-4G-A
45mm
25mm45mm
TER-4G-A
ADD-3R-5A
ADD-3R-5A
50mm
24mm54mm
PANEL ADDITION
3 Output Relay 5 Amp
Model : ADD-3R-5A
TIS BUS Input : 45-75mA/24V DC
Output Current : 3A220VAC
COM OUT3 OUT2 OUT1 COM
www.tissmarthome.com
D- +24V
GND D+
Long press on any buttons 1-8 for 6
seconds. The LED indicator for the
pressed button will start blinking.
LIGHTS / APPLIANCES PROGRAMMING
All channels by default are used for lights/appliances control.
You can pair device light channels to any wall panels by doing the following:
6”
Test the button on the panel by short
pressing it for ON/OFF.
3
TER-4G
45mm
25mm
TER-4G
D-
24V GND
D+
45mm
221
227A
12EM4
227A
12EM4
TER-4G-A
45mm
25mm45mm
TER-4G-A
ADD-3R-5A
ADD-3R-5A
50mm
24mm54mm
PANEL ADDITION
3 Output Relay 5 Amp
Model : ADD-3R-5A
TIS BUS Input : 45-75mA/24V DC
Output Current : 3A220VAC
COM OUT3 OUT2 OUT1 COM
www.tissmarthome.com
D- +24V
GND D+
PAIRING (MANUAL PROGRAMMING)

RELAY 8 CHANNELS 16 AMPS
INSTALLATION MANUAL
MODEL: RLY-8CH-16A
TIS CONTROL LIMITED
RM 1502-p9 Easey CommBldg
253-261 Hennessy Rd Wanchai
Hong Kong
TEXAS INTELLIGENT SYSTEM LLC
SUITE# 610. 860 NORTH DOROTHY DR
RICHARDSON
TX 75081.USA
Copyright © 2020 TIS, All Rights Reserved
TIS Logo is a Registered Trademark of Texas Intelligent System LLC in the
United States of America. This company takes TIS Control Ltd. in other
countries. All of the Specifications are subject to change without notice.
www.tiscontrol.com
Go to oor heater page on any wall panel
with the oor heating function, and press
ON button to turn on the oor heating.
2
1
00:00:00
FLOOR 29
30 MINUTES
ON
32
OFF
00:00:00
FLOOR 29
30 MINUTES
ON
33
OFF
Long press on any buttons 1-8 for 6
seconds. The LED indicator for the
pressed button will start blinking.
FLOOR HEATING PROGRAMMING
Test the oor heating by changing the
temperature and turning it OFF/ON.
3
PAIRING (MANUAL PROGRAMMING)
1 2 3 4 5 678
1 2
TIS-BUS
34 5 678PRG
1
000
1 1
0
1
0
1
0
1
0
1
0
1
GND D- D+ +24V
RLY-8CH-16A WARNING! HIGH VOLTAGE!
!
6”

RELAY 8 CHANNELS 16 AMPS
INSTALLATION MANUAL
MODEL: RLY-8CH-16A
TIS CONTROL LIMITED
RM 1502-p9 Easey CommBldg
253-261 Hennessy Rd Wanchai
Hong Kong
TEXAS INTELLIGENT SYSTEM LLC
SUITE# 610. 860 NORTH DOROTHY DR
RICHARDSON
TX 75081.USA
Copyright © 2020 TIS, All Rights Reserved
TIS Logo is a Registered Trademark of Texas Intelligent System LLC in the
United States of America. This company takes TIS Control Ltd. in other
countries. All of the Specifications are subject to change without notice.
www.tiscontrol.com
SHUTTER COMBINATION PROGRAMMING
You can change any 2 channels in sequence like CH1 & CH2, Ch3 & CH4, ... CH7 & CH8
to be combined (interlocked) together to work as shutter/curtain control.
To combine these 2 channels, complete the following steps manually:
PAIRING (MANUAL PROGRAMMING)
Short press on the rst button and then
the second button that you want to
combine as curtain control; for example,
CH3 and CH4.
21 2 3 4 5 678
1 2
TIS-BUS
34 5 678PRG
1
000
1 1
0
1
0
1
0
1
0
1
0
1
GND D- D+ +24V
RLY-8CH-16A WARNING! HIGH VOLTAGE!
!
2
1
4Test by turning the rst button ON and
then the second button. Both buttons
should not turn ON together. If you see
that the rst button is turning the other
button off, that means that your buttons
are successfully combined as shutter/
curtain mode.
1 2 3 4 5 678
1 2
TIS-BUS
34 5 678PRG
1
000
1 1
0
1
0
1
0
1
0
1
0
1
GND D- D+ +24V
RLY-8CH-16A WARNING! HIGH VOLTAGE!
!
1Press the PRG button for 3 seconds until
the LED starts blinking rapidly. 1 2 3 4 5 678
1 2
TIS-BUS
34 5 678PRG
1
000
1 1
0
1
0
1
0
1
0
1
0
1
GND D- D+ +24V
RLY-8CH-16A WARNING! HIGH VOLTAGE!
!
3”
Wait for few seconds until the PRG LED
stops blinking.
3
1 2 3 4 5 678
1 2
TIS-BUS
34 5 678PRG
1
000
1 1
0
1
0
1
0
1
0
1
0
1
GND D- D+ +24V
RLY-8CH-16A WARNING! HIGH VOLTAGE!
!

