Venitem TUL500EN User manual

MA-AL-T500-01-07 Manual TUL500EN eng rev7 Page 1 of 8
POWER SUPPLY TUL500EN
CERTIFIED with the standard
EN 54-4:1997+A1:2002+A2:2006
EN 12101-10:2005
Installation Manual
GENERAL FEATURES
The Power Supply TUL500EN has been designed to be used as a Power Unit with power backup in Fire
Alarm Systems, in conformity to regulation (EU) No 305/2011 and how power supply equipment in systems
for smoke control and heat.
Its mechanical and electrical features make it complying to EN 54-4: 2007 Standard (Fire Alarm detecting
and signaling devices. Part 4: Power supply devices) which includes A1:2002 and A2:2006 updates.
FUNCTIONAL FEATURES
The power supply unit is made by a switching power supply, limited in constant precision current (rectangular
limitation), two 12 V 17 Ah batteries (not included) digital and analogical control circuit and micro-
controlled supervision circuit.
Power is available on 3 terminal-outputs protected by electronic fuses: A, B and C, for generic loads and one
connection BATT (with fuse): for back-up batteries. When a fuse trips, the corresponding LED on control
board (see Pict.2, DL1, DL6, DL7, DL8) will turn ON.
Electronic fuses try periodically to restore the power output: if an overload is removed, the power will be
available within 10 sec max.
The battery charge occurs at constant current (1 A) until the battery voltage reaches its nominal value (27,6
V @ 25° C), with temperature compensation. Maximum current supplied by the unit is 5 A, where 4 A is
for charge and 1 A is for recharging the battery.
The power supply is able to give 7 A peak for 25 seconds @ 25°C.
Four LEDs show the loads current consumption (3 green and 1 red: DL2, DL3, DL4, DL5)
One LED shows the Mains presence (LED1)
Check of battery efficiency
The power supply periodically carries out the efficiency of the batteries:
- At first activation of the power supply, the microprocessor will carry out the test of battery presence
after about 20 seconds. If connected, the test will be carried out every 10 minutes whilst in case it is
not connected, it will continue carry out the test every 20 seconds showing indication FAILURE.
- During normal operation, the battery efficiency is checked by controlling the batteries voltage. If
batteries do not manage to maintain an acceptable voltage during test, there will be the indication
FAILURE.
- A test of the battery internal resistance is carried out within 15 seconds after the battery connection
and then repeated every 2,5 hours, at least (in conformity to attachment EN54-4/A2); if the internal
resistance is over 1 ohm, there will be a FAILURE indication. With internal resistance failure
detected, this test is repeated every 5 minutes at most 5 times, to ensure recovery from spurious
failure detection. It will then be necessary to replace the batteries and check that terminals and fuses
have a good electrical contact. When the battery is replaced, the user should wait 15 seconds after
battery connection, with presence of mains voltage, for the repetition of the test and check if the
failure is removed. It is possible repeat the test by pressing the button on the back of front panel
display board for more than 2,5 seconds.
-
A microcontroller system controls various possible anomalies and gives a FAILURE indication in the following
conditions:
1. Output Fuses or Battery fuse interruptions
2. Overloaded Battery (> 28,3 V )
3. Low Battery Voltage (< 20,8 V )
4. Mains power supply absence and no battery charge
5. Disconnected Battery
6. Internal battery resistance >1 Ω
Failures are displayed on a frontal board; the detailed failure is showed on the internal power supply board.

