Vectra Fitness FM-1309-Z User manual

USER’S MANUAL
Руководство по установке и эксплуатации
AIR CURTAINS
Воздушные завесы
Models:
Модели:
FM1309Z/Y
FM1312Z/Y
FM1315Z/Y


CONTENTS
LEGEND . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
1 APPLICATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .5
2 CAUTION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
3 TECHNICAL PARAMETERS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
4 ASSEMBLY AND OPERATION PRINCIPLE . . . . . . . . . . . . . . . . . . . . . . . . . 7
5 OPERATION MODES AND CONTROL OF AIR CURTAIN . . . . . . . . . . . . . . 7
6 AIR CURTAIN MAINTENANCE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
7 INSTALLATION AND CONNECTION GUIDANCE . . . . . . . . . . . . . . . . . . . . 9
8 SERVICE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .15
СОДЕРЖАНИЕ
УСЛОВНОЕ ОБОЗНАЧЕНИЕ . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
1 ОБЛАСТЬ ПРИМЕНЕНИЯ . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .17
2 МЕРЫ БЕЗОПАСНОСТИ . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
3 ТЕХНИЧЕСКИЕ ХАРАКТЕРИСТИКИ . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
4 УСТРОЙСТВО И ПРИНЦИП РАБОТЫ . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
5 РЕЖИМЫ РАБОТЫ И УПРАВЛЕНИЕ ЗАВЕСОЙ . . . . . . . . . . . . . . . . . . 19
6 УСЛОВИЯ ЭКСПЛУАТАЦИИ . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21
7 УСТАНОВКА И ПОДКЛЮЧЕНИЕ . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21
8 ОБСЛУЖИВАНИЕ . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27

4
Constructive features*
Length of Air Curtain (x 10), cm
Wind wheel impeller diameter, cm
Air Curtain code
*Constructive features
Y: infrared remote controlling
Z: axial type
Legend
FM 13 XX Z/ Y

1 APPLICATION
Air Curtain is developed for the separation of air zones with the different
temperature by creating of vertical direct air flow to protect from external air
penetrating throw the open door.
Air Curtain can be applied for protection of airconditioning rooms and
cold stores from penetration of external air, dust, insects etc. at heating
switchoff by remote control.
Air Curtain (or several Air Curtains) must overlap all door width for the best
result.
Air Curtain can be controlled by infrared remote control.
The installation height is 2,5 m.
2 CAUTION
2.1 Please follow the general rules of electrical safety at electrical instru
ment operation.
2.2 The unit doesn’t be installed near highly inflammable materials. Don’t
allow the installation in a place where it is splashed by water, exposed to
excessive steam, smoke, dust, vapors of acids, alkali, explosive gas or corro
sive gas and also resins and technical fibers.
2.3 To avoid overheat and ignition don’t overlap the input and output vents,
cover the Air Curtain and put different things on it.
2.4 Air Curtain maintenance is forbid without earth at qualified personnel
absence.
2.5 Service operations are forbid at switchedon Air Curtain.
2.6 At operative termination the Air Curtain must be deenergized.
5
Caution

3 TECHNICAL PARAMETERS.
3.1 Technical parameters are entered in Table 3.1
Table 3.1
2.2 Electric operate circuit is according to items 7.4.1 and 7.4.2 of this
manual.
6
Technical parameters
Model FM1309Z/Y FM1312Z/Y FM1315Z/Y
Power Supply, V/Hz ~230/50
Air volume (m3/h) 1050/1400 1680/1760 1680/2240
Air speed at output grate,
more than, m/s 8,5 / 11
Number of wind wheels,
pieces 5 6 8
Recommended installa
tion height, less than, m 3
Dimensions, mm
length
width
height
900
157
220
1200
157
220
1500
157
220
Protection class IP20
Electric injury Protection
class 1
Motor Power, W 130 160 215
Sound pressure level,
less than, dB(A) 52 54 58
Weight, kg 11,2 14,5 18

7
Operation modes and controls of Air Curtain
4 ASSEMBLY AND OPERATION PRINCIPLE
4.1 Axial wind wheels type with motors are installed in metal cabinet of Air
Curtain (Fig.1). The number of wind wheels is from 5 to 8 (depending on
Model).
Figure 1– Air Curtain assembly.
4.2 At wind wheel impellers, an air is rejected throw the upper panel and
discharged throw the outlet grate creating the direct air flow.
5 OPERATION MODES AND CONTROL OF AIR CURTAIN
5.1 Air Curtain has the next operation modes:
“COOLHi” is high speed ventilation mode.
“COOLLo” is low speed ventilation mode.
Air inlet
Air outlet
Impeller Mounting plate
Control board
Upper panel

