Uvar UDI 6Matic 706M002 User manual

UDI 5-3-2020
Maintenance Manual - 6Matic.
Subject to modifications
No liability accepted for errors or misprints
Automatic Screen Filter
6-Matic
Installation- Operation- and
Maintenance Manual
Serial Number

UDI 5-3-2020
Maintenance Manual - 6Matic.
Subject to modifications
No liability accepted for errors or misprints

1
UDI 5-3-2020
Maintenance Manual - 6Matic.
Subject to modifications
No liability accepted for errors or misprints
INDEX MANUAL 6MATIC
1 - Safety First ............................................................................................2
2 - Technical specification.........................................................................3
3 - Operating principle...............................................................................6
4 - Operating modes..................................................................................8
5 - Installation procedures.........................................................................9
5.1 - Assembly prior to installation...............................................................................................................9
5.2 - Filter installation...................................................................................................................................9
5.3 - Drain line installation............................................................................................................................9
5.4 - Electrical installation..........................................................................................................................10
5.5 - Auxiliary filter......................................................................................................................................12
6 - First commissioning and routine start-up........................................13
6.1 - Filter initial pre-sets............................................................................................................................13
6.2 - First commissioning...........................................................................................................................13
6.3 - Start-up..............................................................................................................................................13
7 - PLC controller (option).......................................................................14
7.1 - Automatic operation...........................................................................................................................14
7.2 - Continous flush..................................................................................................................................14
7.3 - Fault...................................................................................................................................................14
8 - Shut down & draining procedures.....................................................15
8.1 - Shut down procedure........................................................................................................................15
8.2 - Drainage procedure...........................................................................................................................15
9 - Preventive maintenance & inspections.............................................16
9.1 - Daily ..................................................................................................................................................16
9.2 - Bi-weekly............................................................................................................................................16
9.3 - Monthly .............................................................................................................................................17
9.4 - Quarterly.............................................................................................................................................17
9.5 - Intermediate maintenance cycle (minimal once a year).....................................................................17
9.6 - Full maintenance cycle (minimal every two years).............................................................................21
9.7 - Instructions for cleaning the screen...................................................................................................24
10 - Trouble shooting...............................................................................25
11.1 - Illustrated Parts Breakdown - General ............................................................................................26
11.2 - Illustrated Parts Breakdown - Self Cleaning Assembly...................................................................27
11.3 - Illustrated Parts Breakdown - Screen .............................................................................................27
11.4 - Part list.............................................................................................................................................28
12 - Hydraulic control diagram................................................................31
13 - Head loss / flow.................................................................................31
13.1 - Application guideline........................................................................................................................32
13.2 - The assessment and use of the application guideline.....................................................................33
13.1 - Head loss table *..............................................................................................................................34
13.2 - Head loss graph *.............................................................................................................................34

2UDI 5-3-2020
Maintenance Manual - 6Matic.
Subject to modifications
No liability accepted for errors or misprints
1 - SAFETY FIRST
UVAR believes that the safety of personnel working with and around our equipment is the most
important consideration. Please read all safety information below and any other relevant source
before attempting to perform any maintenance function. Comply with all approved and established
precautions for working with your type of equipment and/or environment. Authorized personnel
should perform all maintenance tasks.
Prior to performing a procedure, read it through to the end and understand it. If anything is not clear,
ask the appropriate authority. When performing a procedure, follow the steps in succession without
omission.
Availability of the latest version:
Manuals are subject to changes; The online version on our website www.uvar.nl is the most recent
version. When using a printed version, always check, through the QR-codes, for the latest on our
website or consult your local representative.

