TPA TRS67-8I-8O Operator's manual

1
TRS67-8I-8O
Bus Coupler EtherCAT IP67
Documentation

2
Note
This instruction is used for TRS67-8I-8O Remote IO module.
This instruction is about the specifications, installation, main function and the configuration process of TRS67-8I-
8O IP67 Remote IO module.
Application
This instruction application to the following:
Electrical engineer
Field installation workers.
Disclaimer
This manual is based on existing information, and its contents are subject to change without notice. Tpa has done
its best to ensure that its content is accurate and reliable when writing this manual but shall not be liable for the
loss and damage caused by omission, inaccuracy, or typographical errors in this manual.
Product information
The TRS67-8I-8O series remote IO module is a 16-channel industrial digital input and output module
independently developed by Tpa that complies with the EtherCAT V5.1 communication protocol. This series of
products uses M12 T Code coded connectors for power supply. Compared with the traditional 7/8" connector,
not only it can provide a larger current (12 A), but also save valuable on-site installation space. All channel ports
of the TRS67-8I-8O support fault diagnosis alarms and short-circuit self-recovery functions, which can help
engineers quickly locate and find on-site faults and reduce maintenance costs.
Dimensions
ITEM
INPUT
OUTPUT
TRS67-8I-8O
C0-
C3
C4-
C7

3
Description of each port
1.3.1
Signal and power
Contact definition
Contact No.
ETH
(
ETHERCAT
)
PWR (POWER)
1
TX+
24V (US+
)
2
RX+
GND (UA-
)
3
TX-
GND (US-
)
4
RX-
24V (UA+
)
1.3.2
I/O signal

4
Contact definition
PIN
Description
1
24 V
2
PIN 2 signal
3
GND
4
PIN 4 signal
5
FE
Description of the lights
Light indicator of EtherCAT and Power
Indicator light Color Definition State Description
LINK GN Connection
green
ETH 1/2 connected
extinguish
ETH 1/2 unconnected
ACT YE Acting
flash
ETH 1/2 data transmission
extinguish
ETH 1/2 without data transmission
RDY GN Ready
green
Device turned on, will also remain after the normal
communication of the device is disconnected
flash Waiting for CPU synchronization
extinguish Device did not turn on
BF RD Break red Unconnected with EtherCAT control
extinguish Connection with EtherCAT control
SF RD Inspection error red Inspection error exists
extinguish None

5
US GN/RD Sensor power
green US power supply normal
extinguish
US power supply out
red
US power supply undervoltage (under 18 V)
UA GN/RD Device power
green UA power supply normal
extinguish
UA power supply out
red
UA power supply undervoltage (under 18 V)
Light indicator of I/O signal
Light Color Define State Description
2
GN/RD Signal performance of PIN 2
green Signal exists in Pin2
extinguish No signal exists in Pin2
red Pin2 output overload short circuit
2 @ 4 red at the same time Pin1(power) overload short circuit
4
GN/RN Signal performance of PIN 2
green Signal exists in Pin4
extinguish No signal exists in Pin4
red Pin2 output overload short circuit

6
2.1
Connectors and Accessories
M12 connector - I/O TRS8.3.04
M12 connector – Power in Metal TRS8.3.03
M12 connector – Power out Metal TRS8.3.11
M12 connector – EtherCAT TRS8.3.01
M12 connector male to 2M8 female – I/O TRS8.3.05
M12 cover for female
2.2
Connect description
2.2.1
Device grounding
To avoid data damage or loss, please ensure that the device is well grounded.
2.2.2
Shielded Cable
To avoid data damage or loss, use the EtherCAT cable, ensure that the shielding layer of the cable is well grounded.
2.2.3
Power supply
TRS67-8I-8O module power supply use M12 Tcode connection.
Module system and DI supported with US power supply, DO with UA power supply. Power range 18-30 VDC,
current 12 A. If the module uses series power supply, please pay attention to the voltage drop and the total
current of the power supply.