MA-AL-T500-01-07 Manual TUL500EN eng rev7 Page 2 of 8
In order to avoid that a possible failure in the regulator damages the charges or the battery, a protection
circuit has been inserted against over-Voltages, made of a SCR and a fuse. A fuse for mains alternated
supplying is also present.
In case of failure in the power supply or of mains missing, the logic and control circuits are supplied by
batteries.
Tab 1
MECHANICALSPECIFICATIONS
Size in mm.
width 310; height 373; depth 170
Weight
5,6 Kg
ENVIRONMENTAL SPECIFICATIONS
Operating temperature
from -5°C to +40°C
Humidity
from 5% to 93% ± 2 %
cooling
air cooling
IP
30
Environmental class and Installation site
3K5 of EN 60721-3-3:1995 (Indoor use: sheltered from
atmospheric agents. Control of temperature and humidity is not
required)
Tab 2
FUSES
FUSE1
Fuse of the 230 Vac supplying input (T4 AL
250V~).
Not Replaceable
F
4
Electronic Fuse related to output B (2,5 A self
resetting)
F1
Battery fuse (T6,3 AL 250 V~)
F
3
Electronic Fuse related to output C (2,5 A self
resetting)
F2
Electronic Fuse related to output A (2,5 A self
resetting)
Tab 3
ELECTRICAL SPECIFICATIONS
Functional class EN 12101-10:2007
A ( Suitable to be use in EFC systems)
Mains Supplying Voltage
230 V~ (alternate current) +10% / -15%
Ac mains frequency
50 Hz sinusoidal
Current consumption by mains
1,1 A max. (full load)
Output Voltage
27,6 V (direct current) (20V ÷ 30V )
Minimum output Voltage
20 V at max charge, with mains absence and
battery discharged
Switching-off threshold Voltage
20 V
Output current max
5 A max.(see fig. 4)
Max current for battery recharge
1 A
Max current for charges (Imax.a) with battery recharging
4 A
Max current for charges without battery recharging (Imax.b)
5 A
Max current for any output
2 A
Max current with 2 output in parallel
4 A
Max current with 3 output in parallel
4 A (7 A peak for 25 seconds @ 25°C)
Max total peak current for the outputs
7 A peak for 25 seconds @ 25°C
Minimum current for charges (I min)
0 A
Regulations towards mains variations at full charge (+10% / -
15%)
Better than 1%
Regulations towards charge variations (0 to 100%)
Better than 1%
Ripple at full charge
1 Vpp ( at 195,5 V~ ) 30mVpp ( at 253 V~ )
Compensation of output Voltage according to temperature
4 mV/ K
Protection against battery polarity inversion
Diode
Interruption time
None
Batteries max capacity
17Ah
Recommended batteries: 2 x 12 V in series, 17 Ah,
hermetic with valve and according to regulations IEC 61056-1
e IEC 61056-2. Casing with inflammability class UL-94-V2 or
better
Type:YUASA NP 17-12 or equivalent.
Max current without mains supply
5 A
Alarm threshold of battery internal resistance
1 Ω
Missing mains and failure output relay –dry contacts
25 V~ or 60 V 1 A MAX
Terminals and cables
Mains supply : Ф1,50÷2,0mm
Outputs : Ф1,50÷2,0mm
Battery terminal BATT: Size M6 Crimp 0,5-2,0
Battery cables BATT: Ф1,5mm
ATTENTION, READ THE
DOCUMENTATION
ATTENTION, RISK OF
ELECTRICAL SHOCK

MA-AL-T500-01-07 Manual TUL500EN eng rev7 Page 3 of 8
Recommended types and sections of installation cables (certified EN50200)
Mains supply 230 V~ L-N-PE
FTG10OM1 0,6/1 kV: 3 x 1,5 mm2÷2,0 mm2
A, B, C output terminals
FRHRRNS 2150: 2 x 1,5 mm2÷2,0 mm2
Indication inputs/outputs
FRHRRNS 2050: 2 x 0,5 mm2÷1,5 mm2
Tab 4
The power supply has been certified using YUASA NP 17-12 batteries
SECURITY INSTRUCTIONS
1. For mains input and DC outputs + alarms, use separate holes on the bottom of the box to pass the
cables. Furthermore, the material of the joint pipe/box must have a flammability class V-1 or better
2. The relay contact “GUASTO” and “RETE” must be connected only to circuits operating with SELV
Voltage.
3. For AC supplying, provide an omnipolar switch of the power supply network compliant with Annex L.
of IEC 62368-1 (separation between the contacts of at least 3 mm), easily accessible.
4. The wires must have a section of 1,5 mm and be equipped with adequate buttonholes where they are
subject to pressure contact.
5. The installation of the power supply must be carried out by qualified personnel aware of the security
standard IEC 62368-1 and concerning power supplies CEI-64-8.
INSTALLATION
Mechanical mounting
This device has to be mounted on vertical stable walls, suitable to support the power supply, by means of 4
screws with 8 mm diameter, for spacers and screws on the 4 holes on the bottom of the box. The battery
must be fixed using the strap given within.
Electrical connection
Connect the power supply unit to the mains 230 V~ by use of an omnipolar switch of the power supply
network compliant with Annex L. of IEC 62368-1 (separation between the contacts of at least 3 mm), easily
accessible, aimed to protect the line against possible short circuit and operator against current leakage.
IMPORTANT: use different cables-passes and pipes for ac supplying input (mains 230 V~) and dc
outputs + alarms (SELV) –see Pict.2
The minimum section recommended for ground connection is 1,5 mm2.
For connections refer to Pict. 2. In this figure the following important details are shown:
Output Terminals (Power supply unit)
Output terminal board (power supply)
BATT +
Positive pole of the battery
B +
Positive output for charge B
BATT -
Negative pole of the battery
B -
Negative output for charge B
A +
Positive output for charge A
C +
Positive output for charge C
A -
Negative output for charge A
C -
Negative output for charge C
Tab 4
Terminal board Alternated Supplying
L connection to mains line (230 V~)
Protection ground connection
N connection to neutral
Checks and Adjustments
Control is shown below (VRES1) is adjusted at factory and must not be altered by the operator.
Tampering of this control automatically means the lost of the warranty.
VRES1 - Potentiometer for adjustment of the output Voltage

