Venmar 500VF User manual

INSTALLATION AND USER GUIDE
FOR RESIDENTIAL USE ONLY
REGISTER YOUR PRODUCT ONLINE AT: WWW.VENMAR.CA
30042507B
!
AB0039
CENTRAL VACUUM POWER UNITS
!
MODELS SFDB-DK, SFDB-DL AND SFDB-DM
VENMAR VENTILATION ULC; DRUMMONDVILLE, QUÉBEC WWW.VENMAR.CA 1-888-882-7626
500VF / 600VF / 650VF

2
SAVE THESE INSTRUCTIONS
READ ALL INSTRUCTIONS BEFORE USING THIS APPLIANCE
IMPORTANT SAFETY INSTRUCTIONS
When using an electrical appliance, basic precautions should always be followed, including the following:
GENERAL INFORMATION . . . . . . . . . 3
TOOL LISTING . . . . . . . . . . . . . . . . . . . . .3
WORKING WITH PLASTIC TUBING. . . . . . . . . . . . . 3
WALL INLET INSTALLATION . . . . . . . . 3
V600W VACUSWEEP®
INLET VALVE INSTALLATION . . . . . . 4-6
CONNECTION FROM BELOW . . . . . . . . . . . . . . .4
CONNECTION FROM BEHIND . . . . . . . . . . . . . . .5
CONNECTION IN AWALL . . . . . . . . . . . . . . . .6
POWER UNIT INSTALLATION . . . . . . 7-9
LOCATING THE POWER UNIT . . . . . . . . . . . . . .7
CHANGING INTAKE LINE DIRECTION . . . . . . . . . . .7
MOUNTING THE POWER UNIT . . . . . . . . . . . . . .8
FITTING MAIN LINE TO POWER UNIT . . . . . . . . . . .9
GROUNDING INSTRUCTIONS . . . . . . . 9
WIRING . . . . . . . . . . . . . . . . . . . . . . . .9
OPERATION AND MAINTENANCE . . .10-11
WHEN TO CHANGE BAG OR EMPTY DEBRIS PAIL . . . . 10
HOW TO EMPTY DEBRIS PAIL
(600VF AND 650VF POWER UNITS ONLY). . . . . . . 10
DISPOSABLE BAG REPLACEMENT
(500VF POWER UNIT ONLY) . . . . . . . . . . . . . 10
PERMANENT FILTER
(600VF AND 650VF POWER UNITS ONLY). . . . . . . 10
REMOVAL AND INSTALLATION OF PERMANENT FILTER
(600VF AND 650VF POWER UNITS ONLY). . . . . . . 10
REMOVAL AND INSTALLATION OF HEPA FILTER
(650VF POWER UNIT ONLY) . . . . . . . . . . . . . 11
MOTOR FOAM FILTER (ALL UNITS) . . . . . . . . . . . 11
TROUBLESHOOTING GUIDE. . . . . . . 12
SERVICE PARTS . . . . . . . . . . . . . 13
WARRANTY . . . . . . . . . . . . . . . . 14
TABLE OF CONTENTS
WARNING
To reduce the risk of fire, electric shock or injury:
1. Do not use on wet surfaces or outdoors.
2. Do not vacuum liquids or fine powders (such as drywall dust).
3. Do not use to pick up flammable or combustible liquids such
as gasoline or use in areas where they may be present.
4. Do not pick up anything that is burning or smoking, such as
cigarettes, matches, or hot ashes.
5. Do not allow to be used as a toy.Close attention is necessary
when used by or near children.
6. Use only as described in this manual. Use only
manufacturer's recommended attachments.
7. Keep hair, loose clothing, fingers and all parts of body away
from openings and moving parts.
8. Turn off all controls before unplugging.
9. Use extra care when cleaning on stairs.
10. Do not handle plug or appliance with wet hands.
11. Do not use with damaged cord or plug. If appliance is not
working as it should, if it has been dropped, damaged,
left outdoors, or dropped into water, return it to a Service
Center.
12.Keep your work area well lighted.
13.Connect to a properly grounded outlet only. See grounding
instructions shown on page 9.
14.When performing installation, servicing or cleaning the unit,
it is recommended to wear safety glasses and gloves.
15.When applicable local regulations comprise more
restrictive installation and/or certification requirements,
the aforementioned requirements prevail on those of this
document and the installer agrees to conform to these at
his own expenses.
CAUTION
1. Do not put any object into openings. Do not use with any
opening blocked; keep free of dust, lint, hair and anything
that may reduce air flow.
2. Ensure air flows freely and exhausts unobstructed from top
or side outlet.
3. Do not use without filter (or filters, according to the model)
in place.