8
Operation modes and controls of Air Curtain
5.2 Air curtain control
5.2.1 Air Curtain is controlled by infrared remote control or ON/OFF key on
the front panel of Air Curtain (Fig.2 and 3)
Figure 2. Infrared remote control.
Figure 3. Air Curtain control panel.
ON/OFF Key
High speed indicator Hi
Low speed indicator Lo
ON/OFF key
Remote control signal
receiver mouth

5.2.2 When the Air Curtain is turning off, press ON/OFF key. The “COOL
Hi” mode will start (high speed ventilation). The red lamp of Hi indicator will
light up.
Repeat press of ON/OFF key will switch the Air Curtain to “COOLLo” mode
and the Lo indicator red lamp will light up. The next press of ON/OFF key is
switching off Air Curtain.
5.2.3 Every press of ON/OFF key of Air Curtain panel will switch the unit
into different modes with the next sequence:
6 AIR CURTAIN MAINTENANCE.
6.1 Ambient temperature is from 40°C… to + 40°C.
6.2 Relative humidity is less than 80% at 20°C.
6.3 Dust and other air dirt contents are less than 10 mg/m3.
7 INSTALLATION AND CONNECTION GUIDANCE.
7.1 Installation requirements.
7.1.1 Air Curtains are installed as horizontal as vertical.
If you install Air Curtain horizontally, it must be installed more closely to the
upper of the door, and the interval between an up covered board and a ceil
ing must be more than 100 mm.
7.1.2 Air Curtain has the possibility of air flow angle adjustment to the door
aperture surface relatively. Necessity of angle installation is defined of
designer according to installation place.
9
Installation and connection guidance
COOL-Hi COOL-Lo OFF

10
Installation and connection guidance
7.1.3 Identification and installation dimensions (Figure 4).
Figure 4. Identification and installation dimensions
7.1.4 Air Curtain must be installed on a stable and strong wall able to keep
it weight.
7.1.5 Recommended installation height it less than 2–3 m.
7.1.6 When the entrance is wider than the unit, it is recommended to install
two or more units in parallel. In this case, provide 20–40 mm intervals between
the units.
Model A B
FM1309Z/Y 900 750
FM1312Z/Y 1200 1050
FM1315Z/Y 1500 1350

11
Installation and connection guidance
Figure 5. Abreast installation of several Air Curtains.
7.2 Please follow the next steps at Air Curtain installation.
a) Unscrew the screws and remove the mounting plate
b) Make the marks on the wall according to mounting plate holes.
c) Drill the holes and put the dowels into the wall.
d) Fix the mounting plate on the wall using the screws.
e) Install Air Curtain on the mounting plate. A interval must be more than
100 mm (Fig.6)
Figure 6. Mounting plate fixing.
Screw
Spring nut

12
Installation and connection guidance
f) Install Air Curtain on the mounting plate according to Figure 7.
A interval must be more than 100 mm.
Figure 7. Air Curtain Installation on the mounting plate.
g) Adjust the installation angle respectively a door if it is necessary.
Installation angle is adjusted by special screw in the 010° range (see Figure 8).
Figure 8. Installation angle adjustment.
Внутренняя сторона Наружная сторона
помещения помещения
Монтажная панель
Mounting plate
Outdoor
Indoor

13
Installation and connection guidance
7.3 Power connection
7.3.1 Power connection must be executed by qualified specialist accord
ing to regulations.
7.3.2 Power cable must be connected to the terminal board
7.3.3 Connection to the charging line must be executed by the all polarity
switch with the machining pass more than 3 mm (which has at least 3 mm sep
aration distance) by supplying cable 3 x 1.5 mm2.

14
Electric operation circuit
7.4.1 Electric circuit for key control air curtains is according to Fig.10.
Fig. 10. Electric circuit for key control air curtains.
7.4.2 Electric circuit for infrared remote control air curtains is according to
Fig.11.
Fig. 11. Electric circuit for infrared remote control air curtains.

15
Transportation and storage
8 TRANSPORTATION AND STORAGE.
8.1 Packing Air Curtains are transported by all kinds of covered transport
at t° from – 40°C to + 50°C and relative humidity 80% (at 20° C) excluding kicks,
beats and movements inside a transport.
8.2 Air Curtains must store in manufacturer’s packing at – 40°C to + 50°C
and average monthly humidity 80% (at 20°C).
NOTE: Keep switchedoff Air Curtain in the room where operation is
planning, during 2 hours at least after transportation or storage at
negative temperatures.