MA-AL-T500-01-07 Manual TUL500EN eng rev7 Page 4 of 8
Low battery: Battery voltage lower than 20,8 V
Battery fuse fault (if flashing)
Battery ok: Voltage between 20,9 V and 28 V
Overcharged battery: Battery voltage over 28 V
Battery resistance high >1 Ω (if flashing)
Mains: Presence of 230 V~mains
Failure : LED of general failure, it is activated in
case of:
Absence of 230 V~mains
Faulty fuse
Loss of battery charge
Low battery
Overcharged battery
Disconnected battery
Battery resistance > 1 Ω
INDICATION ON THE FRONT PANEL (located on the door of the power supply):
Standard visualization
Alternate visualization
Pushing SW2 (Pict. 3) on the display board for less than 2 seconds, the Amperometer function is activated.
The five LEDs bar show, from left to right, the current level supplied to the charges; 1 A for every leds. When
the Switch button is pushed again, or after 1 minute, the display go back to the standard visualization.
CONNECTION OF CONTROL BOARD (placed near the power board)
Refer to Pict.2
Relay “RETE” of mains missing, – Terminals NC, NO, C (operating with SELV Voltages)
Relay output with intervention for missing mains and programmable activation delay
DIP-SWITCH
Delay
EN54-4
Compliant
1
2
3
OFF
OFF
OFF
25 min
YES (Factory
default)
OFF
OFF
ON
15 sec
YES
OFF
ON
OFF
60 sec
YES
OFF
ON
ON
5 min
YES
ON
OFF
OFF
15 min
YES
ON
OFF
ON
60 min
NO
ON
ON
OFF
120 min
NO
ON
ON
ON
240 min
NO
Tab 5
In order to be compliant to the EN54-4 standards, the maximum delay permitted is 30 MINUTES of
missing mains. On the contrary the power supply is not compliant to the standards.
Ten seconds after the mains is restored the relays goes back to normal condition.
Relay “GUASTO” of failure indication – Terminals NC, NO, C (operating with SELV Voltages)
Output relay failure indication is active for:
Low battery (voltage lower than 20,8 V )
Overcharged battery (voltage over 28,3 V )
Disconnected battery
Battery internal resistance > 1 Ω
Faulty fuse
START UP OF THE SYSTEM
Even if not imperative, the following sequence of connection is suggested:
1. Connect mains and ground to the concerned terminal AC1. Turn ON the AC power. The load LEDs
flash and after about 20 seconds the missed battery LED flashes
2. Connect the battery. After 20 seconds the LED switches off
3. Connect the loads: the LEDs, indicating the current supplied, light up
Pict.1
Battery low
or Battery fuse
fault
(if flashing)
Battery OK
Battery
Overcharged
or Battery
resistance
high
(if flashing)
Mains
Failure