4. Do not use to blow leaves or debris.
5. Do not place any object on top of the unit.
6. Do not install the unit horizontally.
7. Do not use the pail as a wash bucket.
8. Do not use the pail as a stool.
9. Avoid picking up sharp objects.
10. This appliance is for use on a standard 120 VAC, dedicated
15-amp branch circuit.
11. Do not unplug the unit by pulling on cord. To unplug, grasp
the plug, not the cord.
12.Store your vacuum cleaner indoors in a clean, dry area, and
away from extreme temperatures.
13.Any servicing other than that recommended in this manual
should be performed by an authorized service facility.
14.We recommend that your unit be inspected by a specialized
technician once a year.
!

3
TOOL LISTING
Depending on the installation, the use of the following tools
may be required:
Wire strippers, 1/4’’ and 1/2” drill bits, utility knife, putty knife,
2½’’ hole saw, keyhole saw, hammer, cold chisel, level,
flashlight, drill, electrical tape, Phillips no. 2 screwdriver,
wrench, hacksaw, tape measure, safety glasses.
Power tools are recommended to make the installation proceed
quickly. A mask and gloves should be worn when cutting
ducting and using glue.
WORKING WITH PLASTIC TUBING
CUTTING TUBING
Measure the length of tube needed. Allow 5/8” of tubing for
inserting into fittings and 1½” for placing into flexible tubing.
Cut the plastic tubing with a hacksaw, ensuring that the cut
is exactly square. Use wire cutters or tin snips to cut flexible
tubing, 8” lengths of flexible tubing should not be cut.
Use a small knife or steel wool to remove any burrs from the
inside of the tube.
Use a file to slightly bevel the outside of the tube so that it will
easily slide into the fitting. Use steel wool or a light grained
sandpaper to buff the surface of the tube which will be glued.
MAKING A JOINT
Insert the tube into the fitting,
aligning both parts as they will be
installed. Mark the tube and the
fitting to quickly realign the joint.
Apply cement in an inch-wide
band to the outside of the tube.
Insert the tube into the fitting with
the alignment marks a quarter
turn apart, and then quickly push
and turn the fitting to align the
marks and spread the cement.
Allow 1 minute for the joint to dry.
CEMENTING FLEXIBLE
TUBING
Ensure the ends of the flexible tubing are even. When joining
flexible tubing to plastic tubing or to an inlet mounting plate,
apply cement to both the inside of the flexible tubing and the
outside of the plastic tubing or mounting plate tubing ring.Twist
both pieces while joining them to evenly spread the glue. Allow
5 minutes for the cement to set in flexible tubing.
SECURE WIRE TO
TUBING
The low-voltage power wiring is
run along with the tubing. Use
electrical tape to secure the
wire to the tubing. Tape the wire
approximately every 12" to 18".
MAKING THE WALL INLET CUTOUT
The wall inlet should be located 18” on-center from the floor
and directly in line with the attic or basement inlet tubing hole
previously drilled in the wall plate or header. The wall inlet
cutout must be exactly 378” high by 278” wide.
ATTACHING THE INLET MOUNTING PLATE
(V144)
Reach through the inlet hole and locate the inlet tubing. Pull
the flexible tubing through the inlet hole and remove the
low-voltage wiring from inside the tube.
Remove the nail flange
from the inlet mounting
plate (see illustration at
right). Apply cement to
both the inside of the
flexible tubing and to the
outside of the mounting
plate’s tube ring. Insert
the mounting plate’s
tube ring in the flexible
tubing and twisting the
pieces as you join them
to spread the cement, and align the mounting plate in a vertical
position.
Now, strip the ends of the two low-voltage wires, and then
connect the wires to the screw terminals on the back of the
inlet cover. When the wiring is complete, assemble the inlet
cover to the tube guard and mounting plate.
COMPLETING
THE INLET
ASSEMBLY
Once you have attached
the mounting plate to the
flexible tubing, pull the
low-voltage wire through
the top wiring hole in the
mounting plate.
INSTALLING
THE INLET (V111)
Place the inlet into the
wall cutout (the inlet
cover remains on the
outside). Hold the inlet
in place and gradually
tighten down each screw
a little bit at a time.
GENERAL INFORMATION WALL INLET INSTALLATION
AO0010
AO0011
INLET MOUNTING
PLATE
AE0024A
AO0045
AR0040

4
CONNECTION
FROM BELOW
Measure distance (X) between the kickplate
face and the inside edge of the cabinet.
Then add 2¾” to the measured distance.
Refer to figure . Measure out the new
distance (X + 2¾”) from the cabinet door, to
the reference mark.
Drill a small reference hole straight down
through to the basement. Refer to figure .
Locate the reference hole in the basement
and verify that there are no obstructions
within 2” of either side and 4” behind.
