Trane CVHE Quick setup guide

CVHE-CLD-1A
X39470756-02 February 2000
Information
Manual
Clear Language Display
Water-Cooled, Hermetic CenTraVac®
Clear Language Display for UCP2 and
FastPak™ Control Panels
Models
CVHE, CVHF, CVHG, CVRB, CVRC
50 and 60 Hz
Cooling-Only and Heat Recovery, Direct-Drive CenTraVacs
with UCP2 Control panels

Information Manual ii
Contents
General .................................................................. 1
Literature Change History ................................... 1
About This Manual .............................................. 1
LCD Display ........................................................ 1
Keypad ................................................................ 1
LED Alarm ........................................................... 1
Local Clear Language ......................................... 1
Control System ..................................................... 2
Unit Control Panel ............................................... 2
Custom Report ...................................................... 3
Custom Report Group ......................................... 3
ASHRAE Guideline 3 Report ................................ 4
Chiller Report ...................................................... 10
Chiller Operating Mode ..................................... 10
Chiller Operating Mode ..................................... 12
Active Chilled Water Setpoint/Evap Leaving
Water Temp ..................................................... 12
Active Chilled Water Setpoint/Chilled Water Set-
point Source ..................................................... 12
Active Ice Termination Setpoint/Ice Termination
Setpoint Source ............................................... 12
Active Hot Wtr Setpoint/Hot Wtr
Setpoint Source ............................................... 12
Evaporator Entering and Leaving
Water Temperatures ........................................ 13
Cond Entering and Leaving Water Temps ........ 13
Active Current Limit Setpoint ............................. 13
Active Current Limit Setpoint/Current Limit
Setpoint Source ............................................... 13
Evaporator Water Flow/ Condenser Water Flow 13
Chiller Tons ....................................................... 13
Outdoor Temperature ........................................ 13
Aux. Bundle or Heat Recovery Temps .............. 13
Chilled Water Setpoint Source .......................... 13
Current Limit Setpoint Source ........................... 14
Hot Water Setpoint Source ................................ 14
Ice Termination Setpoint Source ....................... 14
Refrigerant Report ............................................. 15
Report Heading ................................................ 15
Evaporator and Condenser Refrigerant
Pressure .......................................................... 15
Saturated Evap Temperature/Evap Refrigerant
Pressure .......................................................... 15
Saturated Cond Temperature/Cond
Refrigerant Press ............................................ 15
Saturated Evap Temp. and Discharge Temp. .. 15
Purge Operating Mode/Purge Status ............... 15
Purge Alarm Message ...................................... 15
Purge Suction Temp/Purge Liquid Temp. ........ 16
Purge Pumpout Rate/Purge Max Pumpout Rate 16
Purge Total Pumpout Time/ Purge Total Run
Time ................................................................ 16
Purge Adaptive Cycle Time w/Chlr On/Time to
Purge Remaining ............................................ 16
Purge Adaptive Cycle Time w/Chlr Off/Time to
Purge Remaining ............................................ 16
Purge Service Log ............................................ 16
Pumpout Avg, Last 30 Days ............................. 16
Refrigerant Monitor ........................................... 17
Approach Temperature ..................................... 17
Compressor Report ........................................... 18
Report Heading ................................................ 18
Differential Oil Pressure, Oil Temperature ........ 18
Discharge Oil Pressure, Oil Tank Pressure ...... 18
AF Compressor Speed Command ................... 18
AF Boundary Pressure Coefficient/AF Press.
Coefficient ....................................................... 18
AF Re-Optimization Timer Time Remaining ..... 18
Inlet Guide Vane Position ................................. 18
Compressor Phase Currents % RLA ................ 19
Compressor Line Currents Amps ..................... 19
Compressor Line Voltages ............................... 19
Compressor Power Factor and Watts .............. 19
Compressor Winding Temperatures ................. 19
Compressor Starts and Running Time ............. 19
Bearing Temperatures #1 and #2 ..................... 19
Solid State Starter Heat Sink Temp. ................. 19
HGBP Time ...................................................... 19
Operator Settings ............................................... 20
Settings Group Keys ......................................... 20
Operator Settings Group Heading .................... 20
Set Contrast - Applies to
CCCLD Display Only. ...................................... 20

