manuals.online logo
Brands
  1. Home
  2. •
  3. Brands
  4. •
  5. VDH
  6. •
  7. Thermostat
  8. •
  9. VDH ALFA 71 S PI User manual

VDH ALFA 71 S PI User manual

Other VDH Thermostat manuals

VDH ALFA 25 DP User manual

VDH

VDH ALFA 25 DP User manual

VDH ALFA 31 DP User manual

VDH

VDH ALFA 31 DP User manual

VDH ALFA 30 User manual

VDH

VDH ALFA 30 User manual

VDH ALFA 31 User manual

VDH

VDH ALFA 31 User manual

VDH ALFA 75-MTT User manual

VDH

VDH ALFA 75-MTT User manual

VDH ALFA(NET) 33 User manual

VDH

VDH ALFA(NET) 33 User manual

VDH ALFANET 71 User manual

VDH

VDH ALFANET 71 User manual

VDH MC 885-SDHL User manual

VDH

VDH MC 885-SDHL User manual

VDH ALFANET 85 User manual

VDH

VDH ALFANET 85 User manual

VDH ALFA 71 PI User manual

VDH

VDH ALFA 71 PI User manual

VDH ALFA 59 User manual

VDH

VDH ALFA 59 User manual

VDH ALFANET51 RTDN User manual

VDH

VDH ALFANET51 RTDN User manual

VDH ALFA 71 MODulation User manual

VDH

VDH ALFA 71 MODulation User manual

VDH ALFA(NET) 71 PI User manual

VDH

VDH ALFA(NET) 71 PI User manual

VDH ALFA 71 User manual

VDH

VDH ALFA 71 User manual

VDH ALFA 71 MOD User manual

VDH

VDH ALFA 71 MOD User manual

VDH ALFANET 72 User manual

VDH

VDH ALFANET 72 User manual

VDH ALFA 75 RTDF User manual

VDH

VDH ALFA 75 RTDF User manual

VDH ALFA 52-VS User manual

VDH

VDH ALFA 52-VS User manual

VDH ALFA 51 PI User manual

VDH

VDH ALFA 51 PI User manual

VDH ALFANET 71-2SP User manual

VDH

VDH ALFANET 71-2SP User manual

VDH ALFA 71 User manual

VDH

VDH ALFA 71 User manual

VDH ALFA 35 DP User manual

VDH

VDH ALFA 35 DP User manual

VDH MC 785D User manual

VDH

VDH MC 785D User manual

Popular Thermostat manuals by other brands

Full Gauge TIC-17C product manual

Full Gauge

Full Gauge TIC-17C product manual

Imit Chronomix S manual

Imit

Imit Chronomix S manual

ChiliTec ST-35 ana instruction manual

ChiliTec

ChiliTec ST-35 ana instruction manual

Salus VS05 Installer's/user's manual

Salus

Salus VS05 Installer's/user's manual

Azel D-500 user guide

Azel

Azel D-500 user guide

Honeywell Chronotherm III owner's manual

Honeywell

Honeywell Chronotherm III owner's manual

Charmeg MP-R user manual

Charmeg

Charmeg MP-R user manual

dixell WING XW40LS Installing and operating instructions

dixell

dixell WING XW40LS Installing and operating instructions

Network Thermostat NetX X7C-WIFI Installation and programming manual

Network Thermostat

Network Thermostat NetX X7C-WIFI Installation and programming manual

Radio Thermostat CT80 Operation guide

Radio Thermostat

Radio Thermostat CT80 Operation guide

HAI Omnistat RC-120 installation manual

HAI

HAI Omnistat RC-120 installation manual

Lennox iComfort E30 Installation and setup guide

Lennox

Lennox iComfort E30 Installation and setup guide

Lux Products PSD011Ba Installation and operating instructions

Lux Products

Lux Products PSD011Ba Installation and operating instructions

Computherm Q20 operating instructions

Computherm

Computherm Q20 operating instructions

Heatmiser neoStat user manual

Heatmiser

Heatmiser neoStat user manual

Mars HEAT CONTROLLER IR Wireless Thermostat user manual

Mars

Mars HEAT CONTROLLER IR Wireless Thermostat user manual

LUX LP0511D user manual

LUX

LUX LP0511D user manual

Saswell SAS920XWHB-7-S-RF User manual and warranty card

Saswell

Saswell SAS920XWHB-7-S-RF User manual and warranty card

manuals.online logo
manuals.online logoBrands
  • About & Mission
  • Contact us
  • Privacy Policy
  • Terms and Conditions

Copyright 2025 Manuals.Online. All Rights Reserved.

1
User manual
ALFA 71 S PI
Thermostat.
0-100C
VDH doc. 080350 Version: v1.0 Date: 07-03-2008
Software: ALFA71-S-PI 0-100 File: Do080350.WPD Range: 0/+100,0C
*Installation.
On the top side of the ALFA 71 S PI is shown how the sensors, power supply, relays and 0..10Vdc
Solid-State output hastobeconnected.After connectingtheALFA 71 S PI tothe power supply, aself
test function is started. As this test is finished the measured temperature appears in the display.
*Control.
The ALFA 71 S PI thermostat can be controlled by four pushbuttons on the front.
These keys are:
SET - view / change the setpoint.
UP - increase the setpoint.
DOWN - decrease the setpoint.
C- hidden push button above the SET key and behind Csymbol.
*Viewing setpoint.
BypushingtheSET key thesetpoint appearsinthedisplay.Thedecimal pointof thelastdisplaystarts
blinking. A few seconds after releasing the SET key the setpoint disappears and the measured
temperature is shown again in the display.
*Changing setpoint.
Push the SET key and the setpoint appears in the display. Release the SET key. Now push the SET
key again together with the UP or DOWN keys to change the setpoint. A fewseconds after releasing
the keys the measured temperature shows again in the display.
*Status of the Relays.
By pushing thehidden Ckey the display shows thestatus of the relays. Eachdisplay segment shows
thestatus of therelay output, showing 0=off and 1=on. The code 110 meansrelay 1 and 2 are on and
relay 3 is off.
*Setting internal parameters.
Next to the adjustment of the setpoint, internal settings can be made like differential, sensor-offset,
setpoint range and the functions of the thermostat.
Push the DOWN key more than 10 seconds, to enter the 'Internal Programming Menu'. In the left
display the upper and lower segment are blinking. Over the UP and DOWN keys the required
parameter can be selected (see table for the parameters).
If therequiredparameter isselected, the valuecan be read-out by pushing the SET key. Pushing the
UP or DOWN key to change the value of this parameter.
If after 20 seconds no key is pushed, the ALFA 71 S PI changes to the normal operation mode.
2
*Adjustment sensors.
The temperature sensor can be adjusted by using the Sensor Offset parameter 06.
Indicates the Sensor e.g. 2C to much, the Sensor Offset has to be decreased with 2C.
*Error messages.
In the display of the ALFA 71 S PI the following error messages can appear:
LO - Minimum alarm. Solution E1:
HI - Maximum alarm. - Check if the sensor is connected correctly.
E1 - Sensor-1 failure. - Check sensor (1000at 25C).
- Replace sensor.
EEE - Settings are lost. Solution EEE:
- Reprogram the settings.
-L- - In case of sensor short-circuit the display alternates between error-code E..
and -L-, as indication for a short-circuit sensor.
-H- - In case of open-circuit sensor the display alternates between error-code E..
and -H-, as indication for a open circuit sensor.
Reset Alarm. When a error-messages appears it can be resetted by pushing the SET key. The
function of this key depends on parameter P37.
*Technical details.
Type : ALFA 71 S PI Thermostat
Range : 0/+100,0C, display per 0,1C
Supply : 12Vac 50/60Hz (-5/+10%)
Display : 3-digit 7-segment display
Relays : Ry1= SPST(NO) 250V/8A (cos=1) of 250V/5A (cos =0.4)
Ry2= SPST(NO) 250V/8A (cos=1) of 250V/5A (cos =0.4)
Ry3= SPDT(NO/NC) 250V/8A (cos=1) of 250V/5A (cos =0.4)
Relays have one common (C).
Control : By push buttons on front.
Front : Polycarbonate IP65
Sensor : SM 811/2m (PTC 1000/25C).
Analog output : 0..10 Vdc Solid State output
Dimensions : 35 x 77 x 71,5mm (HWD)
Panel cutout : 28 x 70mm (HW)
Accuracy : ± 0,5% of the range.
- Provided with memory protection during power failure.
- Connections with screw terminals on the back side.
- Equipped with sensor failure detection.
- Special versions on request available.
3
*Parameters ALFA 71 S PI
Para-
meter Description Parameter Range Default
01
02
03
04
Function Relay 1 1 = Cool
2 = Heat
3 = Alarm
Function Relay 2 (same as relay 1)
Function Relay 3 (same as relay 1)
Function PI-output 1 = Cool
2 = Heat
1..3
1..3
1..3
1..2
1
2
3
1
05
06
07
08
Offset temperature sensor 1
Offset PI function (zone)
P-band setting
I-time setting (0 means off)
-15.0..+15.0C
-15.0..+15.0C
0.0..20.0C
0..99 Minutes
0.0
0.0
5.0
0
10
11
12
13
14
15
16
17
18
19
Switch on relay 2 by 0 = Temperature
1 = Time
Switch on relay 3 by 0 = Temperature
1 = Time
Switch on delay relay 2
Switch on delay relay 3
Switching differential relay 1
Setpoint offset relay 1
Switching differential relay 2
Setpoint offset relay 2
Switching differential relay 3
Setpoint offset relay 3
0..1
0..1
0..99 Minutes
0..99 Minutes
0.1..15.0C
-15..+15C
0.1..15.0C
-15..+15C
0.1..15.0C
-15..+15C
0
0
15
15
0.5
0.0
0.5
0.0
0.5
0.0
20
21
22
23
24
Switch on delay cooling
Switch off delay cooling
Parameter 20/21 in Sec. or Min.
0 = Seconds
1 = Minutes
Minimum on-time cooling
Minimum off-time cooling
0..99
0..99
0..1
0..99 Minutes
0..99 Minutes
0
0
0
0
0
25
26
27
Minimum set point
Maximum set point
Read-out above -10C per 1C
-50.0..+50.0C
-50.0..+50.0C
0 = No, 1 = Yes
-50
+50
0
30
31
32
33
34
35
36
37
Alarm type 0 = None
1 = Absolute
2 = Relative
Minimum alarm set point
Maximum alarm set point
Time delay minimum alarm
Time delay maximum alarm
Function alarm relay 0 = Fail safe
alarm 1 = Control alarm
Reset alarm relay after recovering alarm
Reset alarm relay after manual reset
0..2
-50.0..+50.0C
-50.0..+50.0C
0..99 minutes
0..99 minutes
0..1
0= No, 1= Yes
0= No, 1= Yes
1
-50
+50
0
0
0
0
0
40
41 Start up delay after power failure
Forced relay function at sensor failure
0 = None
1 = Cool
2 = Heat
0..99 Minutes
0..2 0
0
50
51 Duty Cycle control active
Duty Cycle cycle time 0= No, 1= Yes
5..240 Seconds 1
20
95
96
97
98
99
Software version
Production year
Production week
Serial number (x1000)
Serial number (units)
-
-
-
-
-
-
-
-
-
-
4
*Dimensions.
*Connections.
*Address.
VDH Products BV Tel: +31 (0)50 - 30 28 900
Produktieweg 1 Fax: +31 (0)50 - 30 28 980
9301 ZS Roden Email: info@vdhproducts.nl
The Netherlands Internet: www.vdhproducts.nl