Cut a 2½” diameter hole from the basement
up into the base of the counter using the
reference hole as a center. Refer to figure .
Using the reference hole as a center, cut a
2 ³/8” H x 6 5/8” W rough opening in the
kickplate face. Refer to figure .
Glue the long socket of the tight elbow
(part no. V382XS) onto a section of 2”
central vacuum tube. Make the terminal
connections to the V600W VacuSweep inlet
valve by sliding the low-voltage wire into
wire clips.Turn the power to the vacuum unit
ON to test the connection. After successful
completion of the test, turn power to the
vacuum unit OFF. Wrap a piece of wire/
string around the pipe. Using the wire/string
to temporarily hold the pipe and elbow in
place, insert the V600W VacuSweep inlet
valve into the cabinet base and elbow. DO
NOT GLUE this connection (Designed for
friction fit). Refer to figure .
Remove the wire/string. With the door
in an open position, secure the V600W
VacuSweep inlet valve to the cabinet base
using no. 6 screws. Refer to figure .
Ensure that the spring on the electrical
connector has 1/8” clearance to rough
opening. Continue with remainder of
central vacuum connections.
V600W VACUSWEEP® INLET VALVE INSTALLATION
AD0045A
CABINET
KICKPLATE
CABINET
CABINET
DOOR REFERENCE
MARK
2¾”X
SUBFLOOR
JOIST
REFERENCE HOLE
SEEN FROM BASEMENT
JOIST
2½” DIA
REFERENCE
HOLE
GLUE THIS
CONNECTION
(LONG SOCKET/PIPE)
WIRE/STRING
2” CENTRAL VAC PIPE
TERMINAL CONNECTIONS
ELBOW
GLUE THIS
CONNECTION
2” CENTRAL VAC PIPE
TERMINAL WIRES
(X) + (2¾”)
REFERENCE
MARK
SUBFLOOR
DRILL 2½” DIA HOLE
USING THE REFERENCE HOLE
AS CENTER
CABINET
DOOR
JOIST
2½” DIA HOLE
CUT A2/8” H X65/8” W
ROUGH OPENING USING THE
REFERENCE HOLE AS CENTER
DONOT GLUE THIS
CONNECTION
SHORT SOCKET
END OF ELBOW
VACUSWEEP®
INLET VALVE
VACUSWEEP®
INLET VALVE
2 XNO. 6
SCREWS
DONOT GLUE
THIS CONNECTION

5
CONNECTION FROM BEHIND
Choose a location under the cabinet for the V600W
VacuSweep inlet valve so that it can be connected
to the central vacuum tube. Measure distance (X)
between the kickplate face and the inside edge
of the cabinet. Then, add 2¾” to the measured
distance. Refer to figure . Measure out the new
distance (X + 2¾”) from the cabinet door, to the
reference mark.
Drill a small reference hole straight down through
to the basement. Refer to figure . Locate the
reference hole in the basement and verify that there
are no obstructions.
Using a reciprocating saw, cut an access hole in the
floor under the cabinet and approximately 8” behind
the location of the V600W VacuSweep inlet valve
reference hole so that the V600W VacuSweep inlet
valve can be connected to vacuum tube by reaching
through the access hole. Refer to figure .
Using the reference hole as a center, cut a
2 ³/8” H x 6 5/8” W rough opening in the kickplate
face. Refer to figure .
Insert a coupling (part no.V127) onto the rear of the
housing. DO NOT GLUE this connection (Designed
for friction fit). Refer to figure . Make the terminal
connections to the V600W VacuSweep inlet valve by
sliding the low-voltage wire into wire clips. Turn the
power to the vacuum unit ON to test the connection.
After successful completion of the test, turn power to
the vacuum unit OFF. Insert the V600W VacuSweep
inlet valve into the cabinet base and tube.
With the door in an open position, secure the V600W
VacuSweep inlet valve to the cabinet base using
no. 6 screws. Refer to figure . Ensure that the
spring on the electrical connector has 1/8”
clearance to rough opening. From the basement
reach through the access hole and glue a section
of 2” central vacuum tube to the coupling. Continue
with remainder of central vacuum connections.