3
UDI 5-3-2020
Maintenance Manual - 6Matic.
Subject to modifications
No liability accepted for errors or misprints
2 - TECHNICAL SPECIFICATION
Screen Area & Maximum Flow Rates
* The maximum flow rate refers to screens over 200 microns/ less than 80 mesh and
good water (TSS < 10ppm).
** The flush flow rate is based on a 2 Bar pressure difference.
For a finer filtration degrees consult our representative.
Screen Grades
Electrical Data
motor
Specifications of the supplied motor might differ.
* Default motor. For other motors consult our representative.
Materials
Filter housing : Carbon Steel, electrostatic powder coating (Optional - Stainless Steel)
Filtration Screens : Sintered multi-layer screen. - Stainless Steel 316
Gaskets : SBR (Synthetic Rubber) (Optional - other materials)
Model
In-/Outlet diameter
Max. Flow Rate (*)
Flush Flow rate (**) Screen area
inch mm m/h m/h cm
706M002 2" 50 25 8 2500
706M003 3" 80 40 8 2500
706M034 4" 100 80 8 2500
706M004 4" 100 80 10 4000
706M006 6" 150 150 10 4000
706M086 6" 150 150 12 6000
706M008 8" 200 300 12 6000
706M128 8" 200 300 14 8000
706M012 12" 300 600 14 8000
Micron 10 25 30 40 50 80 100 130 200 300 400 800
Mesh
1500
600 500 400 300 200 150 120 80 50 40 20
Voltage
1 phase 110 VAC
1 phase 230 VAC*
3 phase 280/480 VAC
3 phase 346/600 VAC
Frequency 50 Hz 50 / 60 Hz 60 Hz 60 Hz
Current 3,8 A 2,2 / 2,0 A 1,2 A 1,0 A
Power 0,2 kW 0,25 kW 0,22 kW 0,25 kW

4UDI 5-3-2020
Maintenance Manual - 6Matic.
Subject to modifications
No liability accepted for errors or misprints
Specification of lagers sizes upon request
* The flush flow rate is based on 2 Bar pressure difference.
** The amount of flushing water is based on 2 Bar pressure difference.
Type
706M002
706M003
706M034
706M004
706M006
706M086
706M008
706M128
706M012
Connection - B
inch
2" 3" 4" 4" 6" 6" 8" 8" 12"
Diameter - D
inch
12" 12" 12" 12" 12" 16" 16" 16" 16"
Flange (ISO 7005
PN10) 50 80 100 100 150 150 200 200 300
Pitch mm 125 160 180 180 240 240 295 295 400
Bolt holes mm
4x Ø18
8x Ø18
8x Ø18
8x Ø18
8x Ø22
8x Ø22
8x Ø22
8x Ø22
12x Ø22
Weight kg 177 179 183 214 217 310 314 335 350
Length - L mm 1480 1480 1480 1660 1660 1925 1925 2225 2225
C-C flanges - A mm 430 430 430 600 600 780 780 990 990
Drain valve
inch
1½" 1½" 1½" 2" 2" 2" 2" 2" 2"
Screen area cm 2500 2500 2500 4000 4000 6000 6000 8000 8000
Max. pressure bar 10 10 10 10 10 10 10 10 10
Min. flush press. bar 2 2 2 2 2 2 2 2 2
Flush cap. min. *
m/h
8 8 8 10 10 12 12 14 14
Flushing water ** ltr 67 67 67 83 83 100 100 117 117
Motor 1 phase 230V/50Hz (other voltages on request)
Size E mm 540 540 540 540 540 575 575 575 575
Size H mm 650 650 650 650 650 780 780 780 780
Size L1 mm 2480 2480 2480 2780 2780 3280 3280 3830 3830

5
UDI 5-3-2020
Maintenance Manual - 6Matic.
Subject to modifications
No liability accepted for errors or misprints
Construction
The standard housing of the filter is made of carbon steel with a 120 micron protective coating of
extra durable polyester, applied electro-statically and oven cured on a zinc-phosphate layer, for
maximum anti-corrosion protection both internally and externally.
Access to the internal parts of the filter is through the removable bolted cover.
All immersed parts are made of either plastic materials or non-corrosive metals to ensure many years
of trouble free operation.
For special applications; contact our representative for more information.