iii
Purge Operating Mode ..................................... 20
Time Of Day Setting ......................................... 21
Front Panel Chilled Water Setpoint .................. 21
Front Panel Hot Water Setpoint ........................ 22
Front Panel Current Limit Setpoint ................... 22
Print Report ....................................................... 22
Control Type ..................................................... 22
Free Cooling ..................................................... 22
Chilled Water Reset Type ................................. 22
Reset Ratio ....................................................... 23
Start Reset Setpoint .......................................... 23
Maximum Reset Setpoint .................................. 23
Ice Building Enable ........................................... 23
Front Panel Ice Termination Setpoint ............... 23
Ice Making To Normal Cooling Transition Timer 23
Chilled Water Setpoint Source .......................... 24
Current Limit Setpoint Source ........................... 24
Hot Water Setpoint Source ............................... 24
Ice Termination Setpoint Source ...................... 24
Outdoor Air Temperature Source ..................... 24
Setpoint Source Override ................................. 24
Service Settings (Non Password Protected Ser-
vice Settings Group) .......................................... 25
Service Setting Group Heading ........................ 25
Menu Settings Password .................................. 25
Keypad/Display Lockout ................................... 26
Language Setting .............................................. 27
Display Units ..................................................... 27
Decimal Places Displayed Setpoint .................. 27
Display Menu Headings Enable ........................ 27
Clear Custom Menu .......................................... 27
Differential to Start Setpoint .............................. 27
Differential to Stop Setpoint .............................. 27
Evap/Cond Pump Off Delay Time ..................... 28
Printer Setups ................................................... 28
Clear Restart Inhibit Timer ................................ 29
Field Start-up ...................................................... 30
Field Startup ..................................................... 30
Field Start-up Group Heading ........................... 30
Keypad/Display Lock Feature Enable ............... 30
Menu Settings Password Enable ...................... 30
ICS Address ...................................................... 31
Power Up Start Delay Time .............................. 31
Design Delta Temperature Setpoint ................. 31
Leaving Water Temperature Cutout Setpoint ... 31
Low Refrigerant Temperature Cutout Setpoint .31
Condenser Limit Setpoint ................................. 31
Maximum Restart Inhibit (RI) Timer Setting ...... 31
Purge Control/Type ........................................... 32
Purge Service Log Reset .................................. 32
Purge Maximum Pumpout Rate ........................ 32
Purge Service Excessive Pumpout
Override Timer ................................................ 32
Purge Low Chiller Sat. Cond. Liquid Temp. Protec-
tion Enable ...................................................... 32
Purge Low Chiller Sat. Cond. Temp Setpoint ... 32
Surge Protection Enable ................................... 32
Under/Over Voltage Protection Enable ............. 32
Phase Reversal Protection Enable ................... 33
Phase Unbalance Limit Enable ......................... 33
Momentary Power Loss (MPL)
Protection Enable ............................................ 33
Enhanced Oil Temp. Protection ........................ 33
Oil Temp Setpoint ............................................. 33
Low Oil Temp Cutout ........................................ 34
Low Oil Temp Start Inhibit Differential .............. 34
High Discharge Temp Cutout ............................ 34
External Base Loading Enable .......................... 34
Soft Load Control Enable .................................. 34
Soft Load Starting Current Limit ........................ 34
Soft Load Current Limit Rate Of Change .......... 34
Soft Load Lvng Wtr Temp Rate of Change ....... 34
Hot Gas Bypass Enable .................................... 34
HGBP Timer Enable ......................................... 35
Maximum HGBP Time ...................................... 35
HGBP Mode, Vane Target ................................ 35
LWT Control Integral Gain (Ki) Setpt ................ 35
LWT Control Derivative Gain (Kd) Setpt ........... 35
IGV Maximum Travel Setpt ............................... 35
Guide Vane Closed Travel Stop ....................... 35
AF Adjustable Speed Control Algorithm Enable 36
AF Leaving Water Standard Deviation .............. 36
AF Pressure Coefficient Constant ..................... 36
AF Re-Optimization Factor ............................... 36
AF Re-Optimization Timer ................................ 36
AF Boundary Pressure Coefficient Y Intercept .36
AF Boundary Pressure Coefficient Y
Intercept Max ................................................... 37
AF Pressure Error Deadband ........................... 37
AF Proportional Speed Gain ............................. 37
Minimum Capacity Timer Enable ...................... 37
Time Permitted at Minimum Capacity ............... 37
Evaporator Flow Coefficient .............................. 37
Evaporator Flow Equation Exponent ................ 37
Evaporator Fluid Coefficient .............................. 38
Condenser Flow Coefficient .............................. 38
Condenser Flow Equation Exponent ................ 38
Local Atmospheric Pressure ............................. 38
Refrigerant Pressure Analog Output Option ..... 38
Min Delta Pressure Calibration ......................... 38
Max Delta Pressure Calibration ........................ 38
IGV Stroke Time ............................................... 39
Low Differential Oil Pressure Cutout ................. 39
Check Oil Filter Diagnostic ................................ 39
Check Oil Filter Setpoint ................................... 39
Evap Leaving Water Temp Offset ..................... 39
Saturated Evap Rfgt Temp Offset ..................... 39