MA-AL-T500-01-07 Manual TUL500EN eng rev7 Page 5 of 8
SYSTEM RUNNING
Battery voltage is monitored continuously, if the voltage drops below V(B)low = 20,8 V , the relay
“GUASTO” turns on and the Front panel “Battery Low” lights on.
If the voltage drops below V(B)min = 19,8 V , the battery is isolated to avoid the deep
discharge. After the battery gets unplugged, the battery will be connected to the system if the
voltage is higher than 16 V .
Battery internal resistance is tested every 2,5 hours, at least. If the resistance is higher than 1 Ohm a warning
in raised. The Front Panel LED “Failure” is lighted on, the LED “Overcharged battery”
slow flashes and the internal DL1 quick flashes.
Battery Fuse monitoring, in case of fault of the fuse, the LED “Low battery” starts to flash slowly. When the
fuse is replaced the signal disappear.
Fuses monitoring, if a fuse became open the LED lights on, when the cause of fault disappears the LED
lights off.
Mains monitoring, when the mains is missed, The Front Panel LED “Mains” is lighted off, and the relay
“RETE” is activated. When the mains return LED “Mains” is lighted on, and the relay “RETE”
is restored.
SERVICING
Periodical programmed servicing must be carried out by qualified personnel in order to prevent the possibility
of a malfunctioning of the power supply. It is recommended to carry out servicing every 6 months and to
evaluate control panel of the system in order to check possible alarms during tests.
- Check the connections of the 230 V~ supplying lines
- Check the connections of the alarm indication lines and related shields
- Check the battery connections, they have to be well tightened and there must be no oxidation
- Check the output Voltage on the charge (see electrical specifications)
Although the power supply is equipped with a self-diagnosis system carrying out a periodical control of the
battery and indicating possible failures, it is suggested to manually check the battery every six months.
- Disconnect the battery and check if the voltage of the power supply is within the values shown.
- After re-connecting the battery, disconnect the primary supplying and check if the battery can
maintain the Voltage on the higher 23 V charge. On the contrary, replace battery immediately.
- Check presence of related alarms during tests.
CONTROL BOARD SYNOPTIC LEDs
The DL1 LED shows the failures:
In case of contemporary presence of more alarms, the LED indication follows the priority shown in the tab. 6
Priority
DL1
ALARM
1
Slow flashing (1 Hz)
Battery disconnected
2
Quick flashing (4 Hz)
Battery resistance > 1 ohm
3
On fix
Fuse F1 (battery) interrupted
4
Off
None of previous failures
LEDs DL2, DL3, DL4 and DL5 show the current used by the outputs:
Condition
LED Status
DL5
DL4
DL3
DL2
I < 0,3 A
OFF
OFF
OFF
OFF
I < 0,625 A
SLOW FLASH
OFF
OFF
OFF
0,625 A < I < 1,25 A
ON
OFF
OFF
OFF
1,25 A < I < 1,875 A
ON
SLOW FLASH
OFF
OFF
1,875 A < I < 2,5 A
ON
ON
OFF
OFF
2,5 A < I < 3,125 A
ON
ON
SLOW FLASH
OFF
3,125 A < I < 3,75 A
ON
ON
ON
OFF
3,75 A < I < 4,375 A
ON
ON
ON
SLOW FLASH
4,375 A < I < 5 A
ON
ON
ON
ON
OVERLOAD I > 5 A
SLOW FLASH
SLOW FLASH
SLOW FLASH
SLOW FLASH
Note: SLOW FLASH = 1 Hz
Tab 6
Tab 7

MA-AL-T500-01-07 Manual TUL500EN eng rev7 Page 6 of 8
CABLE CONNECTION:
+ - BATT: connect to the backup battery.
+ - A: connect to the load. MAX 2 A
+ - B: connect to the load. MAX 2 A
+ - C: connect to the load. MAX 2 A
MANUFACTURER DECLARATIONS
Statement of the Manufacturer:
The design has been developed according to the internal quality system observing all the rules aimed to
reach an adequate design of all the elements of the product.
All components of the product have been selected for the expected purposes and their characteristics are
assured when the external environmental conditions correspond to the conditions required by class 3K5 of
EN 60721-3-3:1995
Pict.3
FUSE1 –Fuse of
the 230 V~ mains,
not replaceable
F1 –Battery Fuse
DL2, DL3,
DL4, DL5:
Loads
Current
level
LED1:
Mains presence
DL1, DL6,
DL7, DL8:
lights off =
Electronic
fuses
operating
Pict.2
Fig.3
When pushed
Amperometer function
activated for 1 minute
(SW2)
Missing
Mains Delay
Connect to mains Line (230 V~)
To the
battery
To the
loads
To the
remote
signalling
Do not
connect

MA-AL-T500-01-07 Manual TUL500EN eng rev7 Page 7 of 8
DoP available on site www.venitem.com
1293
Venitem s.r.l. Via del Lavoro, 10 - 30030 Salzano (VE)
18
DoP N° 1293 - CPR - 0587
EN54-4 ; EN12101-10
TUL500EN - Power supply unit for fire detection, fire alarm systems, smoke and heat control systems for
building
Other technical data: see supplier’s technical dossier
EN54-4 Essential characteristics
Performance
Operation reliability
Pass
Performance of power supply
Pass
Durability of operational reliability and response delay, temperature
resistance
Pass
Durability of operational reliability and response delay, vibration resistance
Pass
Durability of operational reliability and response delay, electrical stability
Pass
Durability of operational reliability and response delay, humidity resistance
Pass
EN 12101-10
Functional class PN-EN 12101-10:2007
A
Environmental class PN-EN 12101-10:2007
1
Interruption time
0 s
Batteries max capacity
17 Ah
Max current for charges without battery recharging (Imax.b)
5 A
Mains Supplying Voltage
230 V~ +10% / -15%
Output voltage
27,6 V (20 V ÷ 30 V )
Wasting
This product must be wasted in appropriate
wheelie-bin for electric and electronic materials.
Do not put in wheelie-bin for other kind of
waste.

MA-AL-T500-01-07 Manual TUL500EN eng rev7 Page 8 of 8
NOTE
Via del Lavoro, 10 - 30030 Salzano (VE)
Tel. (+39) 041 5740374 –Fax (+39) 041 5740388
Table of contents
Other Venitem Power Supply manuals