6UDI 5-3-2020
Maintenance Manual - 6Matic.
Subject to modifications
No liability accepted for errors or misprints
3 - Operating principle
A. Filtration mode
The raw water enters the filter inlet and passes through the coarse screen (1), the first stage of filtration.
This prevents passage of any large particles, which may damage the filter internals.
The water then flows through the inside of the filter to the inner side of the fine screen (2). The water
passes through the screen from inside out to the filtered water chamber (8) and flows out through the
outlet.
As the water passes through the fine screen, the solids accumulate creating a cake of dirt on the inner
surface of the screen; as a result the pressure drop across the screen increases, and when it
reaches a preset level (0.5 bar / 7.5 psi) the filter controller activates the self cleaning process.
B. Flushing mode
When flushing command is activated, the controller activates the flushing valve (6) and the gear motor
(5).
The pressure differential between the pressure inside the filter and at the open valve to the atmosphere
on the flushing chamber (4) creates a backflow effect at the unique SA nozzles (3), removing
accumulated solids from the screen to the drain.
The unique design of the SA nozzles achieves an increased suction and significantly decreasing the
water consumption during flushing, due to accurate contact point between the unique SA nozzle and
the screen.
The spiral motion of the nozzles cleans all the area of the screen.
The collector assembly is driven by electrical motor which rotates in one direction. The electrical motor
is connected through the collector (7) to a reversing mechanism (9) which enables a continuous linear
movement (back and forth) of the collector assembly.

7
UDI 5-3-2020
Maintenance Manual - 6Matic.
Subject to modifications
No liability accepted for errors or misprints
The flushing cycle will be activated on pressure differential, time or manual:
1. When the predetermined differential pressure between inlet and outlet of the filter is reached (as
preset on the D.P. Switch, usually 0.5 bar / 0.75 psi).
2. Time interval between one flushing to the next one (prefixed at the controller – can be changed by
the operator) - guarantees that the time passed from the last self-cleaning process will not be longer
than the pre-set value determined by the operator.
3. Manually initiated flushing by pressing a button on the controller.
Testing the pressure differential switch
When functioning correctly, creating a pressure drop by means of closing the valve (75) on the outlet
side of the filter, will result in a flushing cycle of the filter. Please note that during the closing of the
testvalve a small amount of water will be vented to the atmosphere.
C. Continuous flushing
The fine sintered screen is flushed continuously, through the suction nozzles. The flushing valve and
the worm-gear motor are activated continuously.
The "Continuous Flushing" is selected manually by the operator; the selector is located on the electrical
board.

8UDI 5-3-2020
Maintenance Manual - 6Matic.
Subject to modifications
No liability accepted for errors or misprints
4 - OPERATING MODES
This efficient filter is automatic and easy to operate.
When the optional PLC controller is installed the operating modes are as follows:
1. Filtration - The normal function of the filter
2. Automatic Flushing –Flushing of the screen through the suction nozzles, activated by time or
DP. The gear-motor and the flushing valve are activated simultaneously by the controller.
The Yellow Flushing light (on the control board) is ON.
The timer activates the flushing cycle according to pre-set time in the controller.
3. Continuous Flushing - Back flushing of the screen through the suction nozzles. The gear
motor and the flushing valve are activated continuously and the Yellow Flushing light is ON.
This manual mode is selected by the operator.
4. Malfunction mode – This mode takes place when the electric motor's overload is tripped.
Then the RED Fault Light (on the electrical board) is turned ON.