Information Manual iv
Water Pressure Calibration ............................... 39
Machine Configuration ....................................... 40
Service Settings - Machine Configuration ......... 40
Machine Configuration Group Heading ............. 40
Unit Frequency .................................................. 40
Unit Type ........................................................... 40
Nominal Unit Tons ............................................ 40
Refrigerant Type ................................................ 40
Refrigerant Monitor Type ................................... 40
Starter Type ....................................................... 41
Startup Contactor Test - Y-D Starters Only ....... 41
Rated Load Amps .............................................. 41
Motor Heating Constant .................................... 41
Current Overload Setting #1 .............................. 41
Current Overload Setting #2 .............................. 41
Procedure For Selecting Current Overload Settings
for UCP2 .......................................................... 41
Maximum Acceleration Timer #1 ....................... 44
Maximum Acceleration Timer #2 ....................... 44
Hot Water Control Option .................................. 44
Heatsink Start Inhibit Temperature Setpoint
(FastPak) ......................................................... 44
External Chilled Water Setpoint Option ............. 45
External Current Limit Setpoint Option .............. 45
External Hot Water Setpoint Option .................. 45
Acceleration Time Out Action ............................ 45
Motor Over Temperature Protection .................. 45
Motor Winding RTD Type .................................. 45
High Pressure Cutout Setting ............................ 45
Line Voltage Sensing Option ............................. 45
Unit Line Voltage ............................................... 45
Auxiliary Condenser Option ............................... 46
Heat Recovery Option ....................................... 46
Hot Gas Bypass Option ..................................... 46
Free Cooling Option .......................................... 46
Condenser Pressure Sensor Option ................. 46
Bearing Temperature Sensors Option ............... 46
Discharge Temperature Sensor Option ............ 46
Ice Building Option ............................................ 46
Differential Water Press Sensing Option ........... 46
External Analog Input Type Selection,
4-20 ma/2-10 VDC ........................................... 47
Tracer Option .................................................... 47
TCI Option ......................................................... 47
Printer Option .................................................... 47
Duplex Control Module (DCM) Option ............... 47
IGV Output Type ............................................... 47
Oil Pressure Protection .................................... 47
Programmable Analog Output ........................... 47
Programmable Relay Outputs ........................... 48
Current Transducer Setpoint ............................. 48
Current Transducer at 100% RLA ..................... 48
Compressor Power Source ............................... 48
Refrigerant Monitor Settings Group ................. 49
Refrigerant Monitor Settings Group Heading ... 49
Alarm Level 1 .................................................... 49
Alarm Level 2 .................................................... 49
Alarm Level 3 .................................................... 49
Refrigerant Audible Alarm ................................ 49
Trouble Audible Alarm ...................................... 49
Alarm 1 Latching Status ................................... 49
Alarm 2 Latching Status ................................... 49
Alarm 3 Latching Status ................................... 50
Channel Scanner .............................................. 50
Scanner Channel 1 ........................................... 50
Scanner Channel 2 ........................................... 50
Scanner Channel 3 ........................................... 50
Scanner Channel 4 ........................................... 50
Scanner Dwell Threshold ................................. 50
Auxiliary Input ................................................... 50
Auxiliary Input Alarm ......................................... 50
Analog Output Range ....................................... 50
Refrigerant Monitor Calibration ........................ 51
Refrigerant Monitor Settings Group Heading ... 51
Refrigerant Monitor Mode ................................. 51
Refrigerant Zero Calibration ............................. 51
Refrigerant Span Calibration ............................ 52
Service Tests Group .......................................... 54
Service Tools Group Password Request .......... 54
Service Tools Group Heading .......................... 55
Chilled Water Pump .......................................... 55
Chilled Water Flow Switch Status ..................... 55
Evaporator Differential Water Pressure ............ 55
Evaporator Entering/Leaving Water Pressure .. 55
Condenser Water Pump ................................... 55
Condenser Water Flow Switch Status .............. 55
Condenser Differential Water Pressure ............ 55
Condenser Entering/Leaving Water Pressure .. 55
Starter Dry Run ................................................. 56
Oil Pump Status ................................................ 56
Vane Control Status/Vane Position Commands 56
Vane Position ................................................... 56
HGBP Valve Control Status/Manual Open and
Close Commands ............................................ 56
HGBP Valve Manual Opening/Closing
Duty Cycle ....................................................... 57
Vane Control Status/Manual Load and Unload
Commands ...................................................... 57
Manual Loading/Unloading Duty Cycle ............ 57
AF Manual Speed Control - CVHE/F/G Only .... 57
AF Compressor Speed Command - CVHE/F/G
Only ................................................................. 57
AF Compressor Speed Command - CVHE/F/G
Only ................................................................. 58

v
AF Boundary Pressure Coefficient/AF Pressure Co-
efficient - CVHE/F/G Only ............................... 58
AF Re-Optimization Timer Time Remaining- CVHE/
F/G Only .......................................................... 58
Module Software Revision Levels ..................... 58
Diagnostics Menu .............................................. 59
Diagnostics Group Heading .............................. 59
Menu Settings Password .................................. 59
Diagnostics and Annunciation .......................... 60
Clearing Diagnostics ......................................... 60
New Diagnostic Display .................................... 61
Diagnostics ....................................................... 62
FastPak™ “Settings Group” Menu Record ..... 81
Operator Settings Group: .................................. 81
FastPak™ “Settings Group” Menu Record ..... 82
Service Settings Group: Basic Setups .............. 82
FastPak™ “Settings Group” Menu Record ..... 83
Field Startup Group: ......................................... 83
FastPak™ “Settings Group” Menu Record ..... 85
Machine Configuration Group: .......................... 85
FastPak™ “Settings Group” Menu Record ..... 86
Machine Configuration Group: .......................... 86
FastPak™ “Settings Group” Menu Record ..... 87
Refrigerant Monitor Settings Group: ................. 87
FastPak™ “Settings Group” Menu Record ..... 88
Service Tests Group: ........................................ 88

General
Information Manual 1
General
Literature Change History
CVHE-CLD-1 (February 1995)
Application of the Clear Language Display to the
UCP2 Centravac
CVHE-CLD-1A (February 2000)
Updated information and incorporated FastPak™
items.
About This Manual
This manual describes the application of the Clear
Language Display (CLD) to the UCP2 Centravac. It
describes its use as a machine-mounted human
interface.
A description of the UCP2 reports and message
displays are provided along with additional “Help
Notes” to clarify the display messages. In addition, a
Diagnostics section is also included.
LCD Display
The display on the Clear Language Display is a 2-
line by 40-character liquid crystal display (LCD).
Upper and lower case alphabetic characters can be
displayed,along with numeric and special
characters.
LCD Backlight
The LCD display has an LED backlight so it can be
read in low light conditions.
Keypad
A sealed dirt-proof keypad is used on the unit mount
Clear Language Display. Metal dome switch
actuators respond when any key is pressed. See
Figure 1 .
Important! FACTORY DEFAULT SETTINGS: Menu
items that are programmable using the keypad may
have a selectable choice that is listed as Factory
Default. This Factory Default setting is the software
default that is initially factory-programmed for a new
module assembly and may NOT be the correct
setting for a specific operating chiller. Always review
all settings when any module is replaced to verify
that the settings agree with the desired settings that
were selected at initial startup or programmed at the
factory.
LED Alarm
In addition to the alpha-numeric LCD display, there's
a single discrete LED on the human interface. The
red LED flashes on-off whenever a latching
diagnostic is present and a manual reset is required
to restore full unit operation. The LED is also used to
indicate that a function or control has been set to
manual from within the Service Test Menu. If a
control has been set to manual, the LED is on and
non-flashing. A diagnostic supersedes a manual
operation. As a result, the unit could have a manual
mode set and be in a latching diagnostic. In this case
the LED would flash on-off. The LED is off otherwise.
Figure 1
Keypad Matrix
Local Clear Language
The Local CLD “Clear Language Display” resides at
the Chiller providing display of chiller data and
access to operator/service controls, setpoints, and
chiller set-up information. All information is stored in
non-volatile memory in the Chiller module. The Local
CLD and the Chiller module work together to display
and store information requiring non-volatility.
CHILLER REFRIGERANT COMPRESSOR
CUSTOM
OPERATOR
SETTINGS
SERVICE
SETTINGS SERVICE
TESTS DIAGNOSTICS
Previous +Enter Auto
Next -Cancel Stop
REPORT REPORT REPORT REPORT

