Verasys LC-SBH200-0 User manual

LC-SBH200-0, LC-VZC100-0, LC-VEC100-0, LC-ZEC510-0, LC-ZEC310-0, LC-BYP200-0, LC-
VAC1000-0, LC-VAC1001-0, LC-VAC1002-0, LC-VAC1100-0, LC-VAC3000-0, LC-IOM3711-0
Building Technologies & Solutions
www.johnsoncontrols.com
2021-04-08
Verasys System Product Bulletin
LIT-12012342
Release 4.0

2 Verasys System Product Bulletin

Contents
ContentsIntroduction to the Verasys system............................................................................................................. 5
Features and benefits.................................................................................................................................... 5
Verasys documentation................................................................................................................................. 7
SBH user interface......................................................................................................................................... 9
Supported controllers.................................................................................................................................. 10
Zone and Bypass Damper controllers............................................................................................ 10
VAV box controllers........................................................................................................................... 10
Verasys Equipment and Application Controllers (VEC and VAC)................................................. 11
Verasys Equipment Controller (VEC100)......................................................................................... 11
Verasys Lighting controller (VAC1001)............................................................................................ 11
Input/Output Module....................................................................................................................... 11
Controller features................................................................................................................................... 12
Constant Volume application........................................................................................................... 12
Sideloop application.......................................................................................................................... 12
Verasys Zone Coordinator................................................................................................................ 12
TEC30xx or TEC36xx Thermostat controllers................................................................................. 12
Verasys Pro Wireless Field Bus System........................................................................................... 13
Ideal applications..................................................................................................................................... 13
Applications to avoid............................................................................................................................... 13
PENN A52x refrigeration controllers............................................................................................... 14
Third-party BACnet controllers........................................................................................................ 14
Verasys application coverage..................................................................................................................... 14
Ordering information.................................................................................................................................. 16
Technical specifications............................................................................................................................... 21
North American emissions compliance..................................................................................................... 32
United States...................................................................................................................................... 32
Canada................................................................................................................................................ 32
Product warranty......................................................................................................................................... 33
Software terms............................................................................................................................................. 33
Patents........................................................................................................................................................... 33
Single point of contact................................................................................................................................. 33
Contact information..................................................................................................................................... 33
Verasys System Product Bulletin 3

4 Verasys System Product Bulletin

Introduction to the Verasys system
The Verasys system provides bundled equipment and controls solutions that use recognized
and trusted brands. Verasys is a plug-and-play solution that is part of the Johnson Controls®
Smart Systems. The Verasys system features simple, configurable controllers that you can bundle
with HVACR equipment from the factory or install in the field. You can use Verasys to configure
various HVACR controls applications for one building or an entire enterprise without using special
programming tools or control engineering.
The Verasys system features advanced direct digital control (DDC) controllers bundled with Johnson
Controls single packaged units (SPU), actuators, sensors, and damper assemblies. All devices self-
configure, and the Verasys Smart Building Hub (SBH) monitors the devices. Through the SBH,
you can access the system using either a laptop, smart phone, or tablet. The SBH connects to an
Ethernet backbone to enable remote connectivity and additional features, such as email and text
alarms. Verasys supported devices automatically connect the point, alarm, trend, and graphical
definitions. The points appear when you connect devices to the system, thereby making Verasys an
easy-to-use, light commercial building automation system (BAS).
Figure 1: Devices in the Verasys system
Features and benefits
Multi-client connectivity
Access all identifiable devices connected to the BACnet® MS/TP trunk.
Browser-based interface
Local display replacement solution so you can access device information through any supported
web browser.
5Verasys System Product Bulletin

Wi-Fi connectivity
Commission, configure, and access building automation equipment using Wi-Fi-enabled smart
devices or laptops.
Advanced features
View device and site alarms, events, and trends. Modify schedules and commission devices.
Browser-based remote building management
Remote management of building systems.
BACnet MS/TP integration
Add third-party devices into the Verasys ecosystem through BACnet MS/TP integration.
Simple interlocks to IOM controllers
Connects different systems to the Verasys network, such as exhaust and lighting systems.
Schedule synchronization
Combines common schedules with the schedule synchronization feature.
Zone groups for scheduling
Create schedules for multiple controllers in the same zone group.
Easy-to-use intuitive user interface (UI)
Uses color-coded bars on point listings so that you can quickly view the most important statuses
from a long list of points.
Wireless end device solutions
Uses the Verasys Pro Wireless system to connect the TEC3000 Thermostats to a SBH using wireless
signals.
Enterprise connectivity
Verasys Enterprise is a cloud-based solution that provides a multi-site aggregation of equipment,
data, alarms, setpoints, and schedules to authorized users. The enterprise application provides
a holistic view of an enterprise and the information that is required to manage HVAC, lighting,
energy, and input and output data for customers who have large building portfolios.
New user experience for facility
Offers continued improvement and equipment relationship for simple user view for end-users
and contractors. Included is a summary page for all HVAC devices serving spaces that includes
indicators for Name, Temperature, Status, and Occupancy, and a single area to change the
setpoint of the facility.
Data share
Share data from one source to multiple destinations. For example, share an outside air temperature
(OAT) from a SMART Equipment rooftop unit (RTU) to multiple TEC3000 devices using only one OAT
source.
Device cloning
Copy configuration parameters to other devices of the same type.
Backup and restore
Provides a simple interface to back up all SMART Equipment devices in the system. Store the backup
files on the SBH or download the file to any smart mobile device or computer that is connected to
the SBH.
Verasys System Product Bulletin6

