2
*Setting internal parameters.
Next to the adjustment of the setpoint, some internal settings are possible like differential, sensor-
offset, setpoint range and the defrost function.
By pushing the DOWN key for more than 10 seconds, you enter the 'internal programming menu'. In
the left display the upper and lower segments are blinking. Withthe UP and DOWN keys the required
parameter can be selected (see table for the parameters).
If the required parameter is selected, the value can be read-out by pushing the SET key. Pushing the
UP or DOWN keys allows you to change the value of this parameter.
If no key is pushed for 20 seconds, the ALFA(NET) 35 DP changes to it's normal operation mode.
*Adjustment sensor.
Thesensor can be adjusted byusing the ‘Sensor Offset’ (parameter 04). Indicates the ALFA(NET) 35
DP e.g. 2C too much, the Sensor Offset has to be decreased by 2C.
*Error messages.
In the display of the ALFA(NET) 35 DP the following error messages can appear:
Er - Sensor broken. Solution:
- Check if the sensor is connected correctly.
- Check the sensor (1000at 25C).
- Replace the sensor.
EE - Settings are lost. Solution:
- Reprogram the settings.
* Technical details.
Model : ALFA(NET) 35 DP Cool/Defrost Thermostat
Range : -10/+40C, readout per 0,1C
Supply : 230 Vac (or 24Vdc or 12Vdc)
Relay : SPDT 250V/16A(C-NO), 8A(C-NC) (cos phi=1)
Control : by pushbuttons on the front.
Communication: RS 485 Network (2xtwisted pair shielded) only at ALFANET model.
Front : Polycarbonate IP65
Sensor : SM 811/2m (1000at 25C)
Sizes : 35 x 77 x 71,5mm (hwd)
Panel hole : 28 x 70mm (hw)
- Provided with memory protection during power failure.
- Connection with screw terminals on the backside.
- Equipped with self test function and sensor failure detection.
- Special versions are available upon request.