Control System
2CVHE-CLD-1A
Control System
Unit Control Panel
Safety and operating controls are housed in the
UCP2 unit control panel, the starter panel, and the
purge control panel.
The UCP2 control is a modular design partitioned by
major function or group of functions. All modules (see
Figure 2 ) communicate with each other through the
Interprocessor Communication Circuit (IPC).
Major components within each control group are
shown in the figure.
Unit-mounted temperature sensors, pressure
transducers, and functional switches provide analog
and binary inputs to the various modules.
The microcomputer-based modules are illustrated in
the figure. All wiring to the modules are to pluggable
terminal blocks.
Figure 2
UCP2 Control Panel
I/O Module
Stepper Mod
Options Mod
Chiller Mod
Circuit Mod

Custom Report
Information Manual 3
Custom Report
Custom Report Group
Reports are added to the custom report group by
pressing the <+> key when the desired report is
being displayed from its normal report location.
Reports are removed from the custom report group
by pressing the <-> key when the desired custom
report is being displayed. The Custom report group
can contain a maximum of 20 reports. When adding
a report to the Custom Report, if the <+> key is
pressed when the Custom Report already contains
20 reports, a message, “Custom Report Is Full,
Report Not Added,” indicating that the Custom
Report is full,will be displayed for 2 seconds. If an
attempt is made to add a report to the Custom Report
that is already in the Custom Report, a message,
“Report Already In Custom Menu”, will be displayed
for 2 seconds.
The Custom Report sequence is as follows:
Report Heading
If no entries are selected for the Custom Report, see
Empty List Display.
Empty Display List
If no entries are selected for the Custom Report, the
second entry is:
The report then wraps around to the report heading
when <Next> is pressed.
If there are items selected for the Custom Report,
then the empty list display is not used. Instead, the
report heading and the selected items are displayed
sequentially as <Next> or <Previous> are pressed.
User Defined Custom Report
Press (Next)(Previous) To Continue
No Items Are Selected For Custom Report:
See Operators Manual To Select Entries

ASHRAE Guideline 3 Report
4CVHE-CLD-1A
ASHRAE Guideline 3 Report
If <Enter> is pressed the ASHRAE Guideline 3
Report Menu is entered, shown at the end of the
Standard Report below. Otherwise, If <Next> is
pressed the Standard Report is entered. The
ASHRAE Guideline 3 Report Entry screen may be
added to Custom Report by pressing the <+> key.
Adding it to the Custom Report allows the user to
access the ASHRAE Guideline 3 Report from the
Custom Menu.
The following are the Standard Report screens, e.g.
not part of the ASHRAE Guideline 3 Report.
ASHRAE Guideline 3 Reports
Time Of Day/Refrigerant Type
Possible values for refrigerant type are: R11, R123,
R12, R134a, R22, R113, R114, R500, or R502.
Chiller Operating Mode
The chiller operating modes display comes up first in
the standard report:
Line 1 (and 2 if needed) indicates a current condition
of the unit as shown in the following table (Table 1) .
In some cases, an associated timer or system
parameter will be displayed that assures the
transition to an expected mode is in progress,
particularly during the unit start-up sequence.
Press (Enter) For ASHRAE Guideline 3 Rpt
Press (Next)(Previous) To Continue
ASHRAE Guideline 3 Report
Press (Next)(Previous) To Continue
Current Time/Date HH:MM xm Mon,XX XXXX
Refrigerant Type: [type]
[Operating mode line 1]
[Operating mode line 2]

