Operating Instructions INDC60ODP
103424
IMPORTANT: READ AND SAVE THESE INSTRUCTIONS. Read carefully before attempting to assemble, install, operate or
maintain the product described. Protect yourself and others by observing all safety information. Failure to comply with instructions could
result in personal injury and/or property damage! Retain instructions for future reference.
VES-Artex Industrial
Ceiling Fan
INDC60ODP
Description
The VES-Artex model INDC60ODP ceiling fan is a high efficiency, industrial ceiling
fan. It is designed to create air velocity and a cooling effect on high speed. The
lower speeds can be used for reduced velocity or heat de-stratification. The low
speed gently de-stratifies the air giving a constant room temperature. The
INDC60ODP is outdoor rated, ETL Certified in the United States and Canada and
comes with plug and controller.
Unpacking
1. After opening carton, look for concealed damage.
2. If concealed damage is found, immediately le claim with carrier.
General Safety Information
Disconnect power
supply before wiring
connections are made to prevent possible
electric shock or damage to equipment.
Read and follow
instructions carefully.
Failure to comply with instructions could
result in re, electric shock, injury to
persons and/or damage to equipment.
Follow all
maintenance
procedures enclosed.
Failure to properly
ground unit could
result in severe electrical shock or death.
1. All wiring should conform to the
National Electrical Code in the United
States and local regulations.
2. Make certain the entire installation
is grounded as a precaution against
possible electrical shock.
3. Do not exceed maximum amperage
rating of the ceiling fan as overload-
ing can result in damage to ceiling
fan and control.
4. When wiring an electrical appliance
or device follow all electrical and
safety codes, as well as the most
recent National Electrical Codes
(NEC) and the Occupational Safety
and Health Act (OSHA).
Assembly
1. Remove all ceiling fan parts from the
box.
2. Tools and supplies needed – Flat and
Phillips screwdriver – 9/16” and 3/8”
open wrench or adjustable wrench,
2-3 wire nuts.
3. Install a junction box to accept the
wiring of the fan. In many cases, a
qualied electrician will be required
to install the outlet box keeping with
local electrical codes or to meet the
National Electrical Codes (NEC).
4. For installation to open web steel
joist – use threaded J-hook as sup-
plied. For wood joist construction
– use J-hook with lag threads. For
attachment in concrete, drill concrete
anchors into the concretes as per
specication applicable to National
Electrical Code procedures.
Printed in China
Version 2
2020
VES-Artex002
2020
Specications
Model Size Volts Amps Watts RPM Down-Rod Down-Rod
60"120 0.8 95 250 24" Down Draft
Type
PUM-012-INDC60-01

E
N
G
L
I
S
H
Operating Instructions INDC60ODP
2
Installation
Safety Product Inspection of Fan Prior to
Installation (Figure #1 and #2)
To reduce the risk of re
or electric shock, do not
use this fan with any solid-state speed con-
trol device.
To reduce the risk of per-
sonal injury, do not bend
the blade brackets when installing the brack-
ets, balancing the blades or cleaning the
fan. Do not insert foreign objects in between
rotating fan blades.
1. Make certain set screw (4) is tight to
ascertain wobble free operation.
2. Make certain cotter pin (5) is in place
and secure.
3. Make certain lock-nut (7) is tight and set
screw (6) is in place and secure.
4. Slide lower canopy (8) down over
rubber gasket (21) to create a tight seal.
5. Make certain lower canopy set screws
(2) are tight on downrod (1).
6. Make certain cotter pin (13) is in place
and secure.
7. Make certain bolt, cotter pin and nut
(16) are tight.
Hanging of Fan (Figure #1 and #2)
1. Wind one nut (9) down to bottom of J
hook (12) towards the curve. Add a lock
washer and then at washer (3) on top
of the nut (9).
2. Tighten slip loop of safety cable (11)
around J hook shaft (12) and a
structural member of the building. Leave
1 inch of slack in the cable.
Make certain crimp on safety
loop is secure (See Figure
#4). Make certain safety cable is attached
properly to hook and structural member.
3. Drill a 1/2” pilot hole for J hook. Put J
hook (12) through pilot hole in joist. Add
at washer and then lock washer (20)
and nut (22). Do not tighten completely
until fan is put in place on J hook. A
lubricant should not be used on the
single mounting screw; and the pilot
hole should be drilled no larger than the
minor diameter of the mounting screw
threads, and at least 38 mm (1-1/2”) of
the threaded part of the mounting screw
should be secured into a structural
wood joist to provide secure mounting.
4. Loosen set screw (18) on top canopy
(19) on fan downrod (1) and lower the
canopy to make room to place rubber
grommet (14) onto
mounting hook.
5. Tighten top nut (22) on J hook to raise
fan into proper installation
position.
6. Must be plugged into an approved
duplex receptacle. (see Figure #5 for
control wiring diagram).
If the fan is installed
outdoor or in a harsh
environment a GFCI (Ground Fault Circuit
Interrupter) outlet should be used.
7. Raise top canopy (19) up the downrod
to cover hook. Leave 1/8” gap between
top canopy (19) and hanging surface
(so downrod does not move o center
which could make fan wobble or vibrate
and transmit motor noise to ceiling
surface). Tighten set screw (18).
8. Attach blades (23) to motor (24) with
blade bolts (25). (Figure #3) The blade
(24) should be positioned below the
blade arm bracket (26) when attaching
to the motor to get proper air ow and
direction.
VES-Artex Industrial Ceiling Fan
Figure #2
1
18
19
14
16
11
12
20 22
9
13 10
15
3
Figure #1
8
1
5
4
2
6
7
17 11
Safety
Cable
25
24
23 26
Figure #3
Figure #4
21

E
N
G
L
I
S
H
Operating Instructions INDC60ODP
3
IMPORTANT: VES-Artex
fan model INDC60ODP; for
wiring optional included
controller please see
instructions included with the
controller.
Control Installation:
The wall control switch has
been investigated and found
acceptable for use as a speed
control switch.
Models INDC60ODP
Length of downrod is
measured as shown above.
Top of Rubber
Grommet
Flat surface
blades attach.
24”
_______________________________________________________________________________________________________

E
N
G
L
I
S
H
Operating Instructions INDC60ODP
4
Maintenance Estimated Approved S - Scheduled Work Performed/
Date Running Hours Inspector Name: U - Unscheduled Notes/Comments
______________________________________________________________________________________
______________________________________________________________________________________
______________________________________________________________________________________
______________________________________________________________________________________
______________________________________________________________________________________
______________________________________________________________________________________
______________________________________________________________________________________
______________________________________________________________________________________
______________________________________________________________________________________
______________________________________________________________________________________
______________________________________________________________________________________
______________________________________________________________________________________
______________________________________________________________________________________
______________________________________________________________________________________
______________________________________________________________________________________
______________________________________________________________________________________
______________________________________________________________________________________
______________________________________________________________________________________
______________________________________________________________________________________
______________________________________________________________________________________
______________________________________________________________________________________
______________________________________________________________________________________
______________________________________________________________________________________
______________________________________________________________________________________
______________________________________________________________________________________
Maintenance
Always disconnect the
power supply before
servicing the ceiling fan or working with the
unit for any reason.
Parts replacement and
troubleshooting to be
performed only by qualied personnel.
Do not place ngers or
objects in the ceiling
fan while motor is connected to the power
source.
Do not attach foreign
objects to the blades of
the ceiling fan.
Do not use gasoline,
benzene, thinner, harsh
cleaners, etc., which are dangerous and will
damage the ceiling fan.
If you see noticeable
vibration, wobbling or
wear the fan should be removed from service
and repaired or replaced by a qualied
maintenance technician or electrician.
• Below is the maintenance schedule
that must be followed and lled out to
be eligible for warranty and ensure safe
operation.
• Inspection should be every 3500
running hours or every 6 months.
• Maintenance schedule should include
repeating the product inspection
procedure and the fan hanging
procedure.
Initial Installation Date : ______________________ Name of installation supervisor : ______________________________
Maintenance Schedule

E
N
G
L
I
S
H
Operating Instructions INDC60ODP
6
Troubleshooting Chart
VES-Artex Industrial Ceiling Fan is tested before it leaves the factory, resulting in an
extremely low rate of returns. However, due to shipping and installation procedures, oc-
casionally a fan will need a minor adjustment to run satisfactorily. If this should
happen, we recommend that you identify the problem and try the simple suggestions
listed below.
Turn o power at main circuit breaker before checking!
Fan will not start a) Check fuses and circuit breakers.
b) Check wire connections to fan.
c) Check wiring connection in lower canopy.
d) Check voltage at fan connection.
_______________________________________________________________________________________________________
___________
Fan too fast / slow a) Adjust the trim set screw in fan wall control if using optional wall control. If minimum setting
is too low the fan may shut o with voltage uctuations. Increase minimum.
b) Check voltage at fan connection.
c) Blades must be attached to motor to reduce the speed.
_______________________________________________________________________________________________________
___________
Fan makes noise a) Check motor case to make certain all visible screws are snug.
b) Check to make certain that all blade bracket screws are tight.
c) Check for labels or wire nuts that could be rubbing.
d) All ceiling fans may have a slight motor noise known as the “60 cycle hum” when used with
solid state innite speed controls. Especially on lower speeds. This hum will not aect the
fan performance.
e) Make certain upper canopy is at least 1/8” from ceiling
f) Allow a 30 days break-in period which normally eliminates any Residual noise other than a),
b), c), d) or e).
_______________________________________________________________________________________________________
___________
Fan wobbles a) Check that all blade brackets are screwed rmly to motor case.
b) Check distance from tip of blades to ceiling. If blades get bent during installation, you must
re-adjust them so that all blades travel on same plane. Gently bend up or down until all
distance are the same.
c) Make certain upper canopy is 1/8” from ceiling.
d) Make certain that hanging hooks are secured tightly to ceiling.
e) Run fan without blade, if motor does not wobble, then motor is not defective but the blades
maybe bent.
Symptom Corrective Action

E
N
G
L
I
S
H
Operating Instructions INDC60ODP
7
LIMITED WARRANTY
VES-ARTEX ONE-YEAR LIMITED WARRANTY ON ALL PARTS ONLY WITH ACCOMPANYING MAINTENANCE
SCHEDULE. VES-ARTEX MODELS COVERED IN THIS MANUAL, ARE WARRANTED BY VES-ARTEX (VES-ARTEX) TO THE
ORIGINAL USER, AGAINST DEFECTS IN WORKMANSHIP OR MATERIALS UNDER NORMAL USE FOR ONE YEAR ON ALL
PARTS AFTER DATE OF PURCHASE . ANY PART WHICH IS DETERMINED TO BE DEFECTIVE IN MATERIAL OR WORK-
MANSHIP AND RETURNED TO AN AUTHORIZED SERVICE LOCATION, AS VES-ARTEX DESIGNATES, SHIPPING COSTS
PREPAID, WILL BE, AS THE EXCLUSIVE REMEDY, REPAIRED OR REPLACED AT VES-ARTEX’S OPTION. FOR LIMITED
WARRANTY CLAIM PROCEDURES, SEE “PROMPT DISPOSITION” BELOW. THIS LIMITED WARRANTY GIVES
PURCHASERS SPECIFIC LEGAL RIGHTS WHICH VARY FROM JURISDICTION TO JURISDICTION.
LIMITATION OF LIABILITY. TO THE EXTENT ALLOWABLE UNDER APPLICABLE LAW, VES’S LIABILITY FOR
CONSEQUENTIAL AND INCIDENTAL DAMAGES IS EXPRESSLYDISCLAIMED. VES-ARTEX’S LIABILITY IN ALL EVENTS IS
LIMITED TO AND SHALL NOT EXCEED THE PURCHASE PRICE PAID.
WARRANTY DISCLAIMER. ADILIGENT EFFORT HAS BEEN MADE TO PROVIDE PRODUCT INFORMATION AND
ILLUSTRATE THE PRODUCTS IN THIS LITERATURE ACCURATELY; HOWEVER, SUCH INFORMATION AND
ILLUSTRATIONS ARE FOR THE SOLE PURPOSE OF IDENTIFICATION, AND DO NOT EXPRESS OR IMPLYAWARRANTY
THAT THE PRODUCTS ARE MERCHANTABLE, OR FIT FOR APARTICULAR PURPOSE, OR THAT THE PRODUCTS WILL
NECESSARILYCONFORM TO THE ILLUSTRATIONS OR DESCRIPTIONS. EXCEPT AS PROVIDED BELOW, NO WARRANTY
OR AFFIRMATION OF FACT, EXPRESSED OR IMPLIED, OTHER THAN AS STATED IN THE “LIMITED WARRANTY” ABOVE
IS MADE OR AUTHORIZED BY VES-ARTEX.
Technical Advice and Recommendations, Disclaimer. Notwithstanding any past practice or dealings or trade custom,
sales shall not include the furnishing of technical advice or assistance or system design. VES-Artex assumes no obligations or
liability on account of any unauthorized recommendations, opinions or advice as to the choice, installation or use of
products.
Product Suitability. Many jurisdictions have codes and regulations governing sales, construction, installation, and/or use of
products for certain purposes, which may vary from those in neighboring areas. While attempts are made to ascertain that
VES-Artex products comply with such codes, VES-Artex cannot guarantee compliance, and cannot be responsible for how the
product is installed or used. Before purchase and use of a product, review the product applications, and all applicable national
and local codes and regulations, and be certain that the product, installation, and use will comply with them.
Certain aspects of disclaimers are not applicable to consumer products; e.g., (a) some jurisdictions do not allow the
exclusion or limitation of incidental or consequential damages, so the above limitation or exclusion may not apply to you; (b) also,
some jurisdictions do not allow a limitation on how long an implied warranty lasts, consequently the above limitation may not apply
to you; and (c) by law, during the period of this Limited Warranty, any implied warranties of implied merchantability or tness for a
particular purpose applicable to consumer products purchased by consumers, may not be excluded or otherwise disclaimed.
Prompt Disposition. A good faith eort will be made for prompt correction or other adjustment with respect to any
product which proves to be defective within limited warranty. For any product believed to be defective within limited
warranty, first write or call dealer from whom the product was purchased. Dealer will give additional directions. If unable to resolve
satisfactorily, write to VES-Artex at address below, giving dealer’s name, address, date, and number of dealer’s
invoice, and describing the nature of the defect. Title and risk of loss pass to buyer on delivery to common carrier.
If product was damaged in transit to you, file claim with carrier.
Manufactured for VES-Artex, Chippewa Falls, WI 54729 USA

E
N
G
L
I
S
H
Operating Instructions INDC60ODP
8
Notes
________________________________________________________________________________________
________________________________________________________________________________________
________________________________________________________________________________________
________________________________________________________________________________________
________________________________________________________________________________________
________________________________________________________________________________________
________________________________________________________________________________________
________________________________________________________________________________________
________________________________________________________________________________________
________________________________________________________________________________________
________________________________________________________________________________________
________________________________________________________________________________________
________________________________________________________________________________________
________________________________________________________________________________________
________________________________________________________________________________________
________________________________________________________________________________________
________________________________________________________________________________________
________________________________________________________________________________________
________________________________________________________________________________________
________________________________________________________________________________________
________________________________________________________________________________________
________________________________________________________________________________________
________________________________________________________________________________________
________________________________________________________________________________________
________________________________________________________________________________________
________________________________________________________________________________________
________________________________________________________________________________________
________________________________________________________________________________________
________________________________________________________________________________________
This manual suits for next models
1
Table of contents
Other TURNTIDE Fan manuals
Popular Fan manuals by other brands

Matthews Fan Company
Matthews Fan Company PUPLO-DINAMICO manual

AirScape
AirScape 3200 Installation and operation manual

Dynergy
Dynergy MINIFAN BASE Series Installation and operating manual

Rosenberg
Rosenberg SupraBox COMFORT Series Operating instruction

Emerson
Emerson CF717BS01 owner's manual

Emerson
Emerson Builder CF700BS09 owner's manual