3.0 Installation
THIS SECTION FOR USE BY COMPETENT PERSONNEL ONLY
3.1 Safety Information
WARNING READ SAFETY INFORMATION BELOW BEFORE INSTALLATION
WARNING Hazardous voltages may be present on the terminals the
equipment must be installed by suitably qualified personnel and
mounted in an enclosure providing protection to at least IP20.
ISOLATION The power supply terminals and associated internal circuitry are
isolated from all other parts of the equipment in accordance
with BS EN61010-1 for connection to a Category II supply
(pollution degree 2).
Functional isolation (500v max) is provided between input and
output circuits, and between inputs and communications
(where fitted).
Any terminals or wiring connected to the input, output or
communications terminals which are accessible in normal
operation must ONLY be connected to signals complying with
the requirements for Safety extra low voltage (SELV) circuits.
WARNING If not installed in accordance with these instructions, protection
against electrical hazards may be impaired.
●Installation overvoltage category - 2 (as per BS EN61010-1)
●The Mains supply to the equipment must be protected by an external 1 Amp fuse and a
suitable switch or circuit breaker which should be near the equipment.
●The equipment contains no user serviceable parts.
3