ASHRAE Guideline 3 Report
Information Manual 5
Table 1
Operating Modes
Unit Operation Operating Mode Display*
(First Line/Second Line) Unit Operation Operating Mode Display*
(First Line/Second Line)
Stop
Resetting
Run
Unit Is Running
Capacity Limited By Phase Unbalance
Local Stop: Cannot Be Overridden By
Any External Or Remote Device Unit Is Running
Capacity Limited By High Cond Press
Remote Display Stop: Chiller May Be
Set To Auto By Any Ext Or Rmt Device Unit Is Running
Capacity Limited By Low Evap Temp
Remote Run Inhibit
From External Source Unit is Running
Capacity Limited By Vane Open Travel
Stop
Remote Run Inhibit
From Tracer Unit Is Running
Minimum Capacity Due To Vane Closed
Travel Stop
Heat Sink Temp Start Inhibit Unit Is Running in Surge Condition
Diagnostic Shutdown Stop Unit Is Running; Capacity Limited By
Pulldown Rate Based Soft Loading
Auto
Diagnostic Shutdown Auto Unit Is Running; Capacity Limited By
Current Based Soft Loading
Auto
Waiting For Evaporator Water Flow Auto Auto
Waiting For Condenser Water Flow
Auto
Waiting For A Need To Cool
Run
Establishing Evap Water Flow
Establishing Oil Pressure
Waiting For Tracer Communications
To Establish Operating Status Establishing Evap Water Flow
Prelubrication Time: MIN:SEC
Starting Is Inhibited By Staggered Start
Time Remaining: MIN:SEC Evap Water Is Flowing
Prelubrication Time: MIN:SEC
Starting Is Inhibited By Restart
Inhibit Timer: Time Remaining MIN:SEC Evap Water Is Flowing
Performing IGV BPI Search & Calibration
Initialize
Establishing Cond Water Flow
Establishing Oil Pressure Establishing Evap Water Flow
Performing IGV BPI Search & Calibration
Establishing Cond Water Flow
Prelubrication Time: MIN:SEC Unit is Running; Base Loaded
Cond Water Is Flowing
Prelubrication Time: MIN:SEC Unit is Running; Base Loaded
Capacity Limited By High Current
Cond Water Is Flowing
Establishing Oil Pressure Unit is Running; Base Loaded
Capacity Limited By Phase Unbalance
Cond Water Is Flowing
Performing IGV BPI Search and
Calibration
Unit Is Running; Base Loaded
Capacity Limited By High Cond Press
Cond Water Is Flowing
PreStart Unload Time Remaining:
MIN:SEC
Unit Is Running; Base Loaded
Capacity Limited By Low Evap Temp
Start Starting Compressor Unit is Running; Base Loaded
At Vane Open Travel Stop
Run
Unit Is Running Unit is Running; Base Loaded
At Vane Closed Travel Stop
Unit Is Running
Capacity Limited By High Current Unit is Running; Base Loaded
In Surge Condition

ASHRAE Guideline 3 Report
6CVHE-CLD-1A
* Displays are not in any sequence. Some displays will never appear, depending on options and situation
Active Chilled Water Setpoint/Chilled Water
Setpoint Source
Settings source will be one of the following: Front
Panel, Tracer, or External Source.
Active Current Limit Setpt/Current Limit Setpt
Source
Settings source will be one of the following: Front
Panel, Tracer, External Source, or Ice Building.
Refrigerant Monitor
The following item will be displayed if the Analog Rfgt
Monitor is installed.
The following item will be displayed if the IPC Rfgt
Monitor option is installed.
Where (Y) can equal 123, 11, 22, 134a, or 12.
Purge Pumpout Rate/Purge Max Pumpout Rate
The following screen(s) does not appear if the
selected Purge Control/Type is “Stand-Alone Purge.”
Run
Unit Is Running; Base Loaded
Current Based Soft Loading
Run-Ice Build
Unit Is Building Ice
Capacity Limited By High Cond Press
Unit Is Running In Minimum Capacity Unit Is Building Ice
Capacity Limited By Low Evap Temp
Unit Is Running In Minimum Capacity
Time Remaining: MIN:SEC Unit Is Building Ice
Surge Has Been Detected
Run-Unload Unit Is Preparing To Shutdown Ice Building Is Complete
Run-Ice Build
Unit Is Building Ice
Capacity Limited By Vane Open Travel
Stop
Unit Is Running; Transitioning Ice Building
To Normal MIN:SEC
Unit Is Building Ice Post-Lube Post Lubrication
Time Remaining: MIN:SEC
Unit Is Building Ice
Capacity Limited By High Current Stop
Panic Stop
Unit Is Building Ice
Capacity Limited By Phase Unbalance Starter Dry Run
Unit Operation Operating Mode Display*
(First Line/Second Line) Unit Operation Operating Mode Display*
(First Line/Second Line)
Active Chilled Water Setpoint: xxx.x f/c
[settings source] CWS: xxx.x f/c
Active Current Limit Setpoint: xxx %
[settings source] CLS: xxx %
Refrigerant Monitor: xxx.x PPM
Press (Next)(Previous) To Continue
Refrigerant Monitor: xxxx PPM R-YYYY
Press (Next)(Previous) To Continue
Purge Pumpout Rate: xxx.x Min/24Hrs
Purge Max Pumpout Rate: xxx.x Min/24Hrs

ASHRAE Guideline 3 Report
Information Manual 7
Purge Total Pumpout Time/ Purge Total Run
Time
The following screen(s) does not appear if the
selected Purge Control/Type is “Stand-Alone Purge.”
Purge Operating Mode/Purge Status
The following screen(s) does not appear if the
selected Purge Control/Type is “Stand-Alone Purge.”
Possible values of [Mode] are: Auto, Stop, On, or
Adaptive.
Possible values of [Status] are:
Saturated Evap Temperature/Evap Refrigerant
Pressure Compressor Discharge Temp
Compressor Discharge Temperature shown only if
discharge temperature is installed.
Compressor Starts and Running Time
The starts and hours counters are displayed as
follows:
Discharge Oil Pressure, Oil Tank Pressure
This screen is only displayed if the “Oil Pressure
Protection” setpoint is set to “Transducer” or “Xducer
& Switch.”
Differential Oil Pressure, Oil Temperature
This screen is only displayed if the “Oil Pressure
Protection” setpoint is set to “Transducer” or “Xducer
& Switch.”
' Differential Oil Pressure: xxx.x [units]' is only
displayed if the “Oil Pressure Protection” setpoint is
set to “Transducer” or “Xducer & Switch.” If 'Switch' is
selected as the setpoint, then ' Differential Oil
Pressure Switch: [Status]' is displayed where
Status is open or closed.
For FastPak, Differential Oil Pressure: xxx.x [units],
this screen is only displayed if the “Oil Pressure
Protection Setpoint” is set to “Diff Xducer" If 'Switch'
is selected as the setpoint, then ' Differential Oil
Pressure Switch: [Status]' is displayed where
Status is open or closed.
The Possible value for [units] is “psid” or “kPa”
dependent upon whether English or SI units are
selected.
Bearing Temperatures #1 and #2
The following will be displayed only if the Bearing
Temp Sensors Option is Installed.
Evaporator Entering and Leaving Water
Temperatures
Purge Total Pumpout Time: xx,xxx.x Min
Purge Total Run Time: xx,xxx.x Hrs
Purge Operating Mode: [Mode]
Purge Status: [Status]
Idle (Condensing Unit is Off)
Running (Condensing Unit is On)
Pumpout (Temperature initiated
Pumpout)
Service Pumpout (Pumpout initiated by the
service switch)
Running - Pumpout Inhibited
By Low Temp. (Pumpout inhibited by low
liquid temp)
Pumpout Maximum Rate
Disabled (Max. Pumpout Rate alarm
disabled)
Saturated Evap Rfgt Temp: xxx.x f/c
Compressor Discharge Temp: xxx.x f/c
Compressor Starts: xxxxx
Compressor Running Time: HRS:MIN:SEC
Discharge Oil Pressure: xxx.x psig
Oil Tank Pressure: xxx.x psig
Differential Oil Pressure: xxx.x [units]
Oil Tank Temperature: xxx.x f/c
Bearing Temperature 1: xxx.x f/c
Bearing Temperature 2: xxx.x f/c
Evap Entering Water Temp: xxx.x f/c
Evap Leaving Water Temp: xxx.x f/c

