INSTALLATION
- Account for over pressure conditions, according with the local laws or standards.
- Steam traps must not be used with other purpose than the one they were built for (e.g. climbing aids or as
connecting points for lifting gear).
- For the problems that cannot be solve with the help of this instructions, please contact the supplier or the
manufacturer.
Installation area requirements:
•The installation area should have easy access and provide enough space for maintenance and removing
operations.
•In order to allow installation and maintenance work without emptying the system, stop valves should be installed
upstream and downstream of the steam trap.
•The installation area should have the necessary firing system to prevent damage of the equipment due to over
temperature/pressure cause by fire.
•If the system cannot be stopped for maintenance it is recommended that isolating valves are installed
upstream and downstream of the steam trap together with a by-pass manual regulating valve. The
process can be then controlled manually during the steam trap maintenance. The by-pass must be kept
close during the normal operation.
Procedure:
•Prior to install check that the product is suitable for the intended application: materials and
pressure/temperature ratings.
•Before installing remove plastic covers placed on flanges or connection ends. The equipment has an arrow or
Inlet/Outlet designations. Be sure that it will be installed on the appropriate direction.
•Take care with jointing material to ensure that none may be permitted to block or enter the trap.
•In case of using Teflon tape (for screwed connections), avoid rolling it till the edge, because it can get cut and
migrate to the trap interior, blocking or causing a defective sealing.
•Install the steam trap in the point of the system, where the condensate tends to collect.
•An ADCA pipeline strainer should be installed upstream of the trap to protect from dirt which could damage the
steam trap or cause mal-functioning. The strainer must be installed with the sieve sideways, if the medium is
steam, to prevent the collection of condensate.
•External stresses that may be induced by the system due to pipe expansion, etc, can affect this product. The
necessary precautions are recommended during the systems design and equipment assembly.
•The steam trap pipework should be properly supported and free from strain and it should not be subjected to
undue surges of pressure. The start-up condition should be considered.