manuals.online logo
Brands
  1. Home
  2. •
  3. Brands
  4. •
  5. Trane
  6. •
  7. Gas Detector
  8. •
  9. Trane 4190 4100 User manual

Trane 4190 4100 User manual

The Trane Company
3600 Pammel Creek Road
La Crosse, WI 54601-7589
© 2002 American Standard Inc. 3270 3361 Rev 1
®
CO
2
Demand-Controlled Ventilation Wall-Sensor
Ordering number: 4190 4100
The carbon-dioxide (CO2) sensor, shown in Figure 1,
is designed especially for demand-controlled
ventilation zone applications. The exceptional
stability and reliable performance come from
advanced silicon based Non-Dispersive InfraRed
(NDIR) technology.
Figure 1: CO2 demand-controlled ventilation sensor
Specifications
Table 1 shows the specifications of the CO2sensor.
Power supply requirements
CAUTION
AVOID EQUIPMENT DAMAGE!
Make sure that you connect the power wire only to
the 24V terminal. Connecting the power wire to the
output terminal may result in equipment damage.
The CO2 sensor is designed to operate with a
nominal 24 Vac supply. The power supply should
maintain the voltage between 20 to 26 Vac.
Use a 24 Vac power supply according to the following
guidelines. If more than one sensor is connected to
one 24 Vac transformer, a common loop is formed
and the risk of a short-circuit increases. To avoid
this, use a separate floating supply for each sensor,
as shown in Figure 2.
Figure 2: Separate ac power supplies
Table 1: Sensor specifications
Measuring range 0–2000 parts per million (ppm)
CO2
Accuracy at 25°C
< ± [40 ppm CO2+ 3% of
reading] (includes repeatability
and calibration uncertainty)
Non-linearity < 1.0% full scale (FS)
Temperature
dependence of output
0.3% FS/°C
Long-term stability < 5.0% FS/5-years
Recommended
calibration interval
5 years
Response time 1 minute (0–63%)
Operating temperature From 59 to 95°F (15 to 35°C)
Storage temperature From –4 to 158°F (–20 to 70°C)
Humidity range 0–85% relative humidity (RH)
Thinner section for
cut-out
Output signals
(jumper selectable)
4–20 mA, 0–20 mA, 0–10 Vdc
Resolution of analog
outputs
10 ppm CO2
Recommended external
load
Current output: max. 500 Ω
Voltage output: min. 1000 Ω
Power supply Nominal 24 Vac
Power consumption < 5 VA
Warm-up time < 15 minutes
Housing material ABS plastic
Mounting holes
For standard Asian, European,
and North American junction
boxes
Dimensions 41/4in. × 31/8in. × 17/16 in.
(108 mm × 80 mm × 36 mm)
Table 1: Sensor specifications (Continued)
3270 3361 Rev 1 2
If several sensors must share one transformer, the
phase (~) must always be connected to the 24V
connector in each sensor to maintain polarity and to
avoid short-circuit through the shared common line
at the controller (Figure 3).
Figure 3: One ac power supply for several sensors
Figure 4 shows how to wire the sensor with 24 Vac
power from a unit controller.
Figure 4: Power supply from controller
Mounting the sensor
1. Select a proper location in the room to mount the
CO2sensor. Look for an interior wall with good
air circulation, approximately 54 in. (1.4 m) from
the floor.
2. Remove the back plate from the sensor and
thread the power wires and output signal wire
through the hole in the back plate (Figure 1 on
page 1). For surface wiring, make cut-outs with
pliers to the thinner section of the upper or lower
edge of the back plate and to thread the wires
through.
3. Mount the back plate to the wall with screws.
Note that the arrow on the back plate shows the
mounting direction.
4. On the circuit board, use the two jumpers next to
the terminal block to set up the type of output
(0–10 Vdc, 0–20 mA, 4–20 mA) (Figure 5). The
default setting is 4–20 mA.
Figure 5: Jumper settings for output type
5. Insert the circuit board in the back plate as
shown in Figure 1 on page 1. Do not press the
metal tube while inserting the circuit board.
6. Connect the power and signal wires to the screw
terminals of the circuit board. Figure 5 shows
the terminal locations. Refer to Power supply
requirements on page 1 for more information on
wiring ac power.
CAUTION
AVOID EQUIPMENT DAMAGE!
Make sure that you connect the power wire only to
the 24V terminal. Connecting the power wire to the
output terminal may result in equipment damage.
Service and maintenance
This CO2sensor has excellent stability and requires
no maintenance. In most environments the
recommended calibration interval is five years. A
trained service technician can use a portable CO2
meter to certify sensor calibration.
If, when checking the sensor, the reading differs too
much from the reference value, the sensor can be re-
calibrated in the field. A calibration kit, software,
and calibration gases are required.
If certified accuracy is required, the sensor must be
calibrated against accurate and traceable calibration
gases in a laboratory. Consult Trane BAS for further
details.

Popular Gas Detector manuals by other brands

GASTRON GTC-520F instruction manual

GASTRON

GASTRON GTC-520F instruction manual

Riken Keiki RI-2000R operating manual

Riken Keiki

Riken Keiki RI-2000R operating manual

Industrial Scientific OLDHAM 300 Series Operating and maintenance manual

Industrial Scientific

Industrial Scientific OLDHAM 300 Series Operating and maintenance manual

MSR Intec Controls PolyGard CO LC-1112 V3 user manual

MSR

MSR Intec Controls PolyGard CO LC-1112 V3 user manual

Honeywell E3Point E3DA user manual

Honeywell

Honeywell E3Point E3DA user manual

Honeywell Sensepoint XCL quick start guide

Honeywell

Honeywell Sensepoint XCL quick start guide

New Cosmos Electric XP-302M-R-A-1 instruction manual

New Cosmos Electric

New Cosmos Electric XP-302M-R-A-1 instruction manual

RKI Instruments NP-204 instruction manual

RKI Instruments

RKI Instruments NP-204 instruction manual

BEINAT GS920 quick start guide

BEINAT

BEINAT GS920 quick start guide

HST HD105 user guide

HST

HST HD105 user guide

sauermann Si-CD3 quick start guide

sauermann

sauermann Si-CD3 quick start guide

Riken Keiki GP-147 operating manual

Riken Keiki

Riken Keiki GP-147 operating manual

Geca Beta 752CO quick start guide

Geca

Geca Beta 752CO quick start guide

AKO 57624 manual

AKO

AKO 57624 manual

Seitron BEAGLE plus quick start guide

Seitron

Seitron BEAGLE plus quick start guide

Crowcon Flamgard-4/20 Installation, operating and maintenance guide

Crowcon

Crowcon Flamgard-4/20 Installation, operating and maintenance guide

Korno GT903 Serie user manual

Korno

Korno GT903 Serie user manual

Industrial Scientific Oldham MX52 Commissioning, operating and maintenance manual

Industrial Scientific

Industrial Scientific Oldham MX52 Commissioning, operating and maintenance manual

manuals.online logo
manuals.online logoBrands
  • About & Mission
  • Contact us
  • Privacy Policy
  • Terms and Conditions

Copyright 2025 Manuals.Online. All Rights Reserved.