7
Typical connection diagram
2.2.4
IO connection
TRS67-8I-8O series IO signal is PNP. Please pay attention to the wiring method when connecting the sensor and
actuator, the typical connection diagram is shown below.
Typical Connection diagram input Typical Connection diagram output
2.3
Device fasten
Please use standard M4 screws to fix the module, the fixing surface should be kept flat, the module cannot bear
bending stress.
Chapter three: Configuration and operation instructions
3.1
ESI file
TRS67-8I-8O use equipment description files (ESI) that comply with the EtherCAT V2.3 standard
3.2
Main parameters
Housing material
PC
Filler material
Polyurethane
Metal material
Copper nickel plated
Weight
300 g
Operating temperature
-25 – 60 °C
If the device is used at an ambient temperature higher than 50 °C, be careful of
high
temperature burns when it contacts with the metal surface of the device
Storage temperature From -30 to 70 °C
Operating humidity
From 5% to 95%
Storage humidity
From 5% to 95%
Operating pressure
From 70 to 106 kPa
Protecting degree
IP67

8
3.3
EtherCAT
Port
2
Transmission Copper cable
Connect method M12 D code 4 pin
Transmission speed 100 Mbps
Device type EtherCAT Device
Consistency Class B
Refresh time 2 ms
EtherCAT protocol COE FOE
3.4
US device and sensor power supply
Connection method M12 T code 4 pin
Input voltage 18-30 VDC
Output current Max. 12 A
Reverse polarity protection Yes
Current consumption 120 mA/no load
3.5
UA actuator power supply
Connection method M12 T code 4 pin
Input voltage 18-30 VDC
Output current Max. 12 A
Reverse polarity protection Yes
Current consumption 5 mA/no load
3.6
IO connection
Connection method M12 A code 5 pin
Type PNP
Input type EN 61131-2 types 1 and 3
IO typical voltage 24 VDC
Actuator current 500 mA/one signal
Sensor current 500 mA/one signal
Protection of overload and short
circuit
870 mA/self-fixable
3.7
Electrical isolation
Testing parts Testing voltage
US power supply/ETH 1 500 V AC, 50 Hz, 1 Min
US power supply/ETH 2 500 V AC, 50 Hz, 1 Min
US power supply/FE 500 V AC, 50 Hz, 1 Min
ETH 1/FE 500 V AC, 50 Hz, 1 Min
ETH 2/FE 500 V AC, 50 Hz, 1 Min

9
ETH 1/ETH 2 500 V AC, 50 Hz, 1 Min
US/UA power supply 500 V AC, 50 Hz, 1 Min
UA power supply/ETH 1 500 V AC, 50 Hz, 1 Min
UA power supply/ETH 2 500 V AC, 50 Hz, 1 Min
UA power supply/FE 500 V AC, 50 Hz, 1 Min
3.8
Mechanical test
Vibration resistance according to EN60068-2-
6/IEC60068-2-6
5 g
Shock complies with EN 60068-2-27/IEC 60068-2-27
30 g, 1 ms cycle, half-sine shock pulse
Continuous impact according to EN60068-2-
27/IEC60068-2-27
10 g
3.9
EMC test
Noise immunity test complies with EN 61000-6-2 standard
ESD EN 61000-4-2/IEC 61000-4-2 Standard B, 6 kV contact discharge, 8 kV air discharge
Electromagnetic field EN 61000-4-3/IEC 61000-
4-3
Standard A, field strength: 10 V/m
Electrical fast transient burst immunity EN 61000- 4-
4/IEC 61000-4-4 Standard B, 2 kV
Surge immunity (Surge) EN 61000-4-5/IEC
61000-4-5
Standard B; DC power cord: ±0.5 kV/±0.5 kV
(symmetry/asymmetry)
Conducted interference EN 61000-4-6/IEC
61000-4-6 Standard A; testing voltage 10 V
Noise emission test according to EN 61000-6-4
Radio interference EN 55022 Class A
T.P.A. Srl Tecnologie e Prodotti per l’Automazione – Via Carducci, 221 – 20099 Sesto S. Giovanni
Tel. +390236527550 – www.tpaspa.com –P.I.: IT02016240968
Table of contents
Other TPA Control Unit manuals
Popular Control Unit manuals by other brands

XQP
XQP 500 Series manual

Roger
Roger R70/1AC INSTRUCTIONS AND RECOMMENDATIONS FOR THE INSTALLER

Huawei
Huawei MU509-b Application guide

Jetter
Jetter JX3-COM-PND installation manual

Assa Abloy
Assa Abloy Effeff ePED 1386CMC Installation and operating instructions

HEIDENHAIN
HEIDENHAIN TNC 426 PB/M Technical manual

Watts
Watts LFM118-3 Installation, operation and maintenance manual

Peter electronic
Peter electronic VBMS Series Assembly and commissioning instructions

Tektronix
Tektronix 7D11 instruction manual

Grundfos
Grundfos Vaccuperm VGS -141 Installation and operating instructions

Logitech
Logitech Harmony 1100 Remote Repair

SOMAS
SOMAS MTV Operation and service instruction