Support for European light commercial to mid-market architecture
Uses Advanced Terminal Unit controllers (ATC) and application-specific, configurable Verasys
controllers in Europe only. A typical application contains small mini-chillers, boilers, an air handling
unit (AHU), and fan coil units (FCU).
Support for European light commercial to mid-market by the integration of York mini-chillers
to the Verasys system. Chiller model numbers:
• YMAA: software version 3.0.0.1114
• YLAA: software version 3.0.0.1114
• YLPA: software version 3.0.0.1114
Verasys documentation
The following table contains a list of the most important Verasys documents. For more
documentation and resources, visit http://www.verasyscontrols.com.
Table 1: Verasys documentation
Information Document title LIT or Part No.
Using the SBH user
interface for tenant
users
Verasys Tenant User Guide LIT-12013613
Using the SBH to
configure the Verasys
system
Verasys System User's Guide LIT-12012371
Overview of Verasys
system components,
features, and
operating modes
Verasys System Operation Overview Technical
Bulletin
LIT-12012370
Overview of Verasys
BACnet MS/TP
communication
Verasys BACnet MS/TP Communications
Technical Bulletin
LIT-12012362
BACnet MS/TP device
integration into
Verasys
Verasys BACnet MS/TP Integration Technical
Bulletin
LIT-12013606
Installing the SBH Verasys Smart Building Hub (SBH) Installation
Guide SBH200
Part No. 24-10737-00237
SBH network and IT
guidance
Verasys Smart Building Hub (SBH) Network
and IT Guidance Technical Bulletin
LIT-12012324
BACnet over IP
integration
Verasys BACnet over IP Integration User Guide LIT-12013287
Verasys Enterprise
overview
Verasys Enterprise Product Bulletin LIT-12013647
Using the Verasys
Enterprise user
interface
Verasys Enterprise Configuration and User
Guide
LIT-12012995
7Verasys System Product Bulletin

Table 1: Verasys documentation
Information Document title LIT or Part No.
Verasys Enterprise
security and IT
overview
Verasys Enterprise Security and IT Guide LIT-12013026
Wireless system
overview
Verasys Pro Wireless Field Bus System Technical
Bulletin
LIT-12013020
Verasys ZEC310 Zone Damper and BYP200
Bypass Damper Controllers Installation Guide
Part No. 24-10143-1248
Verasys Zone Coordinator (VZC) Installation
Guide
Part No. 24-10143-1280
Verasys Equipment Controller (VEC) Installation
Guide
Part No. 24-10143-1272
Verasys Input/Output Module (IOM)
Installation Guide
Part No. 24-10143-1256
Verasys ZEC510 VAV Controllers Installation
Guide
Part No. 24-10143-01485
Verasys 18 Point 240 VAC Application
Controller Installation Guide
Part No. 24-10143-01507
Verasys 32 Point 24 VAC Application Controller
Installation Guide
Part No. 24-10143-01515
Verasys 18 Point 24 VAC Application Controller
Installation Guide
Part No. 24-10143-01477
Verasys Input/Output Module Installation
Guide
Part No. 24-10143-01736
ZFR1821/ZFR1822 Pro Wireless Router
Installation Guide
Part No. 24-10325-00150
Installing Verasys
controllers
ZFR1825 Wireless Field Bus Coordinator
Installation Guide
Part No. 24-10325-00142
Verasys System Product Bulletin8

Table 1: Verasys documentation
Information Document title LIT or Part No.
VEC100 Generic RTU Controller, Modulated
Heating and Modulated Cooling Application
Note
LIT-12013484
VEC100 Generic RTU Controller, Modulated
Heating and Staged Cooling Application Note
LIT-12013361
VEC100 Generic RTU Controller, Staged
Heating and Modulated Cooling Application
Note
LIT-12013485
VEC100 Generic RTU Controller, Staged
Heating and Staged Cooling Application Note
LIT-12013443
VEC100 Generic RTU Heat Pump Controller
Application Note
LIT-12013452
Verasys Constant Volume Controller
Application Note
LIT-12013067
Verasys Input Output Module Application Note
LC-VAC1002-0
LIT-12012992
Verasys Lighting Controller Application Note LIT-12012524
Verasys Sideloop Controller Application Note LIT-12013364
Using Verasys
applications
Verasys System Changeover Bypass Zoning
System Design Application Note
LIT-12012331
List of alarms from
Verasys controllers
Verasys Alarms Summary Technical Bulletin LIT-12013648
SBH user interface
The SBH provides a wireless, intuitive UI optimized for mobile use.
Figure 2 shows the Facility view. Within this view, you can review the entire system to validate the
conditions of the facility by viewing temperature, mode, and occupancy.
Figure 2: Facility feature
9Verasys System Product Bulletin