V600W VACUSWEEP® INLET VALVE INSTALLATION (CONT'D)
AD0046A
CABINET
KICKPLATE
CABINET
CABINET
DOOR REFERENCE
MARK
2¾”
X
SUBFLOOR
JOIST
JOIST
(X) + (2¾”)
REFERENCE
MARK
SUBFLOOR
REFERENCE HOLE
SEEN FROM BASEMENT
CABINET
DOOR
REFERENCE
HOLE
8” CUT 8” ACCESS
HOLE BEHIND
REFERENCE HOLE
8” ACCESS HOLE
JOIST CUT A2/8” H X65/8” W
ROUGH OPENING USING THE
REFERENCE HOLE AS CENTER
2” CENTRAL
VAC PIPE
COUPLING
DONOT GLUE
THIS CONNECTION
VACUSWEEP®
INLET VALVE
GLUE THIS
CONNECTION
(COUPLING/PIPE)
TERMINAL CONNECTIONS
VACUSWEEP®
INLET VALVE
2 XNO. 6
SCREWS
DONOT GLUE
THIS CONNECTION
8”
ACCESS
HOLE
TERMINAL
WIRES
GLUE THIS
CONNECTION
COUPLING 2” CENTRAL
VAC PIPE

6
V600W VACUSWEEP® INLET VALVE INSTALLATION (CONT'D)
CONNECTION IN A WALL
Remove the baseboard and locate studs in
the wall where V600W VacuSweep inlet valve
will be installed. Locate a position where the
inlet will be clear of vertical studs and have
free access either up or down dependent on
location of central vacuum connection to the
rest of the system. Refer to figure .
Holding the drill at a 45° angle and as close to
the wall as possible, between located studs,
drill a small reference hole through the floor
and subfloor. Locate this reference hole from
beneath and measure over approximately
1 7/8” to center of base plate of wall. Ensure
you have 1½” clearance from any obstacles if
connecting from below. Refer to figure .
If installation is from below use a 2½” diameter
hole saw to remove wood floor and base plate,
sufficient to locate V600W VacuSweep inlet
valve centered over the reference hole. Refer
to figure .
Using the reference hole as a center, cut a
2 ³/8” H x 6 5/8” W rough opening in the wall
and baseboard. Refer to figure .
Glue the long socket of the tight elbow (part
no.V382XS) ontoa section of 2”centralvacuum
tube. Make the terminal connections to the
V600W VacuSweep inlet valve by sliding the
low-voltage wire into wire clips.Turn the power
to the vacuum unit ON to test the connection.
After successful completion of the test, turn
power to the vacuum unit OFF. Wrap a piece of
wire/string around the tubing. Using the wire/
string to temporarily hold the pipe and elbow
in place, insert the V600W VacuSweep inlet
valve into the opening at the base of the wall
and elbow. DO NOT GLUE this connection
(Designed for friction fit). Refer to figure .
Remove the wire/string. With the door in an
open position, secure the V600W VacuSweep
inlet valve to the wall using no. 6 screws. Refer
to figure . Ensure that the spring on the
electrical connector has 1/8” clearance to
rough opening. Continue with remainder of
central vacuum connections.
REMOVE
BASEBOARD STUD STUD
STUD
POSITION
BETWEEN STUDS
REFERENCE HOLE AS CENTER
HOLE TO
BASEMENT REFERENCE HOLE
AS CENTER
CUT A
2/8” H X65/8” W
ROUGH OPENING
AD0047A
DONOT GLUE
THIS CONNECTION
SHORT SOCKET
END OF ELBOW
GLUE THIS
CONNECTION
(LONG
SOCKET/PIPE)
2” CENTRAL
VAC PIPE
VACUSWEEP®
INLET VALVE
VACUSWEEP®
INLET VALVE
2 XNO. 6 SCREWS
2” CENTRAL VAC PIPE TERMINAL
WIRES
GLUE THIS
CONNECTION
ELBOW
TERMINAL
CONNECTIONS
WIRE/STRING

7
LOCATING THE POWER UNIT
• Locate the power unit away from the general living area in
an accessible location for cleaning and maintenance.
• Locatethepowerunitwithin6feetofagroundedelectricaloutlet.
The power unit requires a 120 VAC power source, dedicated
15-amp branch circuit.
• Do not locate the power unit close to a source of extreme
heat (i.e.: water heater) or in an area with a high ambient
temperature (i.e.: attic, furnace room).
• If the power unit is located in a closet or a small utility
room, make sure the area is well-ventilated (e.g.: with door
louvers).
CHANGING INTAKE LINE DIRECTION
The intake line connects to the right side of the unit. However,
it is possible to change this configuration; to connect the intake
line to the left side of the unit, follow these steps:
Remove debris pail from power unit by releasing both latches
on sides of the unit, pulling them out and then pushing up.
Detach the pail from unit.
500VF only: Grasp
the edges of the bag
collar and pull down;
the bag will slide off
easily. Do not pull on
the bag. Set aside the
bag.
500VF only: Using a
Phillips screwdriver
no. 2, remove the
screw tightening the
bag adapter and
intake elbow junction.
Disassemble the
bag adapter from the
intake elbow and set
aside with its screw
and nut.
Allunits:Disassemble
the intake elbow from
the back of the unit
using a 3/8” socket
to remove its both
retaining nuts and
screws.
