TOA Architectural and Engineering Specifications
10
5 System Configuration and Components
General
System Size
The intercom Exchange Unit shall support 16 station ports and 2 paging audio outputs (N-
8000EX only). Connecting exchanges to a local area or wide area IP network (10BASE-
T/100BASE-TX) shall permit the establishment of multiple-exchange systems supporting up to a
maximum of 1280 station ports and a maximum of 160 paging zones. User dialed key sequences
required for inter-exchange calling and paging shall be identical to those used for intra-exchange
calling and paging. A single system shall support up to 80 total Exchange Units and Multi-
Interface Units. Each 16-station exchange shall allow up to eight connected stations or paging
ports to operate simultaneously in conversation with other stations (N-8000EX only).
Connection of External Equipment
The N-8000MI Multi-Interface unit shall support up to 2 audio (BGM) input sources, up to 2 audio
output lines, up to 2 inter-system tie-lines for expansion of existing EXES-6000 and EXES-2000
intercom systems, or up to 2 PBX interface connections. The Multi-Interface Unit shall also allow
simultaneous connection of up to 2 relay contact outputs, and up to 2 no-voltage make contact
inputs. A single system shall support up to 80 total Exchange Units and Multi-Interface Units.
Wiring
Each station shall be connected to its associated exchange by means of a single, non-polarized,
twisted-pair cable. Systems requiring more than one non-polarized, twisted pair cable shall not be
acceptable.
Service Distances
The system Master Stations and Sub-Stations shall remain fully functional using the following
wire gauge and distances: 26 gauge/1,870 ft; 24 gauge/2,950 ft; 22 gauge /4,920 ft; 19
gauge/9,500 ft.
Exchange Components
N-8000EX Exchange Unit
The Exchange Unit shall store and execute the system operating instructions, perform all call
routing and power distribution functions for the connected stations and shall include an
Ethernet/IP interface for connection to a standard 10BASE-T/100BASE-TX LAN or WAN network.
The Exchange Unit shall also provide two paging audio outputs and two paging control outputs.
Connection of each station shall be via one twisted pair cable terminated with supplied mini-
clamp connector. Connection to the network shall be via standard CAT5 cable terminated with
RJ-45 connector. Connection of paging audio and paging control outputs shall be via standard
audio (shielded) and control (unshielded) cabling terminated with 4-pin removable terminal
blocks. Connection to AC Mains power source shall be via removable IEC type Universal Power
Cord. The Exchange Unit shall mount in a standard 19" equipment rack and occupy one vertical
rack space (1.75"). Dimensions (W, H, D) shall be 16.53” x 1.74” x 13.75”. Weight shall be 9.26
lbs.
N-8010EX Exchange Unit
The Exchange Unit shall store and execute the system operating instructions, perform all call
routing and power distribution functions for the connected stations and shall include an
Ethernet/IP interface for connection to a standard 10BASE-T/100BASE-TX LAN or WAN network.
Connection of each station shall be via one twisted pair cable terminated with supplied mini-
clamp connector. Connection to the network shall be via standard CAT5 cable terminated with
RJ-45 connector. Connection to AC Mains power source shall be via removable IEC type
Universal Power Cord. The Exchange Unit shall mount in a standard 19" equipment rack and