9
UDI 5-3-2020
Maintenance Manual - 6Matic.
Subject to modifications
No liability accepted for errors or misprints
5 - Installation procedures
5.1 - Assembly prior to installation
The filter is normally supplied fully assembled.
Electrical connections will be done by authorized personnel only.
The filter may be installed in any position, although for ease of maintenance, horizontal installation is
recommended.
5.2 - Filter installation
1. For best results, the filter should be installed as near as possible to the system it is required to protect. However,
if low filter inlet pressure is a concern, either before or during flushing, the filter may need to be installed closer
to the pressure source.
2. Ensure that the upstream pipe size from the pressure source to the filter is equal to or greater than the filter’s
inlet size.
3. It is strongly recommended to install an isolation valve at the filter’s inlet, and a check valve, or an isolation
valve at the filter’s outlet.
4. An inlet isolation valve must be installed in situations where the pressure source cannot be shut down for
maintenance.
5. Inlet/outlet and by-pass valves must be installed in situations where a constant supply of water is required
downstream during filter servicing.
6. Ensure that the filter is mounted in the proper flow direction, as indicated by the arrows on the filter housing. As
a check, the inlet is closer to the cover end of the filter.
7. If a fixed drain pipe is installed on the auxillairy filter, use a funnel or other means so it will be visible if the valve
is opened or closed.
8. The mounting of the delivered 1”airvalve is strongly advised.
9. Ensure that sufficient space is provided around the filter for maintenance.
10. When the screen element is disassembled, reassembly as follows. Insert the screen element inside the filter
body. Open the service port cover (6) in order to get easy access to place the collector assembly in place. The
drive shaft (39) must be inserted into the shaft guide (19). Before doing so apply grease to the drive shaft.
11. When an acid-base injection is installed the injection location should be downstream from the filter.
Part numbers refer to the illustrated parts breakdown in chapter 11
5.3 - Drain line installation
A drain line should be attached to each flushing valve, as follows:
●The back pressure at the flush valve outlet should not exceed 0.3 bar (4.5 psi)
●Piping should be installed level or pitch down to avoid back-pressure.
●The open end of piping should be securely mounted to avoid vibrations during flushing cycle.

10 UDI 5-3-2020
Maintenance Manual - 6Matic.
Subject to modifications
No liability accepted for errors or misprints
5.4 - Electrical installation
Technical electrical specifications:
●Reduction motor, see chapter 2 (Technical Specification). The electralmotor needs to installed with a current
overload protection acc. to EN 60204-1.
●Dp-switch: SPST 25W max 0,5 A + max. 240 VAC/VDC.
●Solenoid(s): 24 VAC-D 50/60 Hz 2,2W
Filter control:
●Flush modes:
qAutomatic (triggered by pressure difference and by time)
qManual
Automatic flush mode
●The flushing of the filter will be initated by de DP-switch (∆P > 0.5 Bar)
●After approx. 10 seconds a flushing cycle needs to be started (Pre-Dwell time)
●If applicable, first close the mainvalve installed after the filter. The flushing cycle may start if the mainvalve is
fully closed. The time needed for the closure is depending on the type of valve installed.
●The flush cycle will be started when both the eletrical motor and the solenoid on the flushing valve are
activated. A flushing cycle needs to be at least 30 seconds. After this time the electrical motor and the solenoid
valve need to be decativated.
●If more than one filter is installed the pressure difference over all installed filters need to be monitored by means
of one DP-switch. The DP switch need to be installed into the combined in- and outlet line.
●If multiple filters are installed the flushing needs to be preformed one after another. Between the changeover of
the filters a dwell time of 5-10 seconds needs to be taken into account.
●In case an electric valve is installed on the auxilairy filter, we recommend to activate this electrical valve every
30 flushing cycles for approximatly 5-10 seconds.
The flushing of the auxilairy filter may never be done during a regular flushing cycle of the 6Matic filter.

11
UDI 5-3-2020
Maintenance Manual - 6Matic.
Subject to modifications
No liability accepted for errors or misprints
Manual flush mode
●For each installed filter there needs to be a possibility to manualy flush the filter.
●The manual flush cycle needs to be identical to the automatic flushing cycle.
General
●When the system, in which the filter is installed, is not operational, it may not start an automatic flushing cycle.
●Make sure that the filter is flushed based on operational uptime. The manual flush cycle needs to be identical to
the automatic flushing cycle. No matter how the flushing cycle was started the interval to the next cycle will
start to be measured again after each ending of a flushing sequence.
●Connect de DP-switch directly to the IO board of the PLC of computer (without routing through a relay).
Advise
●Generate an alarm if a flushing cycle is repeated directly after another multiple times (for instance 3 times).
●Make sure that the amount of flushing cycles per day are logged. It is recommended to distinguish the various
possiblies that can initiate a flushing cycle
●Make sure the following parameters are changable:
qPre-Dwell time (sec.)
qLength of flushing cycle (sec.)
qDwell time (sec.)
qTime interval for flushing cycle (hrs)
qAmount of filters installed
qMain valve installed (Yes/No)
qMain valve time delay (Sec.)
●Flush the filter before or after a duty cycle. (Clean start and clean stop)
●Use an UDI controller for standalone applications.