All units: Flip the
intake elbow 180°,
then reassemble it to
the unit, taking care to
keep its gasket at its
original position.
NOTE: Ensure the
gasket is not folded in
order to prevent lack of suction and noise.
500VF only:
Reassemble the bag
adapter to the intake
elbow. Align triangle
with small inclined
stud, then tighten
the junction using
the screw and nut
previously removed in
.
500VF only: Put back
in place the bag by
grasping the edges of
its collar and insert
over bag adapter. Be
careful not to tear the
bag. Ensure the collar
is positioned between
the taper ring and the
bag stopper on the
bag adapter.
All units: Put the pail back in its place.
POWER UNIT INSTALLATION
AD0076
AO0078
500VF ONLY
AD0075
500VF ONLY
AD0077
AD0078
500VF ONLY
AO0080
500VF ONLY TAPER RING
BAG STOPPER
WARNING
!
Do not install outdoors. Before being hung, rest the
unit on a leveled surface to prevent the unit to fall
down. When performing installation, servicing or
cleaning the unit, it is recommended to wear safety
glasses and gloves.

8
MOUNTING THE POWER UNIT
Carefully remove debris pail from power unit. Make sure bag
is properly installed in power unit (500VF unit only). Remove
the installation kit and securely reinstall debris pail.
Refer to illustration below to maintain minimum walls and
floor clearance dimensions.
Position and install the wall mounting bracket with the
provided screws. Refer to illustration in the right column for
proper mounting dimensions.
Use the provided mounting screws to secure the mounting
bracket on the wall through upper and lower mounting
holes.
Hang power unit onto wall mounting bracket. Ensure
the back brackets of the power unit are engaged with
corresponding wall bracket fingers (or top fingers and lower
tab for 500VF model; see figure below). Pull the power unit
down to secure.
POWER UNIT INSTALLATION (CONT'D)
C
L
3/4” TYP.
32 7/8”
1” TYP.
45¼”
MIN.
HEIGHT
18 ¹/8”18 ¹/8”
UPPER
MOUNTING
HOLES
LOWER
MOUNTING
HOLES
AD0079A
CAUTION
Ensure to screw the wall mounting bracket directly
to a wall stud for a solid installation.
18” minimum
above floor
12” minimum
from ceiling
12”
minimum
TOP VIEW
FRONT VIEW
MINIMUM CLEARANCE DIMENSIONS
12”
minimum
AD0039A
AD0074
600VF AND 650VF
500VF

9
FITTING MAIN LINE TO POWER UNIT
Run house vacuum line up to the elbow behind the power
unit. Insert the end of the line in the elbow opening and
secure house vacuum line by hand tightening the screw
and nut provided (see illustration below) DO NOT GLUE.
Assemble exhaust tubing to exhaust outlet on top or top
side of the unit, according to the power unit model. DO NOT
GLUE.
NOTE FOR 650VF UNIT ONLY
If desired, the
coupling or elbow
used to connect
the exhaust line to
the top of the unit
may be secured
using two 5/8”
included screws.
See illustration at
right.
NOTE: Using flexible tubing will ease future top cap removal.
Make sure all tubing connections are air tight.
The exhaust should not be vented into a wall, ceiling or
concealed space in the house. It is recommended to vent
the vacuum exhaust air to the outdoors. Exterior vented
exhaust line should end using Model V145 wall cap.
NOTE: For optimal indoor air quality, exhausting the power
unit to the outdoors is recommended but is not
required, especially for 650VF unit which is equipped
with an exhaust HEPA filter.
Grounding Instructions – This appliance must be grounded.
If it should malfunction or break down, grounding provides a
path of least resistance for electric current, to reduce the risk
of electric shock.This appliance is equipped with a cord having
an equipment-grounding conductor and grounding plug. The
plug must be plugged into an appropriate outlet that is properly
installed and grounded in accordance with all local codes and
ordinances.
WIRING
This appliance is for use on a standard 120 VAC, dedicated
15-amp branch circuit with a NEMA 5-15R receptacle. Make
sure that the power unit is connected to an outlet and has a
grounding attachment plug that looks like the plug shown in
illustration below. No adapter should be used with this power
unit.
NOTE: Inlet leads to be connected to power unit low voltage
tabs using crimp connectors (included in parts bag)
and low voltage harness.
POWER UNIT INSTALLATION
(CONT'D)GROUNDING
INSTRUCTIONS
AJ0001
INTAKE LINE
SCREW AND
NUT FROM
PARTS BAG
INTAKE LINE TYPICAL CONNECTION
TO POWER UNIT
WARNING
!
Improper connection of the equipment-grounding
conductor can result in a risk of electric shock.
