Voltage signal values
Fan speed Voltage signal (VDC)
0 0.20...1.25 VDC
1 1.75...2.25 VDC
2 2.75...3.25 VDC
3 3.75...4.25 VDC
4 4.75...5.25 VDC
5 5.75...6.25 VDC
6 6.75...7.25 VDC
7 7.75...8.25 VDC
8 8.75...10.00 VDC
Controlling ventilation
with voltage signal
• The fan power of Vallox 280 SE can be controlled
with voltage signals coming from remote monitoring
control.
• The signal can have speeds 0 to 8, but not higher
than the maximum fan speed if carbon dioxide or
humidity adjustment is active. See section 3.25 in the
Operating instructions for control panel.
• A signal changes the basic fan speed.
• A signal does not lock the fan speed.This means that
the fan speed can be changed within the range set
at the control panel. Carbon dioxide and humidity
adjustment also work within the range set.
Controlling ventilation with remote
monitoring control system (option)
• Vallox 280 SE can be connected to the remote
monitoring control system with an optional LON and
KNX converter.
• When Vallox 280 SE is connected to the remote
monitoring control system, you have to make sure that
they are compatible.
• You can control the same functions via the remote
monitoring control system as at the control panel.
• The remote monitoring control system operates
in parallel with the control panel and the carbon
dioxide and humidity sensors.
Post-heating
For most of the year, heat recovered from the air extract-
ed is enough to heat the cold air coming from the out-
side to a suitable temperature. If the heat of extract air
is not enough, the air coming from the outside can be
heated with the post-heating unit in the ventilation unit.
The post-heating radiator can be electric (Vallox 280
SE electric/electric) or water-circulating (Vallox 280 SE
electric/VKL). In both cases, you can switch heating on
at the control panel. See section 2.1 in the Operating in-
structions for control panel.
When post-heating is on, the unit automatically adjusts
supply air temperature in accordance with the temper-
ature set.
Supply air constant temperature control
• Vallox 280 SE has a relative post-heating adjustment.
This means that when the temperature set for post-
heating goes down, the on-time of post-heating goes
automatically down in two-minute phases. When the
temperature set exceeds supply air temperature by
more than 2.5 °C, the post-heating radiator is on all
the time.
• The heating radiator heats when the ( ) sign is
displayed.
• Temperature adjustment is only active when the post-
heating function has been switched on.
Supply air cascade adjustment
• It is possible to change supply air temperature
adjustment into cascade adjustment. In this case,
the post-heating radiator directs the temperature of
air coming in based on the temperature of extract
air. See section 3.18 in the Operating instructions for
control panel.
• The programme tries to keep the temperature of
supply air at the value defined by the difference
between extract air and the setpoint as follows:
if extract air is warmer than the value set, the
temperature of supply air is lower than the setpoint
by the difference. If extract air is cooler, supply air is
warmer by the difference. If room temperature (the
temperature of extract air) is 25 °C and the value set
is 24 °C, the aim is to blow 23 °C air into the ventilation
zone. If temperature in the ventilation zone is 24 °C
and the setpoint is 25 °C, the aim is to blow 26 °C air
into the ventilation zone.
• In any case, the aim is to keep the temperature of air
blown into the ventilation zone between 10 and 30 °C.
• You can choose cascade adjustment at the control
panel, and it is active when post-heating has been
switched on.
• The heating radiator heats when the ( ) sign is
displayed.
Heat recovery bypass function
• The bypass function tries to get as cool supply air as
possible to the ventilation zone by comparing the
measurement data of the outdoor air sensor and the
extract air sensor.
• The heat recovery cell is bypassed when the post-
heating function is off and outdoor air temperature
is below the operating temperature set for the heat
recovery cell by two degrees and extract air is warmer
than outdoor air.
• The operating temperature of heat recovery bypass
can be changed within the range of 0...25 °C. See
section 3.15 in the Operating instructions for control
panel.
Post-heating indicator light
8
Vallox
280SE GENERAL OPERATING INSTRUCTIONS
OPERATING INSTRUCTIONS