
BAS-SVN141D-EN 11
Step 5: Install Tracer Concierge System Panel
Note: Use wall anchors if the mounting surface is dry wall or masonry.
3. Secure the enclosure to the mounting surface with the enclosed #10
screws and #10 wall anchors.
4. Remove the tie wraps that secure the modules to the DIN rail during shipping.
Wiring High Voltage AC Power
Read all WARNINGS, CAUTIONS, and NOTICES prior to wiring high-voltage AC power.
To ensure proper operation of the controllers, install the power supply circuit in
accordance with the following guidelines:
• The panel must receive power from a dedicated power circuit. Failure to comply
could cause panel malfunctions.
• A disconnect switch for the dedicated power circuit must be near the panel, within
easy reach of the operator, and marked as the disconnecting device for the panel.
• Do not run input or output wires in the same conduit or wire bundle with high
voltage wire or 24 Vac wiring. Failure to comply could cause the controller to
malfunction due to electrical noise.
• Power wiring must comply with the National Electrical Code™ (NEC) and
applicable electrical codes.
• 120 Vac wiring requires three-wire service (Line, Neutral, Ground). Refer to Panel
10 for terminal locations.
Note: The transformer voltage utilization range is 98–132 Vac (120 Vac nominal).
1. Lock open the supply-power disconnect switch.
2. At the top-right corner of the enclosure, remove the knockout for 0.50 inch (13 mm)
conduit.
3. Open or remove the enclosure door if it is already installed.
4. Inside of the enclosure at the top-right corner, remove the line voltage area cover
plate.
5. Feed the 120 Vac power wire into the enclosure.
6. Using Figure 8, connect the line wire to the ‘L’ terminal.
7. Connect the neutral wire to the ‘N’ terminal.
8. Connect the green ground wire to the chassis ground screw.
WARNING
Hazardous Voltage!
Failure to disconnect power before servicing could result in death or serious
injury.Disconnect all electrical power, including remote disconnects, before
servicing. Follow proper lockout/tagout procedures to ensure the power cannot be
inadvertently energized.
WARNING
Proper Field Wiring and Grounding Required!
Failure to follow code could result in death or serious injury. All field wiring MUST
be performed by qualified personnel. Improperly installed and grounded field wiring
poses FIRE and ELECTROCUTION hazards. To avoid these hazards, you MUST follow
requirements for field wiring installation and grounding as described in NEC and
your local/state electrical codes.
NOTICE
Use Copper Conductors Only!
Unit terminals are designed to accept copper conductors only. Other conductors
could cause equipment damage.