Check with a qualified electrician or service person
if you are in doubt as to whether the outlet is
properly grounded. Do not modify the plug provided
with the appliance – if it will not fit the outlet, have
a proper outlet installed by a qualified electrician.
AJ0003
AE0044 INLET
CRIMP
CONNECTORS TO
BE CONNECTED
IN LOW VOLTAGE
TABS
INLET INLET
TO
OTHER
INLETS
MODEL V133 (22/2)
LOW VOLTAGE WIRE
INLET LEADS
GROUNDED OUTLETS
GROUNDING PIN

10
Open the wall inlet cover and insert the end of the hose into the
inlet to turn on the vacuum.
For non-switched hoses, inserting the hose automatically turns
on the power unit; removing the hose shuts off the power unit.
Some hoses have switches which can be used to activate
power unit. The ON/OFF switch located on the power unit
needs to be kept in the OFF position.
As you vacuum, dirt and dust are carried to the power unit
where they remain in a bag or in the debris pail (according to
the power unit model).
Use the cleaning tools as you would for any other vacuum
cleaner. Avoid picking up very large debris or lengthy as these
kinds of objects may become lodged in the hose or tubing.
WHEN TO CHANGE BAG* OR EMPTY
DEBRIS PAIL
With a 6 U.S. gallons (22.7 liters) capacity, under normal
conditions the bag/debris pail requires changing/emptying
approximately twice a year. If the bag/debris pail is full, you will
notice a reduced suction from the system. Unless this loss of
suction is caused by a blockage in the system, changing the
bag or emptying the debris pail will solve the problem.
NOTE: Even if not filled to capacity, if the bag seems tightly
stretched when removing the debris pail, changing
the bag will prevent it from tearing.
* Only 500VF unit is equipped with a disposable bag (391C).
HOW TO EMPTY DEBRIS PAIL (600VF
AND 650VF POWER UNITS ONLY)
To empty the debris pail, release both latches on sides of the
unit by pulling out and then pushing up. Holding the pail by the
latches, lower it from unit. Carry pail to trash receptacle and
dispose of debris. Put the pail back in its place.
DISPOSABLE BAG REPLACEMENT
(500VF POWER UNIT ONLY)
To remove the disposable bag, release both latches on
sides of the unit by pulling out and then pushing up. Remove
the pail from unit. Grasp the edges of the bag collar and pull
down. The bag will slide off easily. Do not pull on the bag.
Unfold the new bag.
Grasp collar where indicated on the new bag and insert over
bag adapter. Be careful not to tear the bag. Ensure the collar
is positioned between the taper ring and the bag stopper on
the bag adapter (see illustration below). Put the pail back in
its place.
PERMANENT FILTER
(600VF AND 650VF POWER UNITS
ONLY)
This filter protects the motor and stops small particles from
escaping to the outside of the power unit wihout the need to
replace it. The filter cleans itself by moving up when the power
unit starts, and dropping down when the unit is turned off.
Under normal use, there is no need to maintenance this filter.
It is possible to remove it to inspect the motor foam filter, or
to replace it if ever it has been damaged (by sharp debris, for
example).
REMOVAL AND INSTALLATION OF
PERMANENT FILTER (600VF AND
650VF POWER UNITS ONLY)
Remove the pail from unit.
To remove the permanent
filter, use pull tab (A)
located on edge of filter to
pull and loosen filter from
inlet chamber wall. Squeeze
from both sides of the filter
to the center of the housing.
Then, carefully remove it
from the unit.
Squeeze the filter in order
to move it past the inlet
opening (B) Let the filter
bear against the unit wall
by releasing the pressure.
Make sure to place the rigid
ring in its groove to ensure
proper sealing.
NOTE: Make sure the filter is
installed so that the pull
tab (A) is accessible
for future filter removal.
OPERATION AND MAINTENANCE
AO0081
TAPER RING
BAG STOPPER
AA0005
A
AD0084
A
AD0085
B
CAUTION
Be sure to reinstall filter properly. Appropriate
location is critical to insure proper protection of
the motor.

11
REMOVAL AND INSTALLATION
OF HEPA FILTER
(650VF POWER UNIT ONLY)
NOTE: This is a disposable HEPA filter; do not attempt to
wash it since this will damage it.
This HEPA filter should be replaced every 5 years. Proceed as
follow:
If installed, detach the exhaust line from the top of the unit.
Disassemble upper part from lower part top cap assembly
by pushing on the 4 retaining tabs (one by one) located on
the lower part and pulling on upper part to disengage it.
NOTE: A small flat blade screwdriver can also be used to
pry on the 4 retaining tabs, as shown in illustration A
at the bottom of the page.