12 UDI 5-3-2020
Maintenance Manual - 6Matic.
Subject to modifications
No liability accepted for errors or misprints
5.5 - Auxiliary filter
For the reversing mechanism to run smoothly, a similar pressure on both sides is required. The
pressure is equalized by means of the pressure equalizing bypass. The filter in the bypass serves to
keep the reversing mechanism clean.
The filter can be fitted with a screen filter element or a disc filter element. The screen filter is standard
(24B).
Assembly seen from the rear of the 6Matic:
Position and view side auxiliary filter in dashed line.
24B 24A
Screen filter (standard) Disc filter
Screen filter:
If drainage is to be installed under the manual valve, use a funnel or other means so it will be visible
when the valve is left open.
Automatic flushing of the auxiliary filter:
It is possible to automate the flushing of the auxiliary
filter (24B), if required the maual valve needs to
exchanged by a 3/4”elecltrical valve. Our advise is to
activate this electrical valve after every 30 flushing cycles for
approximatly 5-10 seconds.
Important:
The flushing of the auxilairy filter may never be done during a
regular flushing cycle of the 6Matic filter.
Make sure the manual valve(s) for flushing
the auxiliary filters are easily accessible.
If needed change valve position and/or
combine the flushing lines.

13
UDI 5-3-2020
Maintenance Manual - 6Matic.
Subject to modifications
No liability accepted for errors or misprints
6 - FIRST COMMISSIONING AND ROUTINE START-UP
NOTE: The manual below is based on the optional PLC controller.
NOTE: The differential pressure switch and timers have been preset to the proper settings. Do not
adjust prior to start-up.
6.1 - Filter initial pre-sets
1. The differential pressure switch is set to 0.5 bar (7 psi) maximum, do not adjust.
2. It is recommended to set the flushing duration to 30 seconds.
3. Flushing interval (time between one flush to the next one) should be set according to water
conditions
6.2 - First commissioning
Check prior to to start-up the following and adjust when required.
1. Check that the line pressure will always be at least 2 bar (29 psi) at the filter inlet during the
flushing cycle.
2. Check that there are no restrictions upstream in the pipeline .
3. Check that the filter is mounted in the correct flow orientation, as indicated by the arrows on
the body.
4. Check that the flushing valve is mounted properly.
5. Check that the tubing connections are installed correctly.
6. Check that power is available to the electrical board and that the main switch on the electrical board
is in the "OFF" position.
7. Check that the flushing valve drain lines are installed.
8. Check that the upstream and downstream isolation valves are closed.
9. Check that adequate space is available around the filter for maintenance.
6.3 - Start-up
1. Slowly open the inlet valve to the filter allowing the filter to pressurize.
2. Check for any external leakage and eliminate if needed .
3. Slowly open the outlet valve of the filter (if installed).
4. Turn the main switch ON.
5. Verify that all power supply and all machine elements are connected.
6. Turn the operation mode switch to "AUTO" position.
7. Initiate a manual flushing cycle, the filter will perform its first flush and stops.
8. During filter flushing:
1. Observe the movement of the screw through the indicating sight on the gear motor
protection cover.
2. Ensure that the filter inlet pressure is higher than 2 bar (29 psi).
3. The flushing chamber pressure should be 1.8 - 2.5 bar (26 - 36 psi) below inlet pressure.
NOTE: At any given time pressing the manual flushing push button will cause one flushing cycle. The
duration of the flushing cycle can be adjusted via the controller, it is recommended not to shorten the
flushing time below 30 seconds, for it then will not clean the whole screen area.

14 UDI 5-3-2020
Maintenance Manual - 6Matic.
Subject to modifications
No liability accepted for errors or misprints
7 - PLC CONTROLLER (OPTION)
When operational, the filter will be in one of the following modes.
7.1 - Automatic operation
The filter will perform a flushing cycle after time interval that is preset in the flushing controller or the filter will perform
a flushing cycle due to the pressure differential switch command (D.P.), whichever is first.
If the pressure differential remains on, the filter will continue its flushing, read chapter 10 "Trouble shooting".
7.2 - Continous flush
In this mode the filter will flush continuously.
7.3 - Fault
The fault condition (RED light on) is generated in case of a motor fault.

15
UDI 5-3-2020
Maintenance Manual - 6Matic.
Subject to modifications
No liability accepted for errors or misprints
8 - SHUT DOWN & DRAINING PROCEDURES
8.1 - Shut down procedure
NOTE: Before shutting down or draining the filter, perform two cycles of manual flush, verify that head
loss on the filter does not exceed 0.1 - 0.2 bar (1.5 - 3.0 psi).
1. Close the isolating valve on the outlet of the filter if equipped.
2. Initiate a manual flushing.
3. Switch off the pump and close the isolating valve on the inlet of the filter
4. Initiate an additional manual flushing cycle to relieve the pressure in the filter, or open the manual
drain valve (22).
8.2 - Drainage procedure
Prior to accessing the filter internals, it is necessary to drain the filter. Note that uncontrolled draining
of the filter may result in excessive water spillage in the area around the filter.
In order to prevent any damage to surrounding equipment or property it is advised to install a drain
connection to the manual drain valve (22) installed on the filter.
To empty the filter:
1. Perform the shutdown procedure as described in chapter 8.1
2. Reduce pressure to ‘0’.
3. The air valve will let air into the filter.
4. Open the manual drain valve (22) on the drain line to drain the filter.

16 UDI 5-3-2020
Maintenance Manual - 6Matic.
Subject to modifications
No liability accepted for errors or misprints
9 - PREVENTIVE MAINTENANCE & INSPECTIONS
General notes:
1. Before filter shut down or draining, perform two cycles of manual flushing, verify that head
loss on the filter does not exceed 0.1 - 0.2 bar (1.5 - 3.0 psi) (see chapter 8).
2. (__) refers to the breakdown drawings of chapter 11.
3. On moving mechanical parts, which are directly in contact with water, apply “Ocean W7”or
equivalent grease (unless otherwise noted).
4. Before installing seals and O-rings, apply silicone grease ‘OKS 1110/0’ or equivalent grease
(unless otherwise noted).
5. Before installing bolts back, apply ‘Molykote G-n Plus Paste’ or equivalent.
6. Do not tighten / untighten bolt of the covers while the filter is pressurized.
Following is a schedule of preventive maintenance and inspections based on average filtration duty,
and should be used as a guideline only. For best results, a maintenance schedule should be compiled
based on gained experience from using the filter. A maintenance kit (which consists of paint, Ocean
W7 grease and OKS 1110/0 Silicon grease) is standard delivered with the filter.
9.1 - Daily
Repair any damage to the protective coating of the filter without delay. Prior to application of protective
paint, thoroughly clean the damaged spot with wire brush.
9.2 - Bi-weekly
Every two weeks clean the auxiliary filter (24A/B).
Manual filter with disc element (24A) (Filter points to the left and has no
valve)
Perform the following actions when the system is without pressure.
1. Unscrew the filter cap and remove the filter element.
2. Turn the black cap to loosen the discs.
3. Thoroughly rinse the discs under the tap .
4. Tighten the discs, assemble the filter element with
the purple O-ring on top and tighten the filter cap.
Manual filter with screen filter element (24B) (filter with ball valve points to the right.)
Perform the following actions when the system is pressurized and
the 6Matic is not flushing. Flushing the auxiliary filter is not allowed during the
flushingcycle of the 6Matic!
1. If necessary place a bucket under the valve.
2. Open the valve and close the valve after 5 - 10 seconds.
3. If needed switch off the pump and thoroughly rinse the auxilairy filter
screen element
Ball valve should always be closed, unless cleaning auxiliary filter.