ASHRAE Guideline 3 Report
8CVHE-CLD-1A
Saturated Evap Temperature/Evap Refrigerant
Pressure
Evaporator Approach Temp.
Evaporator Entering/Leaving Water Pressure
The following will be displayed only if the low
pressure (< or = to 150 psig) Differential Water
Pressure Sensor Option is Installed.
Evaporator Differential Water Pressure
The following will be displayed only if the Differential
Water Pressure Sensor Option is Installed.
Evaporator Water Flow
The following is displayed only if the Differential
Water Sensing Option is installed.
The possible values for units are “gpm” or “lpm.”
Chilled Water Flow Switch Status
The following will be displayed only if the Differential
Water Sensing Option is not installed. This screen
displays the status of the chilled water flow switch
status at the input to the UCM.
Possible values for [y] are: Flow Switch is Open/No
Flow or Flow Switch is Closed/Flow.
Chiller Tons
The following will be displayed only if the Differential
Water Sensing Option is installed.
The possible values for units are “Tons” or “KW.”
Cond Entering and Leaving Water Temps
Dashes will be displayed for condenser entering or
leaving water temperature if the corresponding input
is open or shorted.
Saturated Cond Temperature/Cond Refrigerant
Press
Condenser Approach Temp.
Condenser Entering/Leaving Water Pressure
The following will be displayed only if the low
pressure (< or = to 150 psig) Differential Water
Pressure Sensor Option is Installed.
Condenser Differential Water Pressure
The following will be displayed only if the Differential
Water Pressure Sensor Option is Installed.
Saturated Evap Rfgt Temp: xxx.x f/c
Evap Rfgt Pressure: xxx.x psig
Evaporator Approach Temp.: xx.x f/c
Press (Next)(Previous) To Continue
Evap Entering Water Pressure:xx.x psid/kPa
Evap Leaving Water Pressure: xx.x psid/kPa
Evap Differential Wtr Press: xx.x psid/kPa
Press (Next)(Previous) To Continue
Approx Evaporator Water Flow:xxx.x gpm/lpm
Press (Next)(Previous) To Continue
Chilled Water Flow Switch Status:
[y]
Approximate Chiller Capacity: xxxx Tons/KW
Press (Next)(Previous) To Continue
Cond Entering Water Temp: xxx.x f/c
Cond Leaving Water Temp: xxx.x f/c
Saturated Cond Temp: xxx.x f/c
Cond Rfgt Pressure: xxx.x psig
Condenser Approach Temp.: xx.x f/c
Press (Next)(Previous) To Continue
Cond Entering Water Pressure:xx.x psid/kPa
Cond Leaving Water Pressure: xx.x psid/kPa
Cond Differential Wtr Press: xx.x psid/kPa
Press (Next)(Previous) To Continue

ASHRAE Guideline 3 Report
Information Manual 9
Condenser Water Flow
The following will be displayed only if the Differential
Water Sensing Option is installed.
The possible values for units are “gpm” or “lpm.”
Condenser Water Flow Switch Status
The following screen is displayed only if the
Differential Water Pressure Sensor Option is not
Installed. This screen displays the status of the
condenser water flow switch status at the input to the
UCM.
Possible values for [y] are Flow Switch is Open/No
Flow or Flow Switch is Closed/Flow
Aux. Bundle or Heat Recovery Temps
The following will be displayed only if either the Heat
Recovery Option or Aux Condenser Option is
installed.
Approx Condenser Water Flow: xxx.x gpm/lpm
Press (Next)(Previous) To Continue
Condenser Water Flow Switch Status:
[y]
Aux/Heat Rcvy Ent Wtr Temp: xxx.x f/c
Aux/Heat Rcvy Lvg Wtr Temp: xxx.x f/c

