Certifying authority: NEPSI(China)
Conformity standards: GB3836.1, GB3836.4, GB3836.20, GB12476.1
and GB12476.4
Ex marking: [Ex ia Ga]ⅡC , [Ex iaD]
Maximum voltage: Um=250V
Intrinsic safety parameters: (7, 8 terminals)
Uo=10.5V, Io=14mA , Po=37mW
ⅡC: Co=2.4μF , Lo=165mH
*ⅡB: Co=16.8μF , Lo=495mH
ⅡA: Co=75μF , Lo=1000mH
Note: *ⅡB parameters are also applicable for combustible dust
atmospheres.
(1) For circuits only containing distributed capacitance and distributed
inductance, e.g. cable, allow the values of Co and Lo in accordance with
the allowed values in the certification parameters;
(2) For circuit combined with IS circuit and cables, if the inductance or
capacitance of IS circuit are no greater than 1% of the respective
parameters, then the permissible maximum external output parameters
of capacitance and inductance in accordance with the allowed values in
the certification parameters;
(3) For circuit combined with inductance and capacitance, if both
parameters are greater than 1% of the output parameters (excluding
cables), then the permissible maximum external output parameters of
capacitance and inductance should be 50% of the allowed values in the
certification parameters.
When using the values of maximum external capacitance (Co) and
inductance (Lo), please attend the following requirements:
Application
Dimensions
118.9mm×106.0mm×12.5mm
Note: Bus-powered function is optional.
1 2 3
Safe-area
Hazardous-area
Number of channels: 1/2
Supply voltage: 20~35V DC
Current consumption: ≤40mA(at 24Vdc supply, output relay energized)
Safe-area relay output:
Response time: ≤10ms
Contact loading: 250V AC, 2A or 30V DC, 2A
Load type: resistive load
Hazardous-area input:
Signal: dry contact or NAMUR Proximity Detector
Open Circuit Voltage≈8V
Short Circuit Current≈8mA
Input and output characteristics (K1~K4 are separately set to ON, ON,
OFF, OFF state):
:
Note: 1) K2~K4 are separately set to ON, OFF, OFF.
2) Dy contact switch inputs need to connect according to the
way of Switch ( ).
Power supply protection: Power supply reverse protection
EMC: According to IEC - /
Dielectric strength:
Between non-IS part and IS part≥2500VAC
Between power supply part and output part≥500VAC
Insulation resistance:
Between non-IS part and IS part≥100MΩ
Between power supply part and output part≥100MΩ
Weight: Approx.100g
Suitable location: Mounting in safe area, and connected to the IS
apparatus in hazardous area up to zone 0 IIC and zone 20 IIIC.
Suitable field apparatus:
Dry contact or DIN19234 standard NAMUR proximity switch input field
devices(including the intrinsically safe type pressure switch,
temperature switches, liquid level switch).
Function of the DIP Switch
Ⅱ
61326 1(GB T 18268)
IN OUT
Intrinsic Safety Certification
Specification
Intrinsic Safety Explosion Protection System
Switch
( )Ⅱ
Proximity
switch
Power supply
Power bus
6
5
8 (-)
7 (+)
2(-)
1(+)
7
8
4
3
OUT
LFD
-+
680Ω
22kΩ
GS8512-EX.12
Input signal
Input>2.1mA
Input<1.2mA
Input breakage
Input short-circuits
Output relay LFD relay Sta.
OFF
ON
OFF
OFF
ON Yellow LED OFF
ON
OFF
Yellow LED ON
OFF
Red LED ON
Red LED ON
Function
ON
OFF
K1
Inverted Phase
Normal Phase
115.1mm
118.9mm
12.5mm
99mm
Summarize Ambient Conditions
Digital input, relay output isolated barrier, transfers digital signals (dry
contact or NAMUR proximity switch) from hazardous area to safe area.
The output can be provided to select phase reversal and to enable the
line fault detection. The product needs an independent power supply
and galvanic isolation among power supply, input and output.
(1)There should be no following substances in the air: flammable and
explosive substances; medium that could corrupt the coat of chrome,
nickel and silver. Moreover, please avoid using this product in violent
quiver,impact or strong electromagnetic interference environment.
(2) Operating temperature: -20℃~+60℃
(3) Storage temperature: -40℃~+80℃
(4) Relative humidity: 10%~90%
Special requirements have to be confirmed before using the intrinsically
safety explosion protection system(intrinsically circuit) which connected
by isolated barrier and intrinsically safe apparatus in field:
(1) The EX-proof level of intrinsically safe apparatus should meet the
requirements of operation conditions. The apparatus should pass the
explosion protection test and get the certificate by authorized explosion-
proof product certification bodies.
(2) The intrinsic safety parameters of isolated barrier and intrinsically
safe apparatus both are clear, and comply with GB/T 3836.15.
(3) If any parameters are unclear, the system has to be confirmed by
authorized explosion-proof product certification bodies.