Discard the used filter and replace with a new one (part
no. S10941416). Be sure to install it with the gasket on top as
shown in illustration B (at the botton of the page), then snap
in place the upper part of the top cap. If need be, reconnect
the exhaust line to the top cap.
MOTOR FOAM FILTER
(ALL UNITS)
A motor foam safety filter, located at the top of the vacuum
chamber provides protection against dirt being pulled into
the motor if the disposable bag or permanent filter should
accidentally be torn. This filter should be checked and cleaned
if necessary when replacement bag is installed (500VF unit
only), or when permanent filter is removed (600VF and 650VF
units only). Simply brush filter clean. If the filter is excessively
soiled, hand wash in a water and mild detergent solution, rinse
and let it dry completely on a flat surface before reinstalling.
REMOVING MOTOR
FOAM FILTER
Remove the debris pail
and disposable bag or
permanent filter. Lift the
center of the wire retaining
the motor foam filter and
slide the filter out of its
location.
REINSTALLING
MOTOR FOAM
FILTER
To reinstall the motor foam
filter, reverse the steps
described above.
OPERATION AND MAINTENANCE (CONT'D)
CAUTION
Operating the power unit without the motor foam
filter will void the warranty.
AD0086
WARNING
!
Risk of warm surfaces and sharp edges. It is
recommended to wear safety gloves while handling
this HEPA filter.
4 X
AR0053
AB

12
TROUBLESHOOTING GUIDE
PROBLEMS POSSIBLE CAUSES POSSIBLE REMEDY
1. Loss or decrease of
suction occurs. • Debris pail or disposable bag is completely full.
• Debris pail gasket damaged or missing.
• Obstruction in the hose. A blockage in the hose
can be determined by inserting the hose into
any wall inlet and, while power unit is running,
check each additional inlet for normal suction
by holding the palm of your hand over the
open inlet. If normal suction is felt at all other
inlets, insert the hose into a second inlet. If the
blockage still exists it is located in the hose.
However, if the blockage does not occur when
the hose is changed, the blockage is probably
located in the tubing system leading to the
original inlet.
• Obstruction in the tubing system inside the
walls.
• Permanent filter or disposable bag torn.
• Wall inlet cover not properly sealed.
• Exhaust tubing or vent clogged.
• Change the disposable bag or empty debris pail
as described on page 10.
• Replace the debris pail gasket.
• Disconnect the hose from the wall inlet and
insert a blunt instrument into the hose —
slightly smaller in diameter — such as a flexible
garden hose. Push the garden hose through the
cleaning system hose until the obstruction has
been cleared.
• Insert hose end into any inlet to make power unit
running, then place the palm of your hand over
the opposite end of the hose.When you can feel
the suction increase, hold your hand over the
hose end for a few seconds and then quickly
remove your hand. This procedure repeated
several times should clear the obstruction. If the
blockage is not cleared, contact your nearest
Service Center.
• Clean the interior or the unit and install a new
permanent filter (or disposable bag).
• Check all wall inlet covers to be sure they are
closed and sealed tightly.
• Inspect and remove any blockages.
2. Power unit does
not start, or stops
suddenly.
• Defective inlet. Check other wall inlets.
• Power unit internal circuit breaker has been
activated (the reset button is popped up).
• Blown fuse or tripped circuit breaker on house
electrical panel.
• Defective hose.
• Power unit overcurrent protector has been
activated.
3. Power unit runs
continuously when
the hose is removed.
• The unit power switch is in ON position.
• An electrical short has occurred somewhere in
the system.
• Set the unit power switch to OFF position.
• Perform a complete check of all wall inlets and
power unit low voltage control lead connections.
Contact your authorized Service Center.
• Replace defective wall inlet.
• Push on the
circuit breaker
reset button
located on the
left side of the
power unit. If this
button pops up
again, contact
your authorized
Service Center.
• Replace fuse or reset circuit breaker on house
electrical panel.
• Replace hose as required.
• Unplug the power unit, wait at least 15 minutes
and plug back the power unit.
AC0003
POWER SWITCH
RESET
BUTTON

13
AL0012
SERVICE PARTS
REPLACEMENT PARTS AND REPAIRS
In order to ensure your unit remains in good working
condition, you must use Venmar Ventilation genuine
replacement parts only. Venmar Ventilation genuine
replacement parts are specially designed for each unit
and are manufactured to comply with all the applicable
certification standards and maintain a high standard of
safety. Any third party replacement part used may cause
serious damage and drastically reduce the performance
level of your unit, which will result in premature failing.
Venmar Ventilation also recommends to contact a
VenmarVentilation certified service depot for all replacement
parts and repairs.
