Verasys LC-VAC300 0 Series User manual

Verasys® 32 Point 24 VAC Application Controller Installation Instructions
1
Application
The Verasys® Application Controller is part of the SMART Equipment Controller family. The Verasys Application
Controllers run pre-engineered applications and provide the inputs and outputs required to monitor and control a
wide variety of HVAC equipment.
Verasys Application Controllers operate on an RS-485 BACnet® (MS/TP) Bus as BACnetAdvancedApplication
Controllers (B-AACs) and integrate into Johnson Controls® and third-party BACnet systems.
Verasys Application Controllers have an integral real-time clock. The clock functionality monitors and controls
schedules, calendars, trends, and operate for
extended periods of time as stand-alone controllers when offline from
the system network.
Verasys 32 Point 24VAC Application Controller Features
The Verasys Application Controllers are used in a Verasys system. The Verasys 32 Point 24 VAC Application
Controller comes without an application, but you can load custom built applications into this controller. Depending
on your market, you can access an application library in certain markets. Contact your local Verasys
representative. The Verasys 32 Point 240VAC Application Controller has the following features:
• Input/Output (I/O)quantities andcharacteristics of the Verasys Application Controller
• Real-time clock with local display
• Built-in BACnet schedule objects and calendars
• Mobile Access Portal (MAP) Gateway compatibility for configuration through smart mobile devices and remote
connectivity
• Verasys Smart Building Hub (SBH) compatible through the BACnet MSTP system bus connection
• Dedicated Sensor bus for Johnson Controls smart end-devices
• Dedicated Modbus port for third-party end-device integration with Modbus
•Multi-protocol support for BMS integration BACnet MSTP, N2 and Modbus RTU, through on-board display
IMPORTANT: Use this Verasys Application Controller only as an operating control. Where failure or
malfunction of the Verasys Application Controller could lead to personal injury or property damage to the
controlled equipment or other property, additional precautions must be designed into the control system.
Incorporate and maintain other devices, such as supervisory or alarm systems or safety or limit controls,
intended to warn of or protect against failure or malfunction of the Verasys Application Controller.
IMPORTANT: Utiliser ce Verasys Application Controller uniquement en tant que dispositif de contrôle de
fonctionnement. Lorsqu'une défaillance ou un dysfonctionnement du controller risque de provoquer des
blessures ou d'endommager l'équipement contrôlé ou un autre équipement, la conception du système de
contrôle doit intégrer des dispositifs de protection supplémentaires. Veiller dans ce cas à intégrer de façon
permanente d'autres dispositifs, tels que des systèmes de supervision ou d'alarme, ou des dispositifs de
sécurité ou de limitation, ayant une fonction d'avertissement ou de protection en cas de défaillance ou de
dysfonctionnement du Verasys Application Controller.
Verasys® 32 Point 24 VAC Application Controller
Installation Instructions
LC-VAC300x-0 Part No. 24-10143-01515, Rev A
Issued May 2018
24-10143-01515,Rev—
*2410143015

Verasys® 32 Point 24 VAC Application Controller Installation Instructions
2
North American Emissions Compliance
United States
Canada
Installation
Followtheseguidelineswhen you install a Verasys Application Controller:
• To help
minimize vibration and shock damage, transport the controller in the original container.
• Verify that all parts ship with the controller.
• Do not drop the controller or subject it to physical shock.
Parts Included
• One Verasys 32 point 24V Application Controller
• One installation instruction sheet
Materials and Special Tools Needed
• Three fasteners appropriate for the mounting surface, such as M4 screws or #8 screws
• One 20 cm (8 in.) or longer piece of 35 mm DIN rail and appropriate hardware for DIN rail mount only
• Small straight-blade screwdriver for securing wires in the terminal blocks
Mounting
Follow these guidelines when you mount a field controller:
• Ensure the mounting surface can support the controller, DIN rail, and any user-supplied enclosure.
• Mount the controller horizontally on 35 mm DIN rail whenever possible.
• Mount the controller in the proper mounting position, see Figure 1.
• Useshimsorwasherstomountthecontrollersecurely and evenly on the mounting surface.
• Mount the controller in an area free of corrosive vapors and follow the ambient condition requirements listed in
Table 11.
• Ensure sufficient space around the controller for
cable and wire connections for easy cover removal, and good
ventilation through the controller. Provide a minimum of 50 mm (2 in.) on the top, bottom, and front of the
controller.
This equipment has been tested and found to comply with the limits for a Class A digital device pursuant to
Part 15 of the FCC Rules. These limits are designed to provide reasonable protection against harmful
interference when this equipment is operated in a commercial environment. This equipment generates, uses,
and can radiate radio frequency energy and, if not installed and used in accordance with the instruction manual,
may cause harmful interference to radio communications. Operation of this equipment in a residential area may
cause harmful interference, in which case users will be required to correct the interference at their own expense.
This Class (A) digital apparatus meets all the requirements of the Canadian Interference-Causing Equipment
Regulations.
Cet appareil numérique de la Classe (A) respecte toutes les exigences du Règlement sur le matériel brouilleur
du Canada.
IMPORTANT: Only qualified personnel should install or service Verasys products. These instructions are a
guide for such personnel. Mount the Verasys controllers on a wall or DIN rail inside an enclosure (rated at least
IP20). Carefully follow all instructions in this document and all instructions for the controller.

