
Sales and Technical Support +44 (0) 1206 814879 www.titon.co.uk 11
FAQ’s: Insufcient Airow
Check the Ventilation Unit is supplied with power. Check the mains circuit is live, check the fuse at
local isolator and that each wire core is making contact with terminal at outlet point.
Turn off the power to the Ventilation Unit at the local isolating. Carry out appropriate electrical
safety checks and taking effective precautions ensure that the Ventilation Unit has been wired in
accordance with the Product Handbook requirements. Ensure that no other power source has
been connected to boost circuits as this will damage the electrical components within the unit and
may cause the unit not to run, not to boost or to boost constantly.
Ensure boost control circuit opens/closes as required at PCB connections.
(MVHR Only) Ventilation Units are tted with Automatic Frost Protection Systems that may
automatically reduce the supply air rate during periods where temperatures drop below freezing
especially for long periods and may activate particularly if home has been unheated for more than
24hrs.
(MVHR Only) Some Ventilation Units include a Summer Mode facility that allows the supply air
fan to be turned off by the occupant using an external switch, check if switch is installed at PCB
connections and activated or that PCB terminals have been used in error to connect to a circuit
intended for an alternative use.
Correctly installed product may be running quietly and efciently making it difcult to hear the
fan(s), also the low airow rates required in smaller dwellings may not always be obvious without
close inspection of the room air valves. Also, in some circumstances there may not be a notice-
able increase in sound levels between normal and boost speeds.
Check the unit has been commissioned and set to operate at the appropriate speed settings in
accordance with the Dwelling Commissioning Rates specied by the System Designer.
Check the commissioning control is in the “run” position (MVHR – the sliding switch is in central
position) (CME – the link is on one pin and not making the circuit and not still connected to both
pins) and check no other cables normally attached to the PCB have been disconnected accidentally.
(MVHR Only) Turn off the power supply, remove the front (refer to product manual) and check the
lters (if tted) are clean and not blocked by debris. Make sure that there is no debris (such as
plaster or masonry dust) within the unit’s internal airways leading to the fans.
Check external terminals for fresh air intake and stale air extract, such as air bricks, grilles or roof
mounted terminals, are free of debris and are of the correct size, adequately mounted so as not to
impede air ow. Insect screens are not required and are highly resistive to airow.
Check the duct cross-sectional dimensions comply with the System Design specications
(usually a minimum of ø125mm or 204 mm x 60mm rectangular for MVHR systems and for the
main exhaust duct to outside for CME systems).
Check the ductwork for blockages. Any restriction in any part of the system will create a
resistance to air ow and noise.
Check ANY FLEXIBLE DUCTING used does not exceed the lengths specied by the System
Design (normally 300mm maximum) and that it is pulled taut and straight. Flexible ducting is
highly resistive to airow and will easily crease or distort causing a blockage.
Check all ducts, joints and accessories are leak free. All joints must be fully sealed using a
proprietary product such as the Titon Self Seal Coupler or by using a exible joint sealant. Duct
tape alone is not sufcient and will not provide an effective long term seal.