Chiller Report
10 CVHE-CLD-1A
Chiller Report
The Chiller Report sequence is as follows:
Chiller Operating Mode
Friendly mode line 1 is indicative of a unit mode.
Friendly mode line 2 is usually a verbal continuation
of line 1 and can be viewed as a continuous
message along with line 1. In some cases Friendly
mode line 2 is the display of an associated timer or
system parameter.
[Friendly mode] will be one of the following:
Chiller Status, Water Temps & Setpts
Press (Next)(Previous) To Continue
Friendly mode line 1
Friendly mode line 2
Friendly Mode (First Line/second Line)
Display is Blank
Resetting
Local Stop: Cannot Be Overridden By
Any External Or Remote Device
Remote Display Stop: Chiller May Be
Set To Auto By Any Ext Or Rmt Device
Remote Run Inhibit From Remote Computer
Remote Run Inhibit From External Source
Remote Run Inhibit From Tracer
Run Inhibit From DCM
Heat Sink Temperature Start Inhibit
Diagnostic Shutdown Stop
Diagnostic Shutdown Auto
Auto
Waiting For Evaporator Water Flow
Auto
Waiting For A Need To Cool
Auto
Waiting For A Need To Heat
Waiting For Tracer Communications
To Establish Operating Status
Starting Is Inhibited By Staggered Start
Time Remaining: MIN:SEC
Transitioning To Free Cooling
Waiting For Cond Water Flow
Opening Free Cooling Valves
Cond Water Is Flowing
Closing Free Cooling Valves
Unit Running; Last Mode Free Cooling Limit
Time Remaining To End Of Limit: MIN:SEC
Transitioning To Free Cooling
Waiting For IGV Positioning To Complete
Unit Is Free Cooling
Starting Is Inhibited By Restart
Inhibit Timer: Time Remaining MIN:SEC
Establishing Cond Water Flow
Establishing Oil Pressure
Establishing Cond Water Flow
PreLubrication Time: MIN:SEC
Cond Water Is Flowing
Establishing Oil Pressure
Starting
Unit Is Running

Chiller Report
Information Manual 11
Unit Is Running
Capacity Limited By High Current
Unit Is Running
Capacity Limited By Phase Unbalance
Unit Is Running
Capacity Limited By High Cond Press
Unit Is Running
Capacity Limited By Low Evap Temp
Unit Is Running; Capacity Limited By
Vane Open Travel Stop
Unit is Running; Minimum Capacity
Due To Vane Closed Travel Stop
Unit Is Running In Surge Condition
Unit Is Running; Capacity Limited By
Pulldown Rate Based Soft Loading
Unit Is Running; Capacity Limited By
Current Based Soft Loading
Unit Is Running; Hot Water Control
Unit Is Running; Hot Water Control
Capacity Limited By High Current
Unit Is Running; Hot Water Control
Capacity Limited By Phase Unbalance
Unit Is Running; Hot Water Control
Capacity Limited By High Cond Press
Unit Is Running; Hot Water Control
Capacity Limited By Low Evap Temp
Unit Is Running; Hot Water Control
At Vane Open Travel Stop
Unit is Running; Hot Water Control
At Vane Closed Travel Stop
Unit Is Running; Hot Water Control
In Surge Condition
Unit Is Running; Hot Water Control
Pulldown Rate Based Soft Loading
Unit Is Running; Hot Water Control
Current Based Soft Loading
Unit is Running; Base Loaded
Unit is Running; Base Loaded
Capacity Limited By High Current
Unit is Running; Base Loaded
Capacity Limited By Phase Unbalance
Unit Is Running; Base Loaded
Capacity Limited By High Cond Press
Unit Is Running; Base Loaded
Capacity Limited By Low Evap Temp
Unit Is Running; Base Loaded
At Vane Open Travel Stop
Unit is Running; Base Loaded
At Vane Closed Travel Stop
Unit Is Running; Base Loaded
In Surge Condition
Unit Is Running; Base Loaded
Pulldown Rate Based Soft Loading
Unit Is Running; Base Loaded
Current Based Soft Loading
Unit Is Running In Hot Gas Bypass
Unit Is Running In Minimum Capacity
Time Remaining: HR:MIN:SEC
Unit Is Preparing To Shutdown

Chiller Report
12 CVHE-CLD-1A
Chiller Operating Mode
The chiller operating modes display comes up first in
the standard report:
Line 1 (and 2 if needed) indicates a current condition
of the unit as shown in the preceding table(Table 1) .
In some cases, an associated timer or system
parameter will be displayed that assures the
transition to an expected mode is in progress,
particularly during the unit start-up sequence.
Active Chilled Water Setpoint/Evap
Leaving Water Temp
If the chiller is in the Ice Making or Ice Making
Complete state, the following display is substituted
for the above display:
If the chiller is in the hot water control state, the
following display is substituted for the above display:
Active Chilled Water Setpoint/Chilled
Water Setpoint Source
Settings source will be one of the following: Front
Panel, Tracer, External Source, or Duplex Control.
Active Ice Termination Setpoint/Ice
Termination Setpoint Source
The following will be displayed only if the Ice Building
Option is installed.
Settings source will be one of the following: Front
Panel or Tracer.
Active Hot Wtr Setpoint/Hot Wtr Setpoint
Source
The following will be displayed only if the Hot Water
Control Option is Installed.
Settings source will be one of the following: Front
Panel, Tracer, or External Source.
[Operating mode line 1]
[Operating mode line 2]
Active Chilled Water Setpoint:xxx.x f/c
Evap Leaving Water Temp: xxx.x f/c
Active Ice Termination Setpoint: xxx.x f/c
Evap Entering Water Temp: xxx.x f/c
Active Hot Water Setpoint: xxx.x f/c
Cond Leaving Water Temp: xxx.x f/c
Active Chilled Water Setpoint: xxx.x f/c
[settings source]CWS: xxx.x f/c
Active Ice Termination Setpoint: xxx.x f/c
[settings source] ITS: xxx.x f/c
Active Hot Water Setpoint: xxx.x f/c
[settings source] HWS: xxx.x f/c