Verasys® 32 Point 24 VAC Application Controller Installation Instructions
3
• Do not mount the controller on surfaces prone to
vibration, such as duct work.
• Do not mount the controller in areas where electromagnetic emissions from other devices or wiring can
interfere with controller communication.
Follow these additional guidelines when you mount a field controller in a panel or enclosure:
• Mount the controller so that the enclosure walls do not prevent cover removal and obstruct ventilation through
the controller.
• Mount the controller so that the power transformer and other devices do not radiate excessive heat to
the
controller.
• Do not install the controller in an airtight enclosure.
• Use a zip-tie to secure the controller when you ship it.
Figure 1: Verasys Application Controller mounting position
DIN Rail Mount Applications
Mountingthefield controllerhorizontallyon35 mm DINrail is the preferred mounting method.
To mount a field controller on 35 mm DIN rail, complete the following steps:
1. Securely mount a 20 cm (8 in.) or longer section of
a
35mmDINrailhorizontallyandcenteredintheappropriate
space so that the controller mounts as in in Figure 1.
2. Pull the two lower mounting clips outward from the controller to the extended position.
3. Hang the controller on the DIN rail by the hooks at
the top of the DIN rail channel on the back of the controller
andposition thecontroller snuggly against the DIN rail.
4. Zip tie the controller to the DIN rail when you ship.
5. Push thebottommounting clipsinward (up) to secure the controller on the DIN rail.
To remove the controller from the DIN rail, pull the bottom mounting clips out to the extended position and
carefully lift the controller off the DIN rail.
IMPORTANT: Do not overtighten the mountingscrews. Overtightening the screws may damage the mounting
clips.
Horizontal Mount Position
Required for DIN Rail Mounting

Verasys® 32 Point 24 VAC Application Controller Installation Instructions
4
Figure 2: Back of Controller Showing Extended Mounting Clips, DIN Rail Channel, and Mounting
Dimensions, mm (in.)

Verasys® 32 Point 24 VAC Application Controller Installation Instructions
5
Wiring
For detailed information on configuring and wiring an MS/TP Bus, System Bus, and Sensor Bus, refer to the
Verasys® BACnet® MS/TP
Communications Bus Technical Bulletin (LIT-12012362).
Verasys Application Controller Terminal Blocks and Bus Ports
See Figure 11 for terminal block, spade location, and bus port locations on the LC-VAC300x-0 controller. Use the
following guidelines when wiring a controller.
Input and Output Terminal Blocks
On most field controller models, all of the input terminal blocks or spade terminals are mounted on the bottom of the
controller and the output terminal blocks and spade terminals are mounted on the top of the controller. See Table 5
for more information about I/O
terminal functions, requirements, and ratings.
Risk of Electric Shock.
Disconnect power from the controller before making any adjustments. Do not touch any part of the printed circuit
board while power is applied. Failure to follow these precautions can result in personal injury or death.
Risque de décharge électrique.
Déconnecter l'alimentation du controller avant toute opération de réglage. Veiller à ne toucher aucune partie du
circuit imprimé lorsque celui-ci est sous tension. Le non-respect de ces précautions peut provoquer des blessures
graves, voire mortelles.
Risk of Electric Shock.
Disconnect or isolate all power supplies before making electrical connections. More than one disconnection or
isolation may be required to completely de-energize equipment. Contact with components carrying hazardous
voltage can cause electric shock and may result in severe personal injury or death.
Risque de décharge électrique.
Débrancher ou isoler toute alimentation avant de réaliser un branchement électrique. Plusieurs isolations et
débranchements sont peut-être nécessaires pour -couper entièrement l'alimentation de l'équipement. Tout contact
avec des composants conducteurs de tensions dangereuses risque d'entraîner une décharge électrique et de
provoquer des blessures graves, voire mortelles.
IMPORTANT: Do not exceed the controller electrical ratings. Exceeding controller electrical ratings can result
in permanent damage to the controller and void any warranty.
IMPORTANT: Use copper conductors with a rating of at least 75°C (167°F). Make all wiring in accordance with
local, national, and regional regulations.
IMPORTANT: Electrostatic discharge can damage controller components. Use proper electrostatic discharge
precautions during installation, setup, and servicing to avoid damaging the controller.

Verasys® 32 Point 24 VAC Application Controller Installation Instructions
6
Factory Wiring
For all the I/O terminals listed in Table 5, use the correct gauge wiring. For each spade terminal in this application,
follow the guidelines in Table 5 and use a spade connector with screw terminals. Figure 3 shows
I/O spade terminals.
Figure 3: Verasys Application Controller Spade Terminals
Field Wiring
For all I/O terminals listed in Table 5, use the appropriate gauge wiring. For each spade terminal in this application,
follow the guidelines in Table 5 and use a spade connector with screw terminals.
Figure 4: Verasys Application Controller Spade Connector with Screw Terminals

Verasys® 32 Point 24 VAC Application Controller Installation Instructions
7
Stacked System and Sensor Bus Terminal Block
Adual-stacked connector serves as the system bus and sensor bus port on the Verasys Controllers. The upper row
on the connector is the system bus port. The lower connector row is the sensor bus port.
Figure 5: Stacked System and Sensor Bus Terminal Block
System Bus Terminal Block
The System Bus terminal block is a blue, removable, 4-terminal plug that fits into a board-mounted jack. Wire the
removable system bus terminal block plugs on the controller on the top row of the stacked connector. Wire the other
field controllers in a daisy-chain configuration using 3-wire twisted, shielded cable, as shown in the following figure.
See Table 7 for more information on functions, ratings, requirements and cables.
Figure 6: System Bus Terminal Block Wiring
Note: The System Bus Shield (SHD) terminal is isolated and you can use it to connect the shields, in a daisy-
chain configuration for system bus wiring.
Sensor Bus Terminal Block
The Sensor Bus terminal block is a brown, removable, 4-terminal plug that fits into a board-mounted jack.
Stranded 3-Wire Twisted Shielded Cable
Isolated Shield
Connection
Terminal
To N ex t
Device on
the System Bus
Segment
System Bