WARNING: INSTALLATION AND
MAINTENANCE MUST BE CARRIED OUT BY
SUITABLY QUALIFIED AND COMPETENT
PERSONEL ONLY. HAZARDOUS VOLTAGES
MAY BE PRESENT ON THE CONNECTION
TERMINALS.
INSTALLATION
•Install this product in accordance with local regulations,
codes and instructions.
•An external fuse must be fitted in-line with the PSU.
Recommended fuse: 0.5A Type F with a breaking capacity
of 35A or greater. Fuse voltage rating must be greater than
the maximum supply voltage.
•All conductors carrying hazardous voltage must have
external switching or disconnect mechanisms fitted that
provide at least 3mm of contact separation in all poles. The
switch must be suitably located; easily reached and marked
as the disconnecting device.
•Signal cables connected to this device must not exceed 30
metres long.
•If signal cables are routed outside the building, install extra
surge-protection devices.
•Current measurement input, USB and all outputs: Observe
maximum allowable voltages. All circuits connected to
these connectors must be limited-energy and insulated by
double/reinforced insulation from mains voltages according
to IEC 61010-1:2010
Failure to install or operate the unit in
accordance with the above requirements may
impair the electrical safety of the unit.
Voltage measurements: An external UL
recognized or listed overcurrent protection
device (fuse or circuit breaker) must be fitted
in-line with the voltage lead. Recommended
fuse: 0.5A Type F with a breaking capacity of
35A or greater. Fuse voltage rating must be
greater than the maximum voltage that will be
applied to the meter.
MAINTENANCE
•Before cleaning, inspection or maintenance, isolate all power
sources to the unit.
•There are no user-serviceable parts inside this unit. Never
open the case.
•Inspect all external wiring connections at regular intervals.
Replace any damaged wiring and tighten any loose
connections.
•To clean the unit, use a dry cloth to wipe the casing.
•Take great care connecting the supply. If you connect power
to the wrong terminals, it may destroy the unit.
Size of the cutout in the panel:
Square: 68 x 68mm (2.68in)
Round: 96.2 mm (3.79in) [+0.7 -0mm]
You need the software to configure the setpoints and outputs.
Size
Safety Warnings