  9. VDH ALFA(NET) 51 User manual

VDH ALFA(NET) 51 User manual

1
User manual
ALFA(NET) 51
Rail-Thermostat.
VDH doc. 032797 Version: v1.2 Date: 20-02-2007
Software: ALFANET51 File: Do032797.WP8 Range: -50/+50,0C
*Installation.
On the connection diagram of the ALFA(NET) 51 is shown how the sensors, power supply and relays are
to be connected. After connecting the ALFA(NET) 51 to the power supply, a self test function is started.
As this test is finished, the measured temperature appears in the display. Normally this is the temperature
of sensor-1, unless sensor-2 is active as control sensor (P05=1) in that case the average temperature of
both sensors is displayed and used for control. The ALFANET 51 is by use of the ALFANET PC-
INTERFACE controllable on the PC.
*Control.
The ALFA(NET) 51 thermostat can be controlled by four pushbuttons on the front. These keys are:
SET - view / change the setpoint.
UP - increase the setpoint.
DOWN - decrease the setpoint.
MODE - relay status key.
*Viewing setpoint.
By pushing the SET key the setpoint appears in the display. The decimal point of the last display starts
blinking. A few seconds after releasing the SET key the setpoint disappears and the measured
temperature is shown again in the display.
*Changing setpoint.
Push the SET key and the setpoint appears in the display. Release the SET key. Now push the SET key
again together with the UP or DOWN keys to change the setpoint. A few seconds after releasing the keys
the measured temperature shows again in the display.
*Viewing the individual sensors.
By pressing the UP and DOWN key together, the individual sensors can be shown in the display. After
releasing the keys, the measured temperature of sensor-1 can be shown by pushing the UP key or the
measured temperature of sensor-2 can be shown bypushing the DOWN key. A few seconds after
releasing the keys the (average) temperature shows again in the display.
*Status of the Relays.
By pushing the MODE key the display shows the status of the relays. Each display segment shows the
status of the relay output, showing 0=off and 1=on. The code 110 means relay 1 and 2 are on and relay 3
is off.
2
*Setting internal parameters.
Next to the adjustment of the setpoint, internal settings can be made like differential, sensor offset,
setpoint range and the functions of the thermostat.
Push the DOWN key for more than 10 seconds, to enter the 'Internal Programming Menu'. In the left
display the upper- and lower-segment are blinking. With the UP and DOWN keys the required parameter
can be selected (see the parameter table).
If the required parameter is selected, the value can be read-out by pushing the SET key. Pushing the UP
or DOWN key to change the value of this parameter.
If after 20 seconds no key is pushed, the ALFA(NET) 51 changes to the normal operation mode.
*Adjustment sensors.
Sensor-1 can be adjusted by using the Sensor Offset parameter 06 and Sensor-2 can be adjusted by
using the Sensor Offset parameter 07. Indicates a Sensor e.g. 2C to much, the according Sensor Offset
has to be decreased by 2C.
*Error messages.
In the display of the ALFA(NET) 51 the following error messages can appear:
LO - Minimum alarm. Solution E1,E2:
HI - Maximum alarm. - Check if the sensor is connected correctly.
E1 - Sensor-1 failure. - Check sensor (1000at 25C).
E2 - Sensor-2 failure. - Replace sensor.
EEE - Settings are lost. Solution EEE:
- Reprogram the settings.
-L- - In case of sensor short-circuit the display alternates between error-code E..
and -L-, as indication for a short-circuit sensor.
-H- - In case of open-circuit sensor the display alternates between error-code E..
and -H-, as indication for a open circuit sensor.
Reset Alarm. When a error-messages appears it can be resetted by pushing theSET key. The
function of this key depends on parameter P37.
* Technical data.
Type : ALFA(NET) 51 rail thermostat
Range : -50/+50,0C, above -10C display per 0,1C
Supply : 12Vac 50/60Hz (-5/+10%)
Display : 3-digit 7-segment display
Relays : Ry1= SPST(NO)250V/8A (cos =1) of 250V/5A (cos =0.4)
Ry2= SPST(NO)250V/8A (cos =1) of 250V/5A (cos =0.4)
Ry3= SPDT(NO/NC)250V/8A (cos =1) of 250V/5A (cos =0.4)
Relays have one common (C).
Control : By push buttons on front.
Front : Polycarbonate IP65
Sensors : 2x SM 811/2m (PTC 1000/25C).
Communication : RS485-Network (2x twisted pair shielded cable min. 0,75mm2)
Dimensions : 90 x 71 x 58mm (HWD)
Panel cut out : 46 x 71mm (HW) for front mounting
Accuracy : ± 0,5% of the range.
- Provided with memory protection during power failure.
- Connections with screw terminals on the back side.
- Equipped with sensor failure detection.
- Special versions are on request available.
3
*Parameters ALFA(NET) 51
Para-
Meter Description Parameter Range Standard
value
01
02
03
Function Relay 1
Function Relay 2
Function Relay 3
1 = Cool
2 = Heat
3 = Alarm
1 = Cool
2 = Heat
3 = Alarm
1 = Cool
2 = Heat
3 = Alarm
1
2
3
05
06
07
Function sensor-2
Offset temperature sensor-1
Offset temperature sensor-2
0 = Not
1 = Control
2 = Alarm
-15.0..+15.0C
-15.0..+15.0C
0
0.0
0.0
10
11
12
13
14
15
16
17
18
19
Switch on relay 2 by
Switch on relay 3 by
Switch on delay relay 2
Switch on delay relay 3
Switching differential relay 1
Setpoint offset relay 1
Switching differential relay 2
Setpoint offset relay 2
Switching differential relay 3
Setpoint offset relay 3
0 = Temperature
1 = Time
0 = Temperature
1 = Time
0.. 99 Minutes
0..99 Minutes
0.1..15.0 C
-15..+15 C
0.1..15.0 C
-15..+15 C
0.1..15.0 C
-15..+15 C
0
0
15
15
0.5
0.0
0.5
0.0
0.5
0.0
20
21
22
23
24
Switch on delay cooling
Switch off delay cooling
Parameter 20/21 in Sec. or Min.
Minimum on-time cooling
Minimum off-time cooling
0..99
0..99
0 = Seconds
1 = Minutes
0..99 Minutes
0..99 Minutes
0
0
0
0
0
25
26
27
Minimum setpoint
Maximum setpoint
Read-out above -10C per 1C
-50.0..+50.0C
-50.0..+50.0C
0 = No
1 = Yes
-50
+50
0
30
31
32
33
34
35
36
37
Alarm type (to setpoint)
Minimum alarm setpoint
Maximum alarm setpoint
Time delay minimum alarm
Time delay maximum alarm
Relay function alarm relay
Reset alarm relay after recovering alarm
Reset alarm relay after manual reset
0 = None
1 = Absolute
2 = Relative
-50.0..+50.0C
-50.0..+50.0C
0..99 Minutes
0..99 Minutes
0 = Watch
1 = Control
0 = No
1 = Yes
0 = No
1 = Yes
1
-50
+50
0
0
0
0
0
0
40
41 Start up delay after power failure
Forced relay function at sensor failure 0..99 Minutes
0 = None
1 = Cool
2 = Heat
0
0
90
95
96
97
98
99
Network number
Software version
Production year
Production week
Serial number (x1000)
Serial number (units)
1..250
0..255
00..99
1..52
0..255
0..999
1
0
0
1
0
0
4
*Dimensions. *Connections.
*Address.
VDH Products BV Tel: +31 (0)50 30 28 900
Produktieweg 1 Fax: +31 (0)50 30 28 980
9301 ZS Roden Email: info@vdhproducts.nl
The Netherlands Internet: www.vdhproducts.nl