Условное обозначение
*) Конструктивные особенности: Y – дистанционное управление.
Z – Вентилятор осевого типа
16
FM 13 XX Z/ Y
Конструктивные особенности *)
Длина воздушной завесы (x10), см
Диаметр крыльчатки вентилятора, см
Код воздушной завесы

1 ОБЛАСТЬ ПРИМЕНЕНИЯ
Воздушная завеса (далее, завеса) предназначена для разделения
воздушных зон с разной температурой путем создания в вертикальной
плоскости направленного воздушного потока, препятствующего
проникновению наружного воздуха внутрь помещения через открытые
дверные проемы.
Завеса может применяться для защиты кондиционируемых
помещений и холодильных камер от проникновения наружного воздуха,
пыли, насекомых и т.п.
Завеса может управляться с инфракрасного дистанционного пульта
Высота установки завесы до 3 м.
2 МЕРЫ БЕЗОПАСНОСТИ
2.1 При установке и эксплуатации завесы необходимо соблюдать
общие правила электробезопасности при пользовании электроприбо
рами.
2.2 Не допускается устанавливать завесы в местах с повышенным
содержанием в воздухе, дыма, пыли, паров кислот, щелочей, горючих
агрессивных веществ, а также смол, технических волокон.
2.3 Во избежание перегрева и возможного возгорания не допускает
ся перекрывать входное и выходное воздушные отверстия, накрывать
завесу, класть на завесу различные предметы.
2.4 Запрещается эксплуатация завесы без заземления и в отсутствие
персонала.
2.5 Запрещается проводить работы по обслуживанию на работаю
щей завесе.
2.6 В случае прекращения эксплуатации завеса должна быть обесто
чена.
17
Меры безопасности

18
Технические характеристики
Модель завесы FM1309Z/Y FM1312Z/Y FM1315Z/Y
Источник питания, В/Гц ~230/50
Расход воздуха, м3/час 1050/1400 1680/1760 1680/2240
Скорость воздуха на
выходе из решетки, не
менее,м/с 8,5 / 11
Количество
вентиляторов, шт. 5 6 8
Рекомендуемая высота
установки, не более, м 3
Габаритные размеры,
мм
длина
ширина
высота
900
157
220
1200
157
220
1500
157
220
Степень защиты завесы IP20
Класс защиты от пора
жения электротоком 1
Мощность двигателя, Вт 130 160 215
Уровень звукового дав
ления ,не более, дБ(А) 52 54 58
Вес, кг 11,2 14,5 18
3 ТЕХНИЧЕСКИЕ ХАРАКТЕРИСТИКИ
3.1 Технические характеристики в соответствии с таблицей 3.1
Таблица 3.1
3.2 Схема функциональная электрическая в соответствии с п. 7.4

4 УСТРОЙСТВО И ПРИНЦИП РАБОТЫ
4.1 Завеса представляет собой устройство, в металлическом корпусе
которого установлены от пяти до восьми (в зависимости от модели)
вентиляторов осевого типа с электродвигателями (рис.1)
Рис. 1 – Устройство завесы
4.2 При вращении крыльчаток воздух всасывается через верхнюю
панель и нагнетается через выходную решетку, создавая направленный
воздушный поток.
5 РЕЖИМЫ РАБОТЫ И УПРАВЛЕНИЕ ЗАВЕСОЙ
5.1 Завеса имеет два режима скорости вращения вентиляторов:
«COOLHi» высокая скорость вращения вентилятора
«COOLLo» низкая скорость вращения вентилятора
19
Режимы работы и управление завесой

5.2 Управление завесой
5.2.1 Завеса управляется кнопкой ON/OFF с дистанционного пульта
или на корпусе (рис.2 и 3).
Рис. 2 – Инфракрасный дистанционный пульт управления
Рис.3 – Панель управления на завесе
20
Режимы работы и управление завесой
This manual suits for next models
5
Table of contents
Languages:
Other Vectra Fitness Heater manuals
Popular Heater manuals by other brands

Town & Country Fireplaces
Town & Country Fireplaces TCVT.WSPVB Installation and operating instructions

Ranger
Ranger R45LP manual

Russell Hobbs
Russell Hobbs RHFH1008B manual

Toyostove
Toyostove RSA-850 Operation and maintenance instructions

Varma Tec
Varma Tec VARMA 400 IPX5 operating instructions

TUYA
TUYA MORRIS MPH-20041S instruction manual