4
11
7
12
KEY NO.PART NO.DESCRIPTION 500VF 600VF 650VF
1S10941410 650VF TOP CAP ASSEMBLY (INCLUDING ITEM 5) (UPPER PART)1
S10941412 500VF AND 600VF TOP CAP ASSEMBLY 11
2 S10941416 650VF EXHAUST HEPA FILTER 1
3 S10941414 650VF TOP CAP ASSEMBLY (LOWER PART)1
4 S10941399 MOTOR FOAM FILTER WITH FASTENER 11 1
5 S10941400 GASKET 11 3
6 S10941415 PERMANENT FILTER 11
7 S99670648 DEBRIS PAIL (INCLUDING KEY NO. 8) 1 1 1
8 S10941199 LATCH AND SCREWS 22 2
9 S10941404 LATCH KEEPER WITH SCREWS 22 2
10 S10941405 BAG ADAPTER WITH NUT AND SCREW 1
11 S10941406 INTAKE ELBOW WITH GASKET, SCREWS, AND NUTS 11 1
12 S30390555 UNIT SUPPORT BRACKET 11 1
13 391C DISPOSABLE BAG (SET OF 3, NOT SHOWN)1
NOTE: Order service parts by “Part No.” — not by “Key No.”
5
6
8
1
3
650VF UNIT
500VF AND 600VF UNITS
9
10
1
2

14
WARRANTY
VENMAR MODELS 500VF, 600VF AND 650VF
VENMAR VENTILATION ULC
CENTRAL VACUUM POWER UNIT
LIMITED WARRANTY
Venmar Ventilation warrants to the original consumer purchaser that its central vacuum power unit will be free from defects in materials
and workmanship for five (5) years for 500VF units, eight (8) years for 600VF units and ten (10) years for 650VF units. The first year of this
warranty covers the parts and labor in an authorized service center. After the first year, the parts only will be covered under this warranty.
THERE ARE NO OTHER WARRANTIES, EXPRESSED OR IMPLIED, INCLUDING, BUT NOT LIMITED TO, IMPLIED WARRANTIES OF
MERCHANTABILITY OR FITNESS FOR A PARTICULAR PURPOSE.
During these time periods, Venmar Ventilation will, at its option, repair or replace the power unit or part without charge, which is found to
be defective under normal use and service. THIS WARRANTY DOES NOT APPLY TO THE INSTALLATION OR THE PARTS USED IN THE
INSTALLED TUBING SYSTEM. All central vacuum hoses, electric or air-driven brushes, filters, attachments and accessories are warranted
for one (1) year from the original purchase date with the exception to consumables such as light bulbs and belts.We invite you to register your
product on line at www.venmar.ca. Venmar Ventilation reserves the right to limit this warranty if the product is not registered.
This warranty does not cover (a) normal maintenance and service or (b) any products or parts which have been subject to misuse, negligence,
accident, improper maintenance or repair (other than by Venmar Ventilation or an authorized representative), faulty installation or installation
contrary to recommended installation instructions.
The duration of any implied warranty is limited to the period as specified for the express warranty.
VENMARVENTILATION’S OBLIGATION TO REPAIR OR REPLACE,AT VENMAR VENTILATION’S OPTION, SHALL BETHE PURCHASER'S
SOLE AND EXCLUSIVE REMEDY UNDER THIS WARRANTY. VENMAR VENTILATION SHALL NOT BE LIABLE FOR INCIDENTAL,
CONSEQUENTIAL OR SPECIAL DAMAGES ARISING OUT OF OR IN CONNECTION WITH PRODUCT USE OR PERFORMANCE. Please
do not return your unit to place of purchase. Please visit www.venmar.ca for your closest service center.You may also call 1-888-882-7626 for
the name of an authorized representative in your area. This warranty supersedes all prior warranties.
Warranty service is to be completed by an authorized Service Center designated by Venmar Ventilation. Where applicable, in home service
will be made available only in areas where a contracted service provider offers service (during the first year only). If in home service is not
available, the product will be repaired or replaced, at Vemar Ventilation’s discretion, by the nearest authorized service provider. The unit
removal and reinstallation works are under the customer responsibility, and Venmar Ventilation cannot be charged for them.
To qualify for warranty service, you must notify Venmar Ventilation at the address or telephone number stated below. We will then forward you
the authorized service depot in your area.You will be required to present evidence of the original purchase date.
Date of Installation Builder or Installer
Model Number and Product Description
IF YOU NEED ASSISTANCE OR SERVICE
For the location of your nearest Venmar Ventilation ULC dealer, dial toll free: 1-888-882-7626
Please be prepared to provide: Product model number • Date and proof of purchase • The nature of the difficulty
Venmar Ventilation ULC, 550 Lemire Blvd., Drummondville, Québec J2C 7W9
Product specifications subject to change without notice. Printed in Canada.
This manual suits for next models
5
Table of contents