manuals.online logo
Brands
  1. Home
  2. •
  3. Brands
  4. •
  5. Vector
  6. •
  7. Controllers
  8. •
  9. Vector TCY-MT2-U User manual

Vector TCY-MT2-U User manual

Temperature PID controller TCY-MT-U
Temperature PID controller TCY- MT-U
Temperature PID controller TCY- MT-U
Doc: 70-00-0177-20, V1.2 20160119 © Vector Controls GmbH, Switzerland Subject to alterations
TCY-MT-U Intelligent temperature PID controller
Features
Temperature PID control for HVAC systems.
Up to 2 modulating outputs for DC 0...10V with 10mV resolution.
1 internal temperature sensor and up to 2 external sensor inputs
Multiple remote control functions on external input
Password protected programmable user and control parameters
Blue backlight
Applications
Various temperature control applications
Stand alone VAV control for pressure independent actuators
Water Only Systems: Radiator, floor heating or chilled ceilings
Individual room control for offices, residential, hotel rooms, meeting rooms, etc.
General description
The TCY-MT-U is a stand-alone electronic universal controller with one temperature control loop. Itmay use
up to 2 PID sequences. The TCY-MT-U features 1 internal NTC temperature sensor, one external sensor,
one binary input and one analog output. The configuration has been reduced to a minimum to allowfor a
simple and off the shelve usage. For more advanced features and current in- and outputs the TCI product
range is recommended. The TCY-MT-U can be configured using the standard operation terminal. No special
tool or software is required.
TCY-MT2-U
│ │││ └──── Housing: U = Vertical (2” x 4”) housing, Standard is square housing
│ ││└────── Function: 2 = 2-pipe, 4 = 4-pipe
│ │└─────── Input T = Temperature
│ └──────── Output: B = Binary
└──────────Series Indication TCY
Item Name
Item code
Variant
Features
TCY-MT2-U-W01
40-10 0044-01
Cooling only
Compact PID controller with:
2 TI, 1 AO
TCY-MT2-U-W02
40-10 0044-02
Heating only
TCY-MT2-U
40-10 0044
2-Pipe system
TCY-MT4-U
40-10 0046
4-Pipe system
1 TI, 2 AO
Accessories
S-Tn10-2
SD-Tn10-12-2
SD-Tn10-20-2
SDB-Tn10-12
SDB-Tn10-20
SOA-Tn10
40-20 0001
40-20 0002
40-20 0003
40-20 0051
40-20 0004
40-20 0006
Flying lead sensor with 2 m cable
Flying lead duct sensor 12cm immersion depth, 2m cable
Flying lead duct sensor 20cm immersion depth, 2m cable
Duct sensor with housing, 12cm immersion depth
Duct sensor with housing, 20cm immersion depth
Outdoor sensor
Selection of actuators and sensors
Use only our approved NTC sensors to achieve maximum accuracy. Recommended is SDB-Tn10-20 as
Duct sensor, SRA-Tn10 as Room sensor and SDB-Tn10-20 with AMI-S10 as immersion sensor.
Modulating Actuators:
Choose actuators with an input signal type of 0-10V DC or 2-10V DC.
Mounting location
On an easy accessible interior wall, approx. 1.5 m (4.5’) above the floor in an area of
average temperature.
Avoid exposure to direct sunlight or other heat sources, e.g. the area above radiators and
heat emitting electrical equipment.
Avoid locations behind doors, outside walls and below or above air discharge grills and
diffusers.
Location of mounting isless critical if external temperature sensors are used
Installation
1. Connect the wires to be connected to the terminals of the power case according to wiring
diagram
2. Install the mounting plate to the flush mounting box. Make sure that the nipple with the front
holding screw is facingto the ground. Make sure the mounting screwheads do not stand out
more than 5 mm (0.2”) off the surface of the mounting plate.
3. Ensure that the jumpers are set correctly.
4. Slide the two latches located on the top of thefront part into the hooksat the upper side of
the mounting plate.