17
UDI 5-3-2020
Maintenance Manual - 6Matic.
Subject to modifications
No liability accepted for errors or misprints
9.3 - Monthly
On units equipped with by-pass valve, the by-pass valve should be engaged at least once a month. This will clean
the valve seat of any accumulated dirt, as well as ensuring proper by-pass operation.
9.4 - Quarterly
Visual inspection and lubrication of the drive shaft (39):
1. Switch off the filter and drain the water (see chapter 8)
2. Remove the service cover (6) and start the motor manually; If the dirt collector unit (9) is fully seated in the
filter (the drive shaft (39) is then fully visible), interrupt the power supply of the motor with the main switch
3. Apply a thin layer of Ocean 7W or equivalent grease to the drive shaft (39) .
4. Place the service cover (6) including the rubber cover (5).
5. Re-commision the filter (see chapter 6). If multiple filters are installed, these steps must be performed
separately on all filters.
Filter with screen filter element (24B) (Filter with Electrical valve points to the right.)
Perform the following actions when the system is without pressure.
1. Unscrew the filter cap and remove the filter element.
2. Thoroughly rinse the element under the tap .
3. Assemble the filter element with and tighten the filter cap.

18 UDI 5-3-2020
Maintenance Manual - 6Matic.
Subject to modifications
No liability accepted for errors or misprints
9.5 - Intermediate maintenance cycle (minimal once a year)
1. Replace the parts listed in the revision table.
Refer to chapter 9.1, 9.2, 9.3 and 9.4 for the complete maintenance scope.
A -Removing the fine screen and the drive unit for inspection and replacement of above mentioned
parts:
1. Switch off the filter and drain the water (see chapter 8)
2. Disconnect the connector of the stainless steel pipe (65) near the front cover (3) by loosening
knee (66) and disconnect the PE adapter (69), remove the stainless steel pipe.
3. Disconnect the PE tube (12) by removing the clamp nut (70), clamp ring (71) and seal (72).
4. Open the front cover (3) by loosening the bolts.
5. Carefully pull out the complete screen assembly (Item 7, 8, 9 &13) using the two handles inside
the coarse screen.
6. Place the screen assembly on a clean working surface in order not to damage the screen.
7. Remove large particles from the coarse screen (7) and clean if necessary.
8. Check the fine screen (8) for any markings of the suction nozzle (9/2) and check the nozzles on
the collector unit (9) for wear.
9. Clean the complete screen by means of a high-pressure cleaner.
10. Remove the screen seals (8/4)
11. Remove the bolts (35) from the shaft guide (19)
12. Remove the bolts (8/12) to dismount the guide base (8/7)
13. Remove the bolts from the coarse screen to disconnect the coarse screen (7) from the fine
screen (8).
14. Dismount the reverse housing assembly (13) by means of the following steps:
●Remove nut (13/6) and remove bolt (13/5) from the housing
●Remove bolts (13/3) and remove the housing of the reversing mechanism (13/1)
●Remove the bolts from the housing (14/5) and remove the housing (14/5) from
collector unit (9/1)
●Remove the O-ring/Stopper (14/2) and remove the cover of the drive pawl (14/3)
●Dismount the drive pawl (14/4) from the housing (14/5) and remove the drive screw
(14/1)
Partcode set:
4S7863R02300
Partcode set:
4S7863R08301
# Description
Model: 706M002 /
706M003 / 706M034 /
706M004 / 706M006
Model: 706M086 /
706M008 / 706M128 /
706M012
8/4 Fine Screen Seal 4S7851B9160 4S71500804
8/6 Guide Stopper 4S71500302 4S71500302
8/9 Seal 4S7863R020089 4S7863R080089
8/10
Wiper 4S7863R020810 4S7863R080810
10 Shaft seals (set) 4S71510381 4S71510381
11 Seal 4S71510380 4S71510380
13/2
Seal 4S7851B9163 4S7851B9163
14/6
Seal 4S7863R020146 4S7863R020146
72 Seal 4S70600072 4S70600072
This manual suits for next models
8
Table of contents
Popular Water Filtration System manuals by other brands

AMI
AMI Sola Pure Instruction handbook

BWT
BWT 812916 quick start guide

Oasis
Oasis QE Series Installation and operation manual

Everpure
Everpure ROM III Installation and operation guide

Oase
Oase ProfiClear Premium Compact-M EGC operating instructions

Brita
Brita PURITY 1200 Clean Extra Cartridge Replacement Instructions