RELAY 8 CHANNELS 16 AMPS
INSTALLATION MANUAL
MODEL: RLY-8CH-16A
TIS CONTROL LIMITED
RM 1502-p9 Easey CommBldg
253-261 Hennessy Rd Wanchai
Hong Kong
TEXAS INTELLIGENT SYSTEM LLC
SUITE# 610. 860 NORTH DOROTHY DR
RICHARDSON
TX 75081.USA
Copyright © 2020 TIS, All Rights Reserved
TIS Logo is a Registered Trademark of Texas Intelligent System LLC in the
United States of America. This company takes TIS Control Ltd. in other
countries. All of the Specifications are subject to change without notice.
www.tiscontrol.com
PAIRING (MANUAL PROGRAMMING)
To program the curtain to any wall panel,
press and hold the CH (shutter-Open)
button for 6 seconds. The LED indicator
of the pressed button will start blinking,
5
1 2 3 4 5 678
1 2
TIS-BUS
34 5 678PRG
1
000
1 1
0
1
0
1
0
1
0
1
0
1
GND D- D+ +24V
RLY-8CH-16A WARNING! HIGH VOLTAGE!
!
6”
Short press on any button on the Luna,
Mars, Terre or others wall panels.
6
TER-4G
45mm
25mm
TER-4G
D-
24V GND
D+
45mm
221
227A
12EM4
227A
12EM4
TER-4G-A
45mm
25mm45mm
TER-4G-A
ADD-3R-5A
ADD-3R-5A
50mm
24mm54mm
PANEL ADDITION
3 Output Relay 5 Amp
Model : ADD-3R-5A
TIS BUS Input : 45-75mA/24V DC
Output Current : 3A220VAC
COM OUT3 OUT2 OUT1 COM
www.tissmarthome.com
D- +24V
GND D+
Test the button on the panel by short
pressing for open/stop. Do the same to
program the Close channel with another
button.
7
TER-4G
45mm
25mm
TER-4G
D-
24V GND
D+
45mm
221
227A
12EM4
227A
12EM4
TER-4G-A
45mm
25mm45mm
TER-4G-A
ADD-3R-5A
ADD-3R-5A
50mm
24mm54mm
PANEL ADDITION
3 Output Relay 5 Amp
Model : ADD-3R-5A
TIS BUS Input : 45-75mA/24V DC
Output Current : 3A220VAC
COM OUT3 OUT2 OUT1 COM
www.tissmarthome.com
D- +24V
GND D+
Open
Close
1 2 3 4 5 678
1 2
TIS-BUS
34 5 678PRG
1
000
1 1
0
1
0
1
0
1
0
1
0
1
GND D- D+ +24V
RLY-8CH-16A WARNING! HIGH VOLTAGE!
!
To cancel the curtain interlock and return
to lighting mode, repeat steps 1-3 above.
8

RELAY 8 CHANNELS 16 AMPS
INSTALLATION MANUAL
MODEL: RLY-8CH-16A
TIS CONTROL LIMITED
RM 1502-p9 Easey CommBldg
253-261 Hennessy Rd Wanchai
Hong Kong
TEXAS INTELLIGENT SYSTEM LLC
SUITE# 610. 860 NORTH DOROTHY DR
RICHARDSON
TX 75081.USA
Copyright © 2020 TIS, All Rights Reserved
TIS Logo is a Registered Trademark of Texas Intelligent System LLC in the
United States of America. This company takes TIS Control Ltd. in other
countries. All of the Specifications are subject to change without notice.
www.tiscontrol.com
TROUBLESHOOTING
PRG Button Blinks Red Color
Rapidly
Reason: The Module address conicts with other
device in TIS network, you need to press and hold the
PRG button for 6 seconds so the module can get new
address
Device PRG LED is not Blinking;
Device not Powered
Reason: Device is not powered on; no TIS-BUS 24V
supply connected to the device.
Device Button LED ON but
lights not ON
Reason 1: Lights’ neutral wire not connected
Reason 2: Channel protection delay time is enabled
in software.
Wall Panels can’t Pair with the
Device
Reason 1: TIS-BUS connection has a problem; check
the wires and make sure there’s not a short in the
connection.
Reason 2: Manual programming function disabled in
the device (default is enabled).
Wall Panels can’t Control the
Device Channels
Reason 1: TIS-BUS connection has a problem; check
the wires and make sure there’s not a short in the
connection.
Reason 2: Programming address is wrong.
Channel is turning off by itself
after few seconds
Reason: It is programmed as shutter / curtain
combination, and running time is enabled in the
software.
Table of contents
Popular Control System manuals by other brands

Bosch
Bosch FHP UPM II Installation and operation manual

White Rodgers
White Rodgers 50M56U-801 installation instructions

Parklio
Parklio Brain user manual

vistaCNC
vistaCNC P2-S quick start guide

IDEAL INDUSTRIES
IDEAL INDUSTRIES Audacy Wireless Controls user manual

U-Prox
U-Prox IC E Installation and programming manual