DO NOT CHANGE THE POSITION OF THE MICRO SWITCHES (OFF by default)
Pairing with a radio smoke detector alarm
1. Power up the relay board (receiver).
2. Hold down the conguration push button on Relay Cat. No. 0 405 14 for 5 seconds. 3 beeps conrm that the action has
been taken into account and the orange LED ashes. Relay Cat. No. 0 405 14 sends a request to an existing group
(smoke detector alarms)
3. Press the test button on one of the group's smoke detector alarms. 1 long beep conrms completion of the action.
Relay Cat. No. 0 405 14 is now paired with the smoke detector alarm and automatically switches to installation
optimisation mode.
4. Move Relay Cat. No. 0 405 14 towards its planned location and check the quality of reception of the radio signal
(see "radio link quality check" table below). Sequences of 1 to 5 beeps a few seconds apart indicate the quality of the
radio link.
5. Mount Relay Cat. No. 0 405 14 at its chosen location.
6. Press the conguration push button on Relay Cat. No. 0 405 14. 4 beeps conrm that it has left installation optimisation
mode, and 4 more beeps conrm that it has left conguration mode. The system is now operational.
-
Cancelling the pairing of a smoke detector alarm:
Press for 10 seconds at stage 2 of the pairing procedure (see above). 4 long beeps conrm it has been cancelled.
-
Radio link quality check
When Relay Cat. No. 0 405 14 is in installation optimisation mode, it sounds 1 to 5 beeps a few seconds apart. Check the
quality of the radio link according to the number of beeps sounded by Relay Cat. No. 0 405 14.
1 2 3 4 5
- -
1 2 3 4
ON
OFF
-
Testing a single smoke detector alarm:
T
his function can be used at any time to check the quality of the radio link between a smoke detector alarm or carbon
monoxide detector and Cat. No. 0 405 14.
-
Press the test push button on the smoke detector alarm
-
The test signal is sent to Relay Cat. No. 0 405 14 for 5 minutes.
-
Testing all smoke detector alarms:
:
This function can be used to check the quality of the radio link between all detectors paired with Relay Cat. No. 0 405 14.
- Press (briey) the push button on Relay Cat. No. 0 405 14
- The test is activated on all paired smoke detector alarms. An audible signal indicates that transmission is in progress.
Note: this function is disabled in alarm mode.
-
Visual and acoustic identication
Visual signals Meaning Comment
Blue indicator light radio activity
-
Red indicator
light
steady alarm signal received
-
ashing
test signal received the number of ashes indicates the radio link quality of the last
signal received
Acoustic signals Meaning Comment
1 to 5-beep sequences / 1 minute test signal received number of beeps indicates the quality of the last signal received
1 to 5-beep sequences at intervals
of a few seconds
pairing in progress number of beeps indicates the quality of the signal received
Use
-
To stop the test signal, press the push button on Relay Cat. No. 0 405 14 again.
-
Alarm signaling
Relay Cat. No. 0 405 14 receive informations coming from paired smoke detector alarm in the same system.
When an alarm information is sent, the red indicator of the relay Cat. No. 0 405 14 lights xed.
Rearming is done automatically around 20 seconds after the alarm origin disappeared.
-+ + + +
Number of beeps
Reception quality
NOT RECOMMENDED
Risk of system failure
Recommended installation
TEST signal Comment
For 1 minute Acoustic beeps + ashing red indicator light The number of beeps and ashes indicate the
radio link quality of the last signal received.
Then for 4 minutes Flashing red indicator light