16 BAS-SVX48H-EN
AI3; ocal Fan Mode Input
Local Fan Mode Input AI3 functions as the local (hard wired) fan mode switch input for
applications using the Trane space temperature sensor with a fan mode switch option The
various fan mode switch positions (OFF, LOW, MEDIUM, HIGH, AUTO) provide different
resistances that are interpreted by the UC400 Controller
NNoottee:: The local fan speed switch can be disabled by taking out of ser ice the multi-state point,
supply fan speed local and setting the alue for each to AUTO.
A communicated fan mode request by means of the BACnet communications link, can be used
for controllers operating on a BAS If both hard wired and communicated fan mode values are
present and in service, the UC400 Controller uses the communicated value However, the
controller can be configured to use the local (hard wired) input value instead of the
communicated BAS value The supply fan speed source (local or BAS) can be selected on the
Tracer TU Setup Parameters page If neither a hard wired nor a communicated fan mode value is
present, the controller recognizes the fan mode value as AUTO and operates according to the
default configuration If a valid hard wired or communicated fan mode value is established, and
then is no longer present, the controller generates a Supply Fan Speed Local alarm
AI4; Discharge Air Temperature Sensor
Discharge Air Temperature Sensor AI4 functions as the local discharge air temperature input
NNoottee:: A alid discharge air temperature alue is required for normal operation.
The UC400 Controller receives the temperature as a resistance signal from a 10 kΩ thermistor
wired to analog input AI4 The thermistor is typically located downstream from all unit heating
and cooling coils at the unit discharge area If a discharge air temperature value is invalid, or is
not present, the controller generates a Discharge Air Temp Failure alarm If there is a discharge
air temperature failure, the controller runs a simplified zone control algorithm and controls the
space to the unoccupied setpoints
AI5; Entering Water Temperature
Entering Water Temperature AI5 functions as the local (hard wired) entering water temperature
input An entering water temperature communicated by means of the BACnet communications
link, can be used for controllers operating on a BAS If both hard wired and communicated
entering water temperature values are present, and in service, the UC400 Controller uses the
communicated value If a valid hard wired or communicated entering water temperature value is
established, and then is no longer present, the UC400 Controller generates an Entering Water
Temperature Failure diagnostic
For units configured as 2-pipe or 4-pipe changeover units, the entering water temperature is used
to make heating/cooling operation decisions If neither a hard wired nor a communicated
entering water temperature value is present on changeover units, the UC400 Controller always
operates in heating mode
NNoottee:: For units not configured as changeo er units, the entering water temperature can be
manually configured and used for information and troubleshooting. It will not affect the
operation of the controller.
Universal Inputs
The UC400 Controller has two (2) universal inputs
UI1; Relative Humidity or CO2Sensor
If the UC400 Controller is configured for a local hard wired RH sensor, the factory programming
assumes it is wired to UI1 The pre-configured unit requires a 4-20 mA analog input
corresponding linearly to a 0%-100% relative humidity If the controller is configured for a local
hard wired CO2sensor, the factory programming also assumes it is wired to UI1 The pre-
configured unit requires a 4-20 mA analog input
TTyyppiiccaall AApppplliiccaattiioonnss aanndd TTeerrmmiinnaattiioonnss