Installation
Fixing
The unit must be securely xed
to a single smooth at surface.
Any orientation is possible.
Locate a site for mounting the Titon CME,
take into consideration the position of:
xThe rooms to be ventilated
xThe Electrical services
xThe exhaust port orientation.
Ensure there is adequate access
for installation and maintenance,
see Dimensions for sizes.
Securely mount the unit through the mounting
holes on the casing using the appropriate
xings for the substrate and the CME.
Ensure the unit is not distorted by
the xings or mounting surface.
The xing slots on the unit are 6mm wide,
it may be necessary to use washers to
prevent damage to the CME's xing slots.
Tighten screws by hand, DO NOT over tighten
screws or use power tools.
Ducting Connections
Titon recommend that:
1. Ø125mm ducting is used for the
connection of the Output Port to Outside.
2. Ø125mm or Ø100mm ducting is used
for connection to the other ports.
3. A minimum distance of 200mm
between the CME unit and any
sharp bends in duct work.
4. Ducting should be insulated
where it passes through
unheated areas and voids.
5. Unit should be insulated when
tted in unheated area.
6. Where a duct extends externally above
roof level the section above the roof
should be insulated or a condensate trap
should be tted just below roof level.
7. Where ducts pass through re barriers,
they must be appropriately re stopped in
accordance with the requirements of Part
B Building Regulations (England & Wales).
8. A ducting condensate drain
must be tted to vertical Output
Port to Outside duct work.
9. Condensate drain pipe work must be
adequately secured, installed to have
a minimum 5° fall and be insulated if
any part of the pipe passes though an
unheated void. All insulation to be the
equivalent of at least 25mm of insulating
material with a thermal conductivity
of 0.04 W/(mK).
10. Ducting must be installed in such a way
that resistance to airow is minimised.
11. Ducting connected to the Output Port
to Outside must be to the external
air outside the building envelope.
12. All ducting joints including those
to the CME unit’s Duct Ports and
Convertible Port Covers must be
permanently connected and sealed.
13. Do not distort ducting, Convertible
Port Cover or Duct Ports.
10