The SBH UI scales to the device you are using. The main menus and screens are side-by-side on a
computer screen or tablet. On a phone display, you see either the menu or the screens you selected
from that menu, for example, the TEC3000 Home screen. When you view the UI on a phone or
smaller tablet, drag the screen from the left or right to display the required menu or screens.
Supported controllers
The Verasys system supports the following controllers:
• Zone and Bypass Damper controllers
• VAV box controllers
• Verasys Equipment and Application controllers
• Smart Equipment controllers
• TEC30xx/TEC36xx Thermostats
• Terminal Unit controllers (TUC and ATC)
• PENN® A52x refrigeration controllers
• Third-party BACnet controllers
In the following sections you can read about the controllers in more detail.
Zone and Bypass Damper controllers
The Zone Damper (ZEC310) and Bypass Damper (BYP200) controllers are components of the
Verasys zoning system. The Zone and Bypass Damper controllers run a pre-engineered HVAC
zoning application and provide the inputs and outputs required for this application. These
controllers are factory-configured for field installation on a zone or bypass damper assembly when
they are shipped.
The Zone and Bypass Damper controllers include advanced operating modes and multiple features
that ensure occupant comfort. A carbon dioxide (CO2) demand controlled ventilation (DCV) mode
in the Zone Damper regulates CO2 levels within a zone by adding fresh air into the zone during
occupied times. The controller uses occupancy sensing capability to switch from occupied mode to
standby mode based on local activity. To maximize energy savings, standby mode uses setpoints
that are higher than the occupied cooling setpoint and lower than occupied heating setpoint.
VAV box controllers
The VAV box zone controllers run a pre-engineered HVAC zoning sequence and provide the inputs
and outputs that the VAV application requires.
The ZEC510 controller contains multiple features to ensure occupant comfort. Because of an
optional occupancy sensing capability, the ZEC controller can switch from occupied mode to
standby mode based on zone activity. To maximize energy savings, standby mode uses setpoints
that are higher and lower than the occupied mode setpoints.
The ZEC510 controller also uses plug-and-play technology to detect the connected network sensor
types.
To commission VAV controllers, you can use the Verasys SBH, the MAP Gateway, or the VAV
Balancing Thermostat.
Verasys System Product Bulletin10

Verasys Equipment and Application Controllers (VEC and
VAC)
The Verasys Equipment and Application controllers are part of the SMART Equipment controller
family. The VECs run pre-engineered applications that reside on the zone bus of a zone coordinator,
and provide the inputs and outputs required to monitor and control HVAC equipment.
The Application controllers run pre-engineered applications that reside on the system bus of an
SBH, and provide the inputs and outputs required to monitor and control various applications.
The Equipment and Application controllers include an integral real-time clock to monitor and
control schedules, calendar trends, and to operate for extended periods of time as stand-alone
controllers when they are offline from the system network.
Verasys Equipment Controller (VEC100)
The VEC100 controls either VAV or changeover bypass (COBP) units. You can use this single
controller to control units that are not a Smart Equipment units. The VEC100 ships with an
application that supports up to two stages of heating and four stages of cooling. Additional
applications are available to control modulated heating, modulated cooling, and a heat pump.
You can configure all of the controller applications for use in a VAV or COBP system and to control
an economizer. The controller automatically uses analog sensors when you connect them. If you
connect a return air sensor to the controller and the system is a VAV system, the warm-up feature
is integrated for control. If a CO2 sensor is connected and an economizer is installed, demand
ventilation control sequences are available. For more information about the sequences that this
controller uses, refer to the application note of the relevant application and the Verasys System
Operation Overview Technical Bulletin (LIT-12012370).
Verasys Lighting controller (VAC1001)
The Verasys Lighting controller (VAC1001) is a Verasys Application controller that controls up to
nine lighting contactors that are grouped in zones. You can control and schedule up to eight zones
from a light level sensor. You can connect either a binary or analog light level sensor and drive
the zone control based on light level. The zone also includes an associated schedule that can drive
the output of the zone. You can drive contactors for outside lights because of the flexibility of the
controller; lights come on when it is dark and turn off at a fixed time or drive other zones based on
the schedule. The first seven zones have a binary input that can override the zone output. You can
set the binary input to momentary and allow a set amount of time for the override, or maintain the
input for a more permanent override.
Input/Output Module
The Input/Output Module is a Verasys Application controller (VAC1002). The VAC1002 is a simple
point multiplexer that monitors up to five analog inputs and four binary inputs. The controller
controls up to nine binary outputs, connects to up to five wired or wireless NS sensors, and up to
four Johnson Controls’ energy meters. The VAC1002 uses the SBH to monitor and control auxiliary
points in a facility.
You can configure analog, binary, and NS sensor inputs for trending and alarming. The analog
trend samples are set to 200. The binary trend samples are set to 20, but you can adjust the trend
interval. You can configure each input for alarming. For binary inputs, you can define which state
triggers the alarm. For analog inputs, you can set high and low alarm limits. The alarm message is
adjustable for binary and analog types.
You can connect Smart Edge devices to the VAC1002. The energy meter is compatible with the
controller and the meter monitors the voltage, amperage, demand, and consumption for each
phase of incoming power. The energy meter and all inputs are available to use with the interlock
11Verasys System Product Bulletin

features of the SBH. You can control all the outputs on the VAC1002 with the interlock feature or
with the scheduling feature on the SBH. You can also use the data share feature to share data from
one input source to multiple destinations.
Controller features
• Integrate facility loads, such as lighting or exhaust fans, into building occupancy schedules
• Circuitry and connectors for the five analog inputs, four binary inputs, nine binary outputs, five
wired or wireless NS sensors, and four energy meters
• Point interlocking for advanced control of multiple conditions, such as temperature, humidity,
CO2, fan status, occupancy status, and control mode
• Customizable alarming for monitoring devices, conditions, or spaces
• Power monitoring to help you understand power usage in a facility
Constant Volume application
The Constant Volume application is a Verasys application. You can load the application to a
VAC1000 or VAC3000 depending on the equipment that you want to control. The Constant Volume
application adds to the features present in Smart equipment and extends the capabilities of the
TEC3xxx series for third-party equipment. The application includes support for up to four stages
of cooling and four stages of heating, modulated 0 V to 10 V output for heating and cooling, and
heat pump with an additional two stages of supplemental heat available. The Constant Volume
application can control a mixed air damper or set a minimum outside air damper position, and
meet Title 24 compliance for the state of California. Other supported features include occupancy
scheduling, outdoor air lockouts, dehumidification, humidification, demand control ventilation, and
much more.
Sideloop application
The Sideloop application is a Verasys application. You can load the application to a VAC1000.
You can use the Verasys Sideloop application to design simple loops that control various types of
equipment. Define the inputs, outputs, and netsensors, and enable and configure the control loops
that you want to use.
You can use analog and binary control loops, and a multistage control (MSC) loop. The available
control loop strategies include reset span, PID control with or without setpoint reset, binary to
analog, analog to binary, and binary interlock.
Verasys Zone Coordinator
The Verasys Zone Coordinator is used for multi-zone applications as an engine to coordinate a
complete VAV or COBP system. You can order an individual Verasys Zone Coordinator or a panel
version. The Verasys Zone Coordinator automatically recognizes the unit configuration, and
switches to either VAV or COBP based on the system type.
TEC30xx or TEC36xx Thermostat controllers
The TEC30xx and TEC36xx Series Thermostat controllers are Verasys Pro Wireless or BACnet MS/TP
thermostats that provide on and off, floating, and proportional control of the following elements:
• Local hydronic reheat valves
• Pressure-dependent VAV equipment with or without local reheat
• Two-pipe or four-pipe fan coils
Verasys System Product Bulletin12

• Cabinet unit heaters
• Other zoning equipment using an on and off, floating, or 0 VDC to 10 VDC proportional control
input
Models also provide single or two-stage control of unitary RTUs with or without economizers and
heat pumps.
The TEC30xx Thermostat controllers are Verasys Pro Wireless models that require additional
devices for the Pro Wireless network connection to the SBH.
Verasys Pro Wireless Field Bus System
The Verasys Pro Wireless Field Bus System uses Zigbee technology to wirelessly monitor HVAC
equipment that uses the BACnet protocol. The Verasys system creates a wireless mesh network that
enhances reliability. A resilient, self-healing function in the system uses multiple transmission paths
that automatically form for the data.
The MS/TP trunk and device limits for the Verasys SBH are the same for hard-wired products,
wireless products, or a combination of hard-wired and wireless products. The wireless mesh
network is independent of any building infrastructure and does not require any preexisting wireless
infrastructure.
Ideal applications
The wireless products within a Verasys system are ideal for any location where it is cost-prohibitive,
difficult, or aesthetically unappealing to hardwire between products. Examples of these locations
include the following:
• Office buildings, university campuses, educational facilities, and other commercial structures
with brick or solid concrete walls and ceilings that impede hard-wired applications
• Retail stores and other commercial real estate where tenant turnover is frequent and
temporary walls and ceilings are common
• Museums, historical buildings, atriums, and other sites where building aesthetics and historical
preservation are important
• Gymnasiums and other locations with large, open spaces
• Buildings with marble, granite, glass, mirrors, wood veneer, or other decorative surfaces that
present challenges to hard-wiring
• Buildings with asbestos or other hazardous materials that must not be disturbed
• Buildings with occupants sensitive to disruptions to business
• Regions with high labor costs
• Refrigerator and freezer storage containers
Applications to avoid
Locations or applications that prohibit cellular telephones or Wi-Fi systems are unsuitable for the
wireless Verasys products. Examples of these locations include the following:
• Operating rooms or radiation therapy rooms
• Validated environments
• UL 864 applications
• Department of Defense applications requiring Diacap certification, such as military bases and
military hospitals
13Verasys System Product Bulletin

Do not use the wireless products in applications that cannot tolerate intermittent interference, or in
the following situations:
• Critical control features that impact life-safety or result in large monetary loss, including
secondary backup
• Life-safety applications
• Data centers, production lines, or critical areas that shut down
• Loss of critical control that results from loss of data from humidity or temperature sensor
communications
• Operating exhaust fans or AHUs that impair a purge or pressurization mode
• When missing data invalidates reporting required by the customer
• Monitored security points
PENN A52x refrigeration controllers
The PENN A5xx Series Wall Mount Refrigeration and Defrost Controllers provide refrigerated space
and defrost control for low and medium temperature refrigeration applications.
Third-party BACnet controllers
Verasys supports the automatic discovery of third-party controllers. When you connect a third-
party controller to the system bus, its data automatically fills a predefined set of views based on the
object type.
You can create profiles for third-party controllers. Profiles provide the following benefits:
• You can give BACnet points user-friendly names.
• You can rearrange the data into specific views.
• You can add BACnet extensions such as alarms, trends, and schedules.
You can export profiles from the SBH and import them into another SBH to ensure a consistent
interface across multiple sites. Third-party controller integration also applies to the Verasys
Enterprise cloud. Third-party data is visible in the Verasys Enterprise web user interface alongside
the data from Verasys-compatible devices.
Verasys application coverage
The following tables provide information about the Verasys application coverage.
Table 2: Supported VAV and COBP unit controllers
Feature Simplicity Smart Equipment 3rd party controller (VEC100)
Up to four stages of cooling Yes Yes
Modulated cooling No Yes
Up to two stages of heating Yes Yes
Up to three stages of heating Yes No
Modulated heating Yes Yes
Heat pump Yes Yes
Economizer Yes Yes
Verasys System Product Bulletin14

Table 2: Supported VAV and COBP unit controllers
Feature Simplicity Smart Equipment 3rd party controller (VEC100)
Title 24 economizer
Note: 24 sequence and alarm notification
is implemented from within the
application. State of California certification
is pending.
Yes No
Demand ventilation control Yes Yes
Dehumidification Yes No
Humidification No No
Variable frequency drive for COBP Yes Yes
Note: The table shows the applications that the LC-VEC100-0 covers. You may need to add the
LC-IOM3711-0 to cover some of the features, including modulating heating or cooling. For
more information, refer to the application note and quick start guide for your application.
Table 3: Supported single zone unit controllers
Feature
Simplicity Smart
Equipment TEC3000 LC-VAC1000-0 LC-VAC3000-0
Up to two stages of cooling Yes Yes Yes Yes
Up to four stages of cooling Yes No Yes Yes
Modulated cooling No No Yes Yes
Up to two stages of heating Yes Yes Yes Yes
Up to three stages of heating Yes No Yes Yes
Heat pump Yes Yes Yes Yes
Economizer Yes Yes Yes Yes
Title 24 economizer
Note: 24 sequence and alarm
notification is implemented from
within the application. State of
California certification is pending.
Yes No Yes Yes
Demand ventilation control Yes No Yes Yes
Dehumidification Yes No Yes Yes
Humidification No No Yes Yes
Fixed variable fan Yes No Yes Yes
Note: The table shows the applications that the LC-VAC1000-0 and LC-VAC3000-0 cover. You
may need to add the LC-IOM3711-0 to cover additional applications. For example, the LC-
VAC3000-0 is a 32-point controller with all of the applications available on the base controller
except for humidification, for which you need the LC-IOM3711-0. For more information, refer
to the application note and quick start guide for your application.
Table 4: Supported VAV controllers
Feature Staged Incremental Proportional SCR
Up to three stages of box heat Yes No No
Incremental valve for box heat No Yes No
Proportional signal for box heat (SCR or valve) No No Yes
Supports no fan Yes Yes Yes
Supports series fan Yes Yes Yes
Supports parallel fan Yes Yes Yes
Discharge temp monitoring Yes Yes Yes
Occupancy sensing input Yes Yes Yes
Up to five net sensors (averaging) Yes Yes Yes
15Verasys System Product Bulletin

Table 4: Supported VAV controllers
Feature Staged Incremental Proportional SCR
Up to five CO2 sensors (high select) Yes Yes Yes
Staged supplemental heat Yes No No
Incremental supplemental heat No Yes Yes
Table 5: Supported COBP controller
Feature LC-ZEC310-0
Modulated box heat Yes
On/Off box heat Yes
Modulated supplemental heat Yes
PWM supplement heat (10 sec duty cycle) Yes
On/Off supplemental heat Yes
Occupancy sensing input Yes
Up to five net sensors (averaging) Yes
Up to five CO2 sensors (high select) Yes
Extra output for second damper actuator Yes
Note: Box heat is any heat source that is located in the duct. Supplement heat is any heat
source that is located outside the duct.
Ordering information
Contact your Johnson Controls representative to order Verasys system or related products. See the
following table for product code numbers and product descriptions.
Table 6: Ordering information
Product code
number Description
LC-SBH200-0 SBH with Wi-Fi adapter
LC-SBH200-0S SBH with Wi-Fi adapter and power supply
LC-SBH200-0LA SBH for Latin America
LC-VZC100-0 Verasys Zone Coordinator for VAV and COBP applications
LC-VZCPNL-0 Verasys Zone Coordinator for VAV and COBP applications - panel version
LC-VEC100-0 Verasys Equipment Controller for third-party RTU (VAV, COBP), with staged heating and staged cooling
application. Other applications are available. For application files and documentation, visit http://
verasyscontrols.com.
LC-ZEC510-0 Configurable VAV Box Controller, all fan types, staged, incremental and proportional SCR heating
Note: You can order the ZEC510 controllers mounted and wired in VAV box assembly. For more
information, contact your Johnson Controls representative.
LC-ZEC310-0 Field-installed zone controller, no damper
Note: You can order the LC-ZEC310-0 controller mounted on round dampers. For more
information, refer to the Zone and Bypass Damper Controllers Catalog Page (LIT-1901009).
LC-BYP200-0 Field-installed Bypass Damper Controller, no damper
Note: You can order the LC-BYP200-0 controller mounted on round dampers. For more
information, refer to the Zone and Bypass Damper Controllers Catalog Page (LIT-1901009).
LC-VAC1000-0 18 point 24 VAC Application Controller with no application loaded. For application files and
documentation, visit http://verasyscontrols.com.
LC-VAC1001-0 18 point 24 VAC Application Controller with lighting controller application loaded
LC-VAC1002-0 18 point 24 VAC Application Controller with input and output controller application loaded
LC-VAC1100-0 18 point 240 VAC Application Controller with no application loaded. For application information,
contact Verasys support.
LC-VAC3000-0 32 point 24 VAC Application Controller with no application loaded. For application files and
documentation, visit http://verasyscontrols.com.
Verasys System Product Bulletin16

Table 6: Ordering information
Product code
number Description
LC-VLP100-0 16 in. x 20 in. lighting panel with LC-VAC1001-0 Controller, with 96 VA power supply, without relays,
without contactors
LC-VLP110-0 24 in. x 24 in. lighting panel with LC-VAC1001-0 Controller, with pilot relays, without contactors
LC-VLP120-0 24 in. x 36 in. lighting panel with LC-VAC1001-0 Controller, with pilot relays, with contactors
LC-IOP200-0 16 in. x 20 in. input and output panel with LC-VAC1002-0, with 96 VA power supply
LC-ZFR1825-0 Wireless coordinator
LC-ZFR1822-0B Wireless Repeater Kit Wall mount type
LC-ZFR1821-0B Wireless Repeater Kit Flag mount type
LC-IOM3711-0 12-point IOM with 4 UI, 4 UO, 4 BO, Zone bus, and Sensor bus support. Relays are rated for 120/240
VAC.
A525AEDV-0203C PENN electronic wall mount refrigeration and defrost controller with two sensor inputs and five output
relays. Includes two A99B type sensors, and BACNet MSTP communication option.
Table 7: SBH200 accessories
Product code
number Description Shipped with
ACC-PWRKIT-1A24
AC-PWRKIT-1D24
Verasys LC-SBH200-0 power supply for North America
ACC-PWRKIT-1E24 Verasys LC-SBH200-0 power supply for Europe
LC-SBH200-0S
ACC-WIFIKIT-0DU Verasys LC-SBH200-0 USB Wi-Fi adapter for North America and Europe LC-SBH200-0
LC-SBH200-0S
Table 8: Supported third-party USB Wi-Fi adapters for SBH
Manufacturer Model Name
D-LINK® DWA-131 E
D-LINK DWA-171 A
D-LINK DWA-171 C
NETGEAR® A6100
TP-LINK® Archer
PREMIERTEK® PT-8811AU
Table 9: Zone controller accessories
Product code number Description
Zone temperature sensors (hard-wired) ZEC310 only
TE-68NT-0N00S Wall temperature sensor, 1000 ohm, nickel with temperature occupancy button
TE-68NT-1N00S Wall temperature sensor, 1000 ohm, nickel with warmer and cooler (W/C) adjustment and
temperature occupancy pushbutton
Second zone damper actuator
Note: You must purchase the actuator and add it to a damper without a ZEC310 controller.
M9106-GGA-2 6 N•m torque non-spring return damper actuator
Network sensors for zone temperature and CO2
NSB8BTC240-0 Network sensor, fixed segment display, Johnson Controls logo, local setpoint, white
NSB8BTC242-0 Network sensor, fixed segment display, Johnson Controls logo, local setpoint, black
NSB8BTC241-0 Network sensor, fixed segment display, no logo, local setpoint, white
Network sensors for zone temperature
NS-B8BTN240-0 Network sensor, 120 mm x 80 mm, Johnson Controls logo, local setpoint, white
NS-B8BTN241-0 Network sensor, 120 mm x 80 mm, no logo, local setpoint, white
NS-B8BTN040-0 Network sensor, 120 mm x 80 mm, Johnson Controls logo, no setpoint, white
NS-B8BTN041-0 Network sensor, 120 mm x 80 mm, no logo, no setpoint, white
NS-B8BTN140-0 Network sensor, 120 mm x 80 mm, Johnson Controls logo, warmer and cooler adjustment, white
NS-B8BTN141-0 Network sensor, 120 mm x 80 mm, no logo, warmer and cooler adjustment, white
17Verasys System Product Bulletin

Table 9: Zone controller accessories
Product code number Description
NS-B8BTN242-0 Network sensor, 120 mm x 80 mm, Johnson Controls logo, local setpoint, black
NS-B8BTN243-0 Network sensor, 120 mm x 80 mm, no logo, local setpoint, black
NS-B8BTN042-0 Network sensor, 120 mm x 80 mm, Johnson Controls logo, no setpoint, black
NS-B8BTN043-0 Network sensor, 120 mm x 80 mm, no logo, no setpoint, black
NS-B8BTN142-0 Network sensor, 120 mm x 80 mm, Johnson Controls logo, warmer and cooler adjustment, black
NS-B8BTN143-0 Network sensor, 120 mm x 80 mm, no logo, warmer and cooler adjustment, black
Occupancy lighting switch
OLS-2100-1 Occupancy sensing light switch for control of indoor incandescent and fluorescent lights
RIBU1C Enclosed relay for OLS-2100-1 sensor
Table 10: Wireless thermostat controller models
Code number Control output Occupancy Dehumidification
Johnson
Controls logo Color
TEC3012-13-000 On/off or floating fan coil
and zoning
No Yes Yes Black
TEC3012-14-000 On/off or floating fan coil
and zoning
No Yes Yes White
TEC3012-16-000 On/off or floating fan coil
and zoning
No Yes No White
TEC3013-14-000 On/off or floating fan coil
and zoning
Yes Yes Yes White
TEC3022-13-000 0 to 10 VDC proportional
fan coil and zoning
No Yes Yes Black
TEC3022-14-000 0 to 10 VDC proportional
fan coil and zoning
No Yes Yes White
TEC3022-16-000 0 to 10 VDC proportional
fan coil and zoning
No Yes No White
TEC3023-14-000 0 to 10 VDC proportional
fan coil and zoning
Yes Yes Yes White
TEC3030-13-000 Single- or two-stage
RTU/heat pump with
economizer
No No Yes Black
TEC3030-14-000 Single- or two-stage
RTU/heat pump with
economizer
No No Yes White
TEC3030-16-000 Single- or two-stage
RTU/heat pump with
economizer
No No No White
TEC3031-14-000 Single- or two-stage
RTU/heat pump with
economizer
Yes No Yes White
TEC3031-13-000 Single- or two-stage
RTU/heat pump with
economizer
Yes No Yes Black
TEC3031-14-000 Single- or two-stage
RTU/heat pump with
economizer
Yes No Yes White
TEC3031-15-000 Single- or two-stage
RTU/heat pump with
economizer
Yes No No Black
TEC3031-16-000 Single- or two-stage
RTU/heat pump with
economizer
Yes No No White
Verasys System Product Bulletin18

Table 11: Field-selectable BACnet MS/TP or N2 Networked Thermostat Controller models
Code number Control output Occupancy Dehumidification Johnson Controls logo Color
TEC3612-13-000 On/off or floating fan coil
and zoning
No Yes Yes Black
TEC3612-14-000 On/off or floating fan coil
and zoning
No Yes Yes White
TEC3612-16-000 On/off or floating fan coil
and zoning
No Yes No White
TEC3613-14-000 On/off or floating fan coil
and zoning
Yes Yes Yes White
TEC3622-13-000 0 to 10 VDC proportional
fan coil and zoning
No Yes Yes Black
TEC3622-14-000 0 to 10 VDC proportional
fan coil and zoning
No Yes Yes White
TEC3622-16-000 0 to 10 VDC proportional
fan coil and zoning
No Yes No White
TEC3623-14-000 0 to 10 VDC proportional
fan coil and zoning
Yes Yes Yes White
TEC3630-13-000 Single- or two-stage
RTU/heat pump with
economizer
No No Yes Black
TEC3630-14-000 Single- or two-stage
RTU/heat pump with
economizer
No No Yes White
TEC3630-16-000 Single- or two-stage
RTU/heat pump with
economizer
No No No White
TEC3631-14-000 Single- or two-stage
RTU/heat pump with
economizer
Yes No Yes White
Table 12: TEC3000 accessories (order separately)
Code number Description
TEC-WALLPLT Wallplate for retrofitting existing installations or concealing mounting surface damage, use with any
TEC3000 Series Thermostat Controller
T-4000-119 Allen-head adjustment tool (30 per bag)
19Verasys System Product Bulletin

Table 13: Verasys Pro Series wireless field bus system components selection chart
Code number Description
LC-ZFR1825-0 The LC-ZFR1825-0 kit is comprised of the following components:
• ZFR1825 coordinator and mounting base with 110/220 VAC power supply
• ZFR1825 antenna with mounting bracket
LC-ZFR1821-0B The LC-ZFR1821-0B kit is comprised of the following components:
• ZFR1821 Pro Router, electrical mechanical tubing (EMT) mount, with 3 ft RJ-12 connecting
cable
• 24 VAC to 15 VDC power supply for the router
• Box mount for ZFR1821 Pro Router
Use the ZFR1821 EMT mount repeater above the ceiling mounting.
Use the alternative ZFR1822 Pro Router for flush wall-mount or below the ceiling-mount
applications.
Note: A field-provided ceiling clip is required to mount the ZFR1822 Pro Router below grid
ceilings.
LC-ZFR1822-0B The LC-ZFR1822-0B kit is comprised of the following components:
• ZFR1822 Pro Router, wall-mount, with 10 ft RJ-12 connecting cable
• 24 VAC to 15 VDC power supply for the router
• Drywall-mounting hardware ceiling clips not provided due to variety of ceiling types
Note: Use the ZFR1822 Pro Router for flush wall-mount or below the ceiling-mount
applications. Use a field-provided ceiling clip to mount the ZFR1822 Pro Router below grid
ceilings. Use the alternative ZFR1821 Pro Router, EMT mount for above the ceiling mounting.
LC-ZFR1821-0 The LC-ZFR1821-0 kit is comprised of the following components:
• ZFR1821 Pro Router, EMT mount, functions with Metasys BACnet Wireless-Enabled Field
Controller (WEFC) and WRZ Series Sensors
• Box mount for ZFR1821
Note: Use the ZFR1821 EMT mount repeater for above the ceiling mounting. Use the
alternative ZFR1822 Pro Router for flush wall-mount or below the ceiling-mount applications.
Use a field-provided ceiling clip to mount the ZFR1822 Pro Router below grid ceilings.
LC-ZFR1822-0 The LC-ZFR1822-0 kit is comprised of the following components:
• ZFR1822 Pro Router and wall-mount
• Drywall-mounting hardware ceiling clips not provided due to variety of ceiling types
Note: Use the ZFR1822 Pro Router for flush wall-mount or below the ceiling-mount
applications. Use a field-provided ceiling clip to mount the ZFR1822 Pro Router below grid
ceilings. Use the alternative ZFR1821 EMT mount repeater for above the ceiling mounting.
Table 14: ZFR1825 accessories (order separately)
Product code number Product description
TP-2420 Transformer, Wall Plug Mount, 120 VAC to 24 VAC, 20 VA, Class 2
WRZ-SST-120 Wireless Sensing System Tool. Requires WRZ Series Sensor to function as a site survey tool for
ZFR1800 Wireless Field Bus System, or for WRZ-7860-0 One-to-One Room Sensing System.
Y65T31-0 Transformer, 120/208/240 VAC to 24 VAC, 40 VA, Class 2, Foot Mount, 20 cm (8 in.) Primary Leads and
Secondary Screw Terminals
Note: Additional Y60 Series Transformers are available from Johnson Controls.
ZFR-USBHA-0 USB Dongle with ZFR Driver provides a wireless connection through the CCT to allow wireless
commissioning of the wireless enabled FAC, FEC, IOM, and VMA16 controllers. Use the USB ZFR
Dongle with the ZFR Checkout Tool to troubleshoot and validate ZFR wireless meshes using a laptop
computer.
ZFR-1810ANT-700 Replacement antenna kit for ZFR1825 Wireless Field Bus Coordinator. Includes antenna, coaxial
cable, and mounting hardware.
Verasys System Product Bulletin20
This manual suits for next models
11
Table of contents
Other Verasys Control System manuals
Popular Control System manuals by other brands

Seav
Seav LRX 2035 NEW manual

Grundfos
Grundfos CONTROL MPC Safety instructions and other important information

VIPA
VIPA System 200V CP 240 manual

Salus
Salus CO10RF installation manual

Extron electronics
Extron electronics TouchLink TLP 350CV user manual

MachMotion
MachMotion 2000 Series General installation manual

Carel
Carel infrared IR32CE Series user manual

MEKANIKA
MEKANIKA CNC EVO quick start guide

elsner elektronik
elsner elektronik 60121 Installation & operation

Siemens
Siemens QAW10 operating instructions

Novatron
Novatron Xsite EASY 100022 installation manual

Intermatic
Intermatic RC2263BE Installation, operation & service manual