Other VDH Thermostat manuals

VDH MC 785-DF KLIMA User manual

VDH

VDH MC 785-DF KLIMA User manual

VDH Alfanet 95 User manual

VDH

VDH Alfanet 95 User manual

VDH ALFANET51 RTDN User manual

VDH

VDH ALFANET51 RTDN User manual

VDH ALFA 25 DP User manual

VDH

VDH ALFA 25 DP User manual

VDH ALFA(NET) 52 User manual

VDH

VDH ALFA(NET) 52 User manual

VDH PROBA 5 Compact User manual

VDH

VDH PROBA 5 Compact User manual

VDH ALFA 52-VS User manual

VDH

VDH ALFA 52-VS User manual

VDH ALFA 75-MTT User manual

VDH

VDH ALFA 75-MTT User manual

VDH PROBA 5 Compact User manual

VDH

VDH PROBA 5 Compact User manual

VDH ALFA 21 User manual

VDH

VDH ALFA 21 User manual

VDH ALFA 30 User manual

VDH

VDH ALFA 30 User manual

VDH ALFA 31 User manual

VDH

VDH ALFA 31 User manual

VDH ALFANET 71 User manual

VDH

VDH ALFANET 71 User manual

VDH ALFANET 53 User manual

VDH

VDH ALFANET 53 User manual

VDH ALFANET 55 RTDF User manual

VDH

VDH ALFANET 55 RTDF User manual

VDH ALFANET 95 User manual

VDH

VDH ALFANET 95 User manual

VDH ALFANET 71 User manual

VDH

VDH ALFANET 71 User manual

VDH ALFA 71 PI User manual

VDH

VDH ALFA 71 PI User manual

VDH ALFANET 85 User manual

VDH

VDH ALFANET 85 User manual

VDH ALFA-45 User manual

VDH

VDH ALFA-45 User manual

VDH ALFA 15 User manual

VDH

VDH ALFA 15 User manual

VDH ALFANET 72 User manual

VDH

VDH ALFANET 72 User manual

VDH ALFA 71 User manual

VDH

VDH ALFA 71 User manual

VDH ALFA 11 User manual

VDH

VDH ALFA 11 User manual

Popular Thermostat manuals by other brands

Watts Milux Star Installer's and User's Parameters

Watts

Watts Milux Star Installer's and User's Parameters

Lux Products LuxPro SMART TEMP P521Ua Installation and operating instructions

Lux Products

Lux Products LuxPro SMART TEMP P521Ua Installation and operating instructions

Honeywell T10 Pro Smart user guide

Honeywell

Honeywell T10 Pro Smart user guide

JUMO heatTHERM-AT operating instructions

JUMO

JUMO heatTHERM-AT operating instructions

ritetemp 8085 Operation guide

ritetemp

ritetemp 8085 Operation guide

SOMFY Telis 6 Chronis RTS user manual

SOMFY

SOMFY Telis 6 Chronis RTS user manual

DELTA DORE TYBOX PAC installation guide

DELTA DORE

DELTA DORE TYBOX PAC installation guide

Sinope TH1400NP installation guide

Sinope

Sinope TH1400NP installation guide

RCS TZ16 Installation and operation manual

RCS

RCS TZ16 Installation and operation manual

Contemporary Controls BAST-221C user manual

Contemporary Controls

Contemporary Controls BAST-221C user manual

RG2i LoRaWAN Vicki installation guide

RG2i

RG2i LoRaWAN Vicki installation guide

Tekmar tekmarNet 554 Quick setup guide

Tekmar

Tekmar tekmarNet 554 Quick setup guide

American Standard ASYSTAT300C owner's guide

American Standard

American Standard ASYSTAT300C owner's guide

Siemens RDD100.1RF operating instructions

Siemens

Siemens RDD100.1RF operating instructions

Tekmar tekmarNet 557 Quick setup guide

Tekmar

Tekmar tekmarNet 557 Quick setup guide

Aura JGSTATW2W instruction manual

Aura

Aura JGSTATW2W instruction manual

Rehau PD1 instructions

Rehau

Rehau PD1 instructions

Etaluma Lumascope 500 Startup guide

Etaluma

Etaluma Lumascope 500 Startup guide

manuals.online logo
manuals.online logoBrands
  • About & Mission
  • Contact us
  • Privacy Policy
  • Terms and Conditions

Copyright 2025 Manuals.Online. All Rights Reserved.