Chiller Report
Information Manual 13
Evaporator Entering and Leaving Water
Temperatures
Cond Entering and Leaving Water Temps
Dashes will be displayed for condenser entering or
leaving water temperature if the corresponding input
is open or shorted.
Active Current Limit Setpoint
Active Current Limit Setpoint/Current
Limit Setpoint Source
Settings source will be one of the following: Front
Panel, Tracer, External Source, or Ice Building.
Evaporator Water Flow/ Condenser
Water Flow
The following will be displayed only if the Differential
Water Sensing Option is installed.
The possible values for units are “gpm” or “lpm.”
Chiller Tons
The following will be displayed only if the Differential
Water Sensing Option is installed.
The possible values for units are “Tons” or “KW.”
Outdoor Temperature
If the outdoor air temperature input is open or
shorted and neither Outdoor Air Reset nor Low
Ambient Lockout is enabled, display “------” in place
of “xxx.x F.” Otherwise the temperature received
from the chiller module is displayed.
Aux. Bundle or Heat Recovery Temps
The following will be displayed only if either the Heat
Recovery Option or Aux Condenser Option is
installed.
Chilled Water Setpoint Source
Settings source will be one of the following: Front
Panel, Tracer, or External Source.
Reset condition will be one of the following: None,
Outdoor Temp, or Return Wtr Temp.
Evap Entering Water Temp: xxx.x f/c
Evap Leaving Water Temp: xxx.x f/c
Cond Entering Water Temp: xxx.x f/c
Cond Leaving Water Temp: xxx.x f/c
Active Current Limit Setpoint: xxx %
Press (Next)(Previous) To Continue
Active Current Limit Setpoint: xxx %
[settings source] CLS: xxx %
Approx Evaporator Water Flow:xxx.x gpm/lpm
Approx Condenser Water Flow: xxx.x gpm/lpm
Approximate Chiller Capacity: xxxx Tons/KW
Press (Next)(Previous) To Continue
Outdoor Air Temperature: xxx.x f/c
Press (Next)(Previous) To Continue
Aux/Heat Rcvy Ent Wtr Temp: xxx.x f/c
Aux/Heat Rcvy Lvg Wtr Temp: xxx.x f/c
Chld Wtr Setpt Source: [settings source]
Reset Condition: [reset condition]

Chiller Report
14 CVHE-CLD-1A
Current Limit Setpoint Source
Settings source will be one of the following: Front
Panel, Tracer, External Source, or Ice Building.
Hot Water Setpoint Source
The following will be displayed only if Hot Water
Control is Installed.
Settings source will be one of the following: Front
Panel, Tracer, or External Source.
Ice Termination Setpoint Source
The following will be displayed when/if remote
computer is installed.
Settings source will be one of the following: Front
Panel or Tracer.
Cur Lim Setpt Source:[settings source]
Press (Next)(Previous) To Continue
Hot Water Setpt Source: [settings source]
Press (Next)(Previous) To Continue
Ice Termn Setpt Source: [settings source]
Press (Next)(Previous) To Continue

Refrigerant Report
Information Manual 15
Refrigerant Report
Report Heading
Evaporator and Condenser Refrigerant
Pressure
Saturated Evap Temperature/Evap
Refrigerant Pressure
Saturated Cond Temperature/Cond
Refrigerant Press
Saturated Evap Temp. and Discharge
Temp.
The Discharge Temp will be displayed only if the
Discharge Sensor Option is installed.
Purge Operating Mode/Purge Status
The following screen(s) does not appear if the
selected Purge Control/Type is “Stand-Alone Purge.”
Possible values of [Mode] are: Auto, Stop, On, or
Adaptive.
Possible values of [Status] are:
Purge Alarm Message
The following screen(s) is not displayed if the
selected Purge Control/Type is “Stand-Alone Purge.”
Possible values for [Status] are: No Diagnostics
Present (the [Help Message] is: Press (Next)
(Previous) To Continue) or Diagnostic Alarm (the
[Help Message] is: Go to Diag. Menu for Description/
Reset).
Refrigerant Temp & Pressure Report
Press (Next)(Previous) To Continue
Evap Rfgt Pressure: xxx.x psig
Cond Rfgt Pressure: xxx.x psig
Saturated Evap Temp: xxx.x f/c
Evap Rfgt Pressure: xxx.x psig
Saturated Cond Temp: xxx.x f/c
Cond Rfgt Pressure: xxx.x psig
Saturated Evap Rfgt Temp: xxx.x f/c
Compressor Discharge Temp: xxx.x f/c
Purge Operating Mode: [Mode]
Purge Status: [Status]
Idle (Condensing Unit is Off)
Running (Condensing Unit is On)
Pumpout (Temperature Initiated
pumpout)
Service Pumpout (Pumpout initiated by service
switch)
Running - Pumpout inhibited by
low temp. (Pumpout inhibited by low
liquid temp)
Pumpout Maximum Rate
Disabled (Max. pumpout rate alarm
disabled)
Purge Alarm Msg: [Status]
[Help Message]
Other manuals for CVHE
8
This manual suits for next models
4
Table of contents
Other Trane Monitor manuals

Trane
Trane Tracer MP580 Reference guide

Trane
Trane AdaptiView User manual

Trane
Trane Symbio 800 Control Upgrade Kit User manual

Trane
Trane TruSense RMWH Installation and operating instructions

Trane
Trane Tracer Summit User manual

Trane
Trane Tracer AdaptiView User manual

Trane
Trane Tracker Reference guide

Trane
Trane Tracer AdaptiView User manual

Trane
Trane Tracer TD-5 Installation and operating instructions

Trane
Trane BCU Operator Display Instruction Manual