5. Carefully lower the front part until the interconnector reaches the mounting-plate. Continue
pressing in a gentle way until the front part isfully connected.While inserting the connectors,
a slight resistance can be felt. This is normal. Do not use excessive force!
6. With a Philips-type screw driver of size #2, carefully tighten the front holding screw to secure
the front part to the mounting plate. This screw is located on the front lower side of the unit.
There is no need to tighten the screw toomuch.
Display and operation
Power failure
Upon power-interruption,all parameters and set points are memorized in non-volatile memory and therefore do not
have to be re-entered again.
Error messages
Err1: The connection tothe temperature sensor may be interrupted or thetemperature sensor is damaged.
The output is switched off. Verify parameter settings and wiring.
Technical specification
Power Supply
Operating Voltage
24 V AC/DC ± 10 %, 50/60 Hz, Class 2 48VA max
Power Consumption
Max. 1.5 VA
Electrical Connection
Terminal Connectors,
wire 0.34…2.5 mm2(AWG 24…12)
Signal inputs
Temperature Input
Range
0…50 °C (32…122 °F)
Accuracy
0.5 K
Signal outputs
Analog Outputs
Output Signal
Resolution
Maximum Load
AO1, For TCY-MT4 AO2
DC 0...10 V
9.76 mV (10 bit)
10 mA
Environment
Operation
Climatic Conditions
Temperature
Humidity
To IEC 721-3-3
class 3 K5
0…50 °C (32…122 °F)
<95 % r.H. non-condensing
Transport & Storage
Climatic Conditions
Temperature
Humidity
Mechanical Conditions
To IEC 721-3-2 and IEC 721-3-1
class 3 K3 and class1 K3
-25…70 °C (-13…158 °F)
<95 % r.H. non-condensing
class 2MT2
Standards
conform according
to
EMC Standard
89/336/EEC
EMEI Standard
73/23/EEC
EN 61 000-6-1/ EN 61 000-6-3
Product standards
Automatic electrical controls for
household and similar use
Special requirement on temperature
dependent controls
EN 60 730 –1
EN 60 730 –2 –9
Degree of Protection
IP30 to EN 60529
Safety Class
III (IEC 60536)
Housing
Cover, back part
Mounting Plate
Fire proof ABS plastic (UL94 class V-0)
Galvanized Steel
General
Dimensions (H x W x D)
Front part: 112 x 73 x 15 mm (4.4” x 2.9” x 0.6”)
Power case: ø 58 x 32 mm (ø 2.3” x 1.3”)
Weight (including package)
270 g (9.5 oz)
Wiring diagram
Description:
G0 Power supply: 0V, -24VDC, internally connected to signal common
G Power supply: 24VAC, +24VDC
M Signal common: Common 0 potentialfor analog inputs and analog outputs.
X1 External temperature input: NTC 10kΩ @ 25°C (77°F)
TCY-MT2:
X2 Changeover input: NTC 10kΩ @ 25°C (77°F)
U1 Analog output: 0…10 V DC
TCY-MT4:
U1 Analog heating output: 0…10 V DC
U2 Analog cooling output: 0…10 V DC
Dimensions [mm] (in)
58 (2.3)
112 (4.4)
73 (2.9)
32 (1.2)
15
(0.6
)
0V (COM)
24V AC
2
G
TCY-MT2-U
1
G0
34
G0U1
YM1
XT CO
5 6
M X2
XT EXT
7 8
M X1
0V (COM)
24V AC
2
G
TCY-MT4-U
1
G0
34
G0U1
YM H
XT EXT
7 8
M X1
5 6
G0U2
YM C
Left (POWER): Press < 2 sec.: Toggle
STANDBY-COMFORT mode or switch
from OFF to ON
Press > 2 sec.: Turn unit OFF. Text OFF
displayed with current time (deluxe)
temperature (standard)
(Parameter setting: ENTER to select
menu option, accept parameter change)
Up: Increment SET POINT
(Parameter setting:
SCROLL menu options and
parameters)
Down: Decrement SET POINT
(Parameter setting: SCROLL menu
options and parameters)
Mode
Display of operation mode
Large Digits: Display of input
or parameter value.
Indicators
1 Remote temperature
sensor
2 Dew point sensor
Vertical Bar: (scrolls
up/down, 10% resolution)
Small Digits: Display of set
point, clock or parameter
number.
Right (OPTION):
Press < 2 sec.: Select Control Loop
Press > 2 sec.: Manual H/C change
(Parameter setting: ENTER to
select menu option, accept
parameter change)
Temperature PID controller TCY-MT-U
Temperature PID controller TCY- MT-U
Temperature PID controller TCY- MT-U
Doc: 70-00-0177-20, V1.2 20160119 © Vector Controls GmbH, Switzerland Subject to alterations
Configuration parameters for firmware version 1.2
The TCY-MT-U is preset to work for most applications. For special requirementsit can be fine tuned to work
ideal with a simple parameter setup routine. The parameters can be changed on the unit without the need of
additional equipment.
Identifying the firmware version
The parameters andfunctionality of controller depend on its firmware version and revision. It is therefore
important to use a matching product version and parameter set. The Firmware version and revision version
can be found when pressing simultaneously the andkeys during several seconds. On the upper 7
segment display, the firmware version can be found, on the lower 7 segment display the current revision
index (or “sub-version”).
Setting of user parameters
The TCY-MT-U can be adapted tofit perfectly into your application. The control operation is defined by
parameters. The parameters are set during operation by using the control buttons.
The parametersmay only be accessed by entering a code. There are two levels of parameters: User
operation parametersfor access control settings, and Expert parameters for control functions and unit setup.
The codes for user levels and expert levels are different. Only control experts should be given the control
parameter code.
The parameters can be changed as follows:
1. PressUP and DOWN button simultaneously for three seconds. The display shows the software
version in the large digitsand the product codein the small digits.
2. Pressing the OPTION button will indicate CODE onthe small digits and 000 on the large digits.
3. The code for accessing the user parameters is 009
4. Select this using UP or DOWN buttons.
5. Press OPTION button after selecting the correctcode.
6. Once logged in, the parameter is displayed immediately.
7. Select the parameters with the UP/DOWN buttons. Change a parameter by pressing the OPTION
button. Three triangleswill show up on the lower right and indicate thatthe parameter may be
modified now. Use UP or DOWN buttonsto adjust the value.
8. After you are done, press OPTION or POWER in order to return to the parameter selection level.
Press the POWER button again so as to leave the menu. The unit will return to normal operationif no button
is pressed for more than 5minutes.
User parameters (Password 09)
Parameter
Description
Range
Default
UP 00
Enable access to operation modes
ON, OFF
ON
UP 01
Enable access to set points
ON, OFF
ON
UP 02
Not used
ON, OFF
OFF
UP 03
Enable manual change of Heating/Cooling Mode.
No influence on TCY-MT2-U-W01 (cooling only) or
TCY-MT2-U-W02 (heating only)
ON, OFF
TCY-MT2-W01: OFF
TCY-MT2-W02: OFF
TCY-MT2: ON
TCY-MT4: ON
UP 04
Not used
ON, OFF
OFF
UP 05
State after power failure:
0 = off, 1 = on, 2 = state before power failure
0, 1, 2
2
UP 06
Enable Economy (unoccupied) Mode.
Shift the set point to a lower temperature in winter or
higher temperature in summer in order to save energy.
May be activated through the POWER button, or with
the external input (typically for key card switches in hotel
rooms or motion detectors for meeting rooms.)
ON, OFF
ON
UP 07
ON = Fahrenheit, OFF = Celsius
ON, OFF
OFF (Celsius)
UP 08
Calibrate internal temperature sensor
–10° to +10° in 0.1° steps. (Sensor is factory calibrated;
use this feature for field adjustment only as required.)
-10…10
0
UP 09
Enable Frost Protection.
Activates the output independent of operation mode
when the control temperature drops below 5°C or 41°F.
The controller returns to normal operation when the
temperature increases above 10°C or 50°F.
ON, OFF
TCY-MT2-W01: OFF
TCY-MT2-W02: ON
TCY-MT2: ON
TCY-MT4: ON
Control parameters (Access code: 241)
Warning! Only expertsshould change these settings! See user parameters for login procedure.
Parameter
Description
Range
Default
CP 00
Minimum set point limit in Heating mode
0…60°C (32..160°F)
16°C (61°F)
CP 01
Maximum set point limit in Heating mode
0…60°C (32..160°F)
30°C (86°F)
CP 02
Minimum set point limit in Cooling mode
0…60°C (32..160°F)
18°C (65°F)
CP 03
Maximum set point limit in Cooling mode
0…60°C (32..160°F)
30°C (86°F)
Controls configuration
CP 04
Economy (unoccupied) Mode temperature shift:
The comfort (occupied) set point is shifted by the value set
with parameter. If heating is active the comfort set point will
be decreased, if cooling is active, the set point will be
increased. (Enable with UP06.)
0…100°C (200°F)
5.0°C (10°F)
CP 05
Dead Zone Span (TCY-MT4-U only):
The Dead Zone Span lies between the heating and the
cooling set point. The outputis off while the temperature is
within the dead zone span. A negative dead zoneis not
possible.
0…100°C (200°F)
1.0°C (2°F)
CP 06
Heat/Cool Changeover Delay (TCY-MT4-U only):
A demand to switch between heating and cooling must
persist for thelength of time set with this parameter before
the controller switches. Prevents activation of a sequence
during a short-term change in temperature in order to
protect equipment (with control overshoot for example)
0…255 min
5 min
CP 07
P-band heating XPH
0…100°C (200°F)
2.0°C (4.0°F)
CP 08
P-band cooling XPC
0…100°C (200°F)
2.0°C (4.0°F)
CP 09
KIH, Integral gain heating, in 0.1 steps, (TI is fixed to 4s)
0 disables ID part
low value = slow reaction
high value = fast reaction
0…25.5
0.0
CP 10
KIC, Integral gain cooling, in 0.1 steps, 0 disables I part
0…25.5
0.0
CP 11
Configuration of operation mode
0 = TCY-MT2-U-W01 = Cooling mode YC1
1 = TCY-MT2-U-W02 = Heating mode: YH1
2 = TCY-MT2-U = Heating and Cooling (2 pipe system)
3 = TCY-MT4-U = Heating and Cooling (4 pipe system)
TCY-MT2: 0 - 2
TCY-MT4: 0 –3
TCY-MT2-W01: 0
TCY-MT2-W02: 1
TCY-MT2: 2
TCY-MT4: 3
Proportional control (P-band)
The proportional control function calculatesthe output based on the difference between set point and
measured value. The proportional band (P-band) defines the difference between set point and measured
value which will result in a 100% output. For example, with a heating or reverse 0-10v control sequence, and
a 2.0°C (4.0°F) P-bandvalue, at 10v the controller will be 2.0°C (4.0°F) below set point. This is the working
range of the proportional control sequence.
Setting the proportional band to 0 disablesproportional control.
Integral and differential control
Proportional control is avery stable control mode. The flaw of proportional control alone, however, is that the
set point is normally not reached. As the measured value gets closer to the set point, the output reduces
until it reaches a point, a fraction above or below the set point, where the output equals the load. To reach
the set point and achieve a higher level in comfort the Integral/Differential function should be activated.
Integral Gain (KI) dynamically increases the output by the selected KI valueuntil the set point is reached.
The challenge, however, is to prevent hunting, where the output increases too fast, the temperature
overshoots the set point, the output goes to 0, thetemperature undershoots the set point, and the cycle
repeats itself. Hunting may result if the integral gain is too high. Each system is different. It is recommended
to start with a KI value of 0.5 for water based systems and 1.0 for air based systems. Reduce thisvalue if
the measured value overshoots the set point by more than 1°C (2°F). Increase the value if the output takes
too long to reach the set point. Air based systems react faster than water based systems.
Setting the integral gain to 0 disables integral and differential control.
Output configuration
Parameter
Description
Range
Default
CP 12
Manual Override Mode:
Allows manual control of the analog outputsfor using the
controller as positioned, or during commissioning.
ON, OFF
OFF
CP 13
Min output for AO1 (TCY-MT4-U = heating output)
0 –100 %
20%
CP 14
Max output for AO1 (TCY-MT4-U = heating output)
0 –100 %
100%
CP 15
Min output for AO2 (TCY-MT4-U = cooling output)
0 –100 %
20%
CP 16
Max output for AO2 (TCY-MT4-U = cooling output)
0 –100 %
100%
CP 17
Maximum Output in Economy (unoccupied)Mode
Reduces the load on the system when is the space is
unoccupied.
0 –100 %
50%
Input configuration
CP 18
Configuration of remote control input (X1)
0 = Control input if temperature sensor connected
1 = Occupation sensor –Comfort / Standby
2 = Remote enable –Comfort / OFF
3 = Keycard function: fixed set point
0…3
0
CP 19
Activation delay (Minutes) = the time the binaryinput needs
to be open before standby/off mode is activated.
0…255 min
5
CP 20
Fixed set point for key card function in heating mode
0…60°C
(32..160°F)
17°C (63°F)
CP 21
Fixed set point for key card function in cooling mode
0…60°C
(32..160°F)
27°C (81°F)
CP 22
For TCY-MT2-U only: Enable Auto changeover
ON, OFF
OFF
CP 23
For TCY-MT2-U only: Auto-changeover limit heating
0…60°C
(32..160°F)
30°C (86°F)
CP 24
For TCY-MT2-U only: Auto changeover limit cooling
0…60°C
(32..160°F)
15°C (59°F)
Configuring the function of the external input X1
The external input X1 may be configured for several functions:
CP18 = 0
External control
input
The control input is provided by the external input. The
internal input will not be used.
CP18 = 1
Switching Economy
and Comfort modes
Economy (unoccupied) and Comfort (occupied) modes
are controlled through an external contact by connecting
X1 through a dry contactto signal common. This function
may be used together with key card switches for hotels or
motion detectors for offices.
CP18 = 2
Switching Energy
Hold OFF and
Comfort modes
Opening the external temperature input will force the unit
into the OFF operation mode. The operation mode cannot
be overridden by using theterminal. Connectingthe
binary input to GND returns control of the operation mode
to the terminal. Thisfunction may be used as window
contact to prevent loss of energy.
CP18 = 3
Key card function
As with CP18 = 1, the key card function switches
economy (unoccupied) and comfort (occupied) modes.
Instead of usingthe set point shift, the set points in
unoccupied mode are defined by parameter CP20 and
CP21.
CP18 = 4
Output enable
This may be used for a dewpoint sensor input. Output will
switch off if contact opens.
Configuring auto changeover input X2 (TCY-MT2-U only):
The auto changeover function automatically changes heating and coolingmode based on supply
media temperature or outdoor temperature. The difference between the two is in the values of the
changeover limits CP23 and CP24. See table below for recommended settings.
Heating and cooling may be as well changed by an open contact switched to signal ground. Note: all
signal ground levelsof involved controllersmust be the same in case more than one controller is
switched.
Recommended settings for CP23 and CP24:
Change over mode
Relation CP23 to
CP24
Example
CP23
Example:
CP24
Supply media
CP23 > CP24
25°C (77F)
18°C (64F)
Outside temperature
CP23 < CP24
15°C (59F)
25°C (77F)
Dry contact: Heating if contact closed
CP23 > CP24
25°C (77F)
15°C (59F)
Dry contact: Cooling if contact closed
CP23 < CP24
15°C (59F)
25°C (77F)

This manual suits for next models

3

Other Vector Controllers manuals

Vector TCI-W11 User manual

Vector

Vector TCI-W11 User manual

Vector TCI-C Series User manual

Vector

Vector TCI-C Series User manual

Vector TRA-F121-A User manual

Vector

Vector TRA-F121-A User manual

Vector 40-10 0259 User manual

Vector

Vector 40-10 0259 User manual

Vector TLR-D5P-U SeriesTLR-D5P-24 Installation and operation manual

Vector

Vector TLR-D5P-U SeriesTLR-D5P-24 Installation and operation manual

Vector TCI-W User manual

Vector

Vector TCI-W User manual

Vector TCI2 Series Operational manual

Vector

Vector TCI2 Series Operational manual

Vector OPA2 Series User manual

Vector

Vector OPA2 Series User manual

Vector MZ3-C-V11 User manual

Vector

Vector MZ3-C-V11 User manual

Vector TLC3-FCR-M-U-120 User manual

Vector

Vector TLC3-FCR-M-U-120 User manual

Vector TLC3-FCR-2T Installation and operation manual

Vector

Vector TLC3-FCR-2T Installation and operation manual

Vector TCY3-T0121R User manual

Vector

Vector TCY3-T0121R User manual

Vector MZ3-V11 User manual

Vector

Vector MZ3-V11 User manual

Vector TLC3-FCR-T Installation and operation manual

Vector

Vector TLC3-FCR-T Installation and operation manual

Vector TLC3-FCR-T-U Series Installation and operation manual

Vector

Vector TLC3-FCR-T-U Series Installation and operation manual

Vector TCI-W13-H User manual

Vector

Vector TCI-W13-H User manual

Vector TRA-F12 A Series User manual

Vector

Vector TRA-F12 A Series User manual

Vector TCI-W13-U-H User manual

Vector

Vector TCI-W13-U-H User manual

Vector TRA-F22 A Series User manual

Vector

Vector TRA-F22 A Series User manual

Vector TRA-F12x-A User manual

Vector

Vector TRA-F12x-A User manual

Vector MZ3-FU-V11 User manual

Vector

Vector MZ3-FU-V11 User manual

Vector MZ3-V11 User manual

Vector

Vector MZ3-V11 User manual

Vector TCI-W13 User manual

Vector

Vector TCI-W13 User manual

Vector VEC-VA Series Owner's manual

Vector

Vector VEC-VA Series Owner's manual

Popular Controllers manuals by other brands

METRON FD2 manual

METRON

METRON FD2 manual

BST ekr 500 Plus Quick reference guide

BST

BST ekr 500 Plus Quick reference guide

Johnson Controls M9308-A Z Series installation guide

Johnson Controls

Johnson Controls M9308-A Z Series installation guide

Paratec TE Series user manual

Paratec

Paratec TE Series user manual

YASKAWA SI-EM3 Technical manual

YASKAWA

YASKAWA SI-EM3 Technical manual

Lynn Electronics CTR2-Mini+ Assembly manual

Lynn Electronics

Lynn Electronics CTR2-Mini+ Assembly manual

Zareba B10LI user manual

Zareba

Zareba B10LI user manual

Swagelok KPF Series Maintenance instructions

Swagelok

Swagelok KPF Series Maintenance instructions

ST STEVAL-IHM037V1 user manual

ST

ST STEVAL-IHM037V1 user manual

TWR Lighting E-1DB manual

TWR Lighting

TWR Lighting E-1DB manual

PPI neuro 202 user manual

PPI

PPI neuro 202 user manual

Rollerdor RD10X2ELL installation guide

Rollerdor

Rollerdor RD10X2ELL installation guide

Cleco Tools CellCore mPro200GC-AP Quick installation guide

Cleco Tools

Cleco Tools CellCore mPro200GC-AP Quick installation guide

Ltech LT-800 quick start guide

Ltech

Ltech LT-800 quick start guide

METRON MP430 Series manual

METRON

METRON MP430 Series manual

Elan SC1 Quick install guide

Elan

Elan SC1 Quick install guide

Kaysun KC-03.1 SPS User and installation manual

Kaysun

Kaysun KC-03.1 SPS User and installation manual

Lexicon MC-12 EQ - REV 1 user guide

Lexicon

Lexicon MC-12 EQ - REV 1 user guide

manuals.online logo
manuals.online logoBrands
  • About & Mission
  • Contact us
  • Privacy Policy
  • Terms and Conditions

Copyright 2025 Manuals.Online. All Rights Reserved.