Trumeter Shunt Series User manual

APM
SHUNT METER
* Non-Isolated,
for Low Side
DC Applications
Only *
CAUTION: Risk of Danger
Read complete instructions prior to installation
and operation of the unit
CAUTION: Risk of electric shock
Before installation, read the Safety Warnings overleaf.
Intended Use: The APM has been specifically designed for engineers requiring an effective way to monitor and
display data. The APM accepts a range of electrical inputs (depending on the model) and displays the data on its
integrated multi-format display. The APM has been designed for installation into electrical cabinets or display
panels. Output models include two independent outputs that can be configured by the user to be either digital set-
point outputs or 4-20mA monitor outputs.
DIP Switches
Sw
Pos Bar Graph
Item 1234 Input Range
1 0000 Custom (defined in software application)
2 1000 60mV 10A
3 0100 50mV 20A
4 1100 75mV 30A
5 0010 60mV 40A
6 1010 50mV 50A
7 0110 60mV 60A
8 1110 50mV 100A
9 0001 60mV 100A
10 1001 50mV 200A
11 0101 60mV 300A
12 1101 60mV 400A
13 0011 50mV 500A
14 1011 75mV 500A
15 0111 60mV 600A
16 1111 75mV 1000A
Use the DIP switches to set the Shunt Meter
bar graph range and annunciators to standard
values. Use the software application to
configure custom settings.
The switch positions are shown in the table
where:
0 = OFF and 1 = ON.
VALUE UNIT
INPUT Voltage
Range 0 –1VDC
Impedance 1Meg
Accuracy 0-200mV: 0.1% of full scale or
0.5mV, whichever is greater
201-1000mV: 0.2% of full scale
Max Working
Voltage (Input
to COM) 1.5V
Max Continuous
Voltage
Withstand (Input
to COM)
30VDC
Size
68 x 68mm (2.68in) +0.7 -0mm
Size of the cutout in the panel:
!! Note: This meter is designed for low side
DC applications only, and must only be
connected to current shunts that have been
installed between the load and ground !!
The DIP switches
are on the back of
the unit.
Safety Warnings
WARNING: INSTALLATION AND MAINTENANCE MUST BE CARRIED OUT
BY SUITABLY QUALIFIED AND COMPETENT PERSONEL ONLY.
HAZARDOUS VOLTAGES MAY BE PRESENT ON THE CONNECTION
TERMINALS. INSTALLATION
•Install this product in accordance with local regulations, codes and instructions.
•All fuses must be 0.5A / 250V Type F with a breaking capacity of 35A or greater.
•All conductors carrying hazardous voltage must have external switching or
disconnect mechanisms fitted that provide at least 3 mm of contact separation in all
poles.
•Signal cables connected to this device must not exceed 30 metres long.
•If signal cables are routed outside the building, install extra surge-protection
devices.
•Power supply, current input, USB and all outputs: Observe maximum allowable
voltages. All circuits connected to these connectors must be limited-energy and
insulated by double/reinforced insulation from mains voltages according to IEC
61010-1:2010
Failure to install or operate the unit in accordance with the
above requirements may impair the electrical safety of the unit.
Voltage measurements: An external UL recognized or listed
overcurrent protection device (fuse or circuit breaker) must be
fitted in-line with the voltage lead. Recommended fuse: 0.5A
Type F with a breaking capacity of 35A or greater. Fuse voltage
rating must be greater than the maximum voltage that will be
applied to the meter. MAINTENANCE
•Before cleaning, inspection or maintenance, isolate all power sources to the unit.
•There are no user-serviceable parts inside this unit. Never open the case.
•Inspect all external wiring connections at regular intervals. Replace any damaged
wiring and tighten any loose connections.
•To clean the unit, use a dry cloth to wipe the casing.
•Take great care connecting the supply. If you connect power to the wrong terminals,
it may destroy the unit.
Operating Specification
www.GlobalTestSupply.com
Find Quality Products Online at: sales@GlobalTestSupply.com

Specification Outputs
VALUE EN: 4-20 mA analogue output using setpoint 1.
Note: DC PSU ONLY
DE: 4-20 mA Analogausgang mit Sollwert 1.
FR: Sortie analogique 4 à 20 mA via le point de consigne 1.
ES: 4-20 mA salida analógica utilizando punto de ajuste 1.
IT: Uscita analogica 4-20 mA con valore di riferimento 1.
EN: Using a diode-protected relay on setpoint 1.
Note: DC PSU ONLY
DE: Mit einem diodengeschützten Relais auf Sollwert 1.
FR: Utilisation d’un relais avec diode de protection contre l’inversion de
polarité au point de consigne 1.
ES: Usando un relé de diodo protegido en punto de ajuste 1.
IT: Utilizzare un relè protetto da diodo su valore di riferimento 1.
EN: Analogue Output and relay using both setpoints.
Note: DC PSU ONLY
DE: Analogausgang und Relais mit beiden Sollwerten.
FR: Sortie analogique et relais utilisant les deux points de consigne.
ES: Salida analógica y el relé usando ambos puntos de ajuste.
IT: Uscita analogica e relè con entrambi i valori di riferimento.
EN: Use the Reset input with the peak hold function
Note: DC PSU ONLY
DE: Verwenden Sie den Reset-Eingang mit der Peak-Hold-Funktion
FR: Effectuer l’entrée de réinitialisation via la fonction de maintien de la
valeur de crête
ES: Utilice la entrada Reset con la función de mantenimiento de pico
IT: Utilizzare l'ingresso di reset con la funzione Mantieni
Environment
Temperature - operating –10 to +60 deg C
Temperature - storage –40 to +70 deg C
Altitude 2000 metres
Relative Humidity (non-condensing) - Continuous 0 –85 %
Relative Humidity (non-condensing) - Intermittent 0 –95 %
Pollution Degree (IEC664) 2
IP rating (from the front) IP65
NEMA Rating (from the front) Type 4 & Type 12
Vibration
Shock
Power supply
Input 12-24V DC +/-10%
Max Power 1.6W
Supply Frequency DC
Isolation None
Display
Number of digits 4
Digit height 12 mm
Number of bar-graph segments 40
Number of starburst message characters 4
Backlight colours Red, Green, White
LCD Positive or negative
Digit update frequency 0.08 –21 sec
Bar-graph update frequency 0.08 –21 sec
Viewing angle +/-70° Horizontal
+/-70° Vertical
Open Collector Outputs
Max voltage (open collector outputs) 34 V
Max current (open collector outputs) 500 mA
Analogue Output
Output 4-20 mA
Accuracy 0.50 %
Resolution 0.02 mA
Connections
Type Screw Terminals
Wire type Solid or Stranded
Min. cable temperature rating 65 deg C (149F)
Wire strip length 6.5mm to 7mm
(0.26” to 0.28”)
Wire gauge 0.8mm² - 3.3mm²
(18AWG to 12AWG)
Torque 0.5-0.6Nm
(4.42-5.31 lbf-in)
Certification CE
cULus
IEC 61010-1
In the Box
APM
Getting started & safety guide
Gasket
Retaining clip
Panel Cut-out: 68 x 68 mm (2.68 in) +0.7 -0 mm
(0.02 in). Max. panel thickness: 10 mm.
Dimensions: Depth behind panel inside front: 55mm
(2.17in) incl. external connections. Weight: 180 grams.
-
+
12 to 24V
DC
PSU Fuse
0V
4-20mA
Output
-
+
12 to 24V
DC
PSU Fuse
RELAY
+
-
-
+
12 to 24V
DC
PSU Fuse RELAY
+
-
0V
4-20mA
- ~
+ ~
12 to 24V
AC or DC
PSU Fuse
Wiring Diagrams
CURRENT INPUT
Ground referenced
DC POWERED (12 to 24V)
CURRENT INPUT
Ground Referenced
DC POWERED (12 to 24V)
WITH SETPOINT OUTPUT
CURRENT INPUT
Ground Referenced
DC POWERED (12 to 24V)
WITH EXTERNAL RESET
-
+
12 to 24VDC
PSU
Fuse
NOTE:
Max Voltage 1.5V
Referenced to
COM Terminal
SHUNT
-
+
12 to 24VDC
PSU
Fuse SETPOINT 1
OUTPUT
SHUNT
0V
NOTE:
Max Voltage 1.5V
Referenced to
COM Terminal
-
+
12 to 24VDC
PSU
Fuse
SHUNT
NOTE:
Max Voltage 1.5V
Referenced to
COM Terminal
www.GlobalTestSupply.com
Find Quality Products Online at: sales@GlobalTestSupply.com
Other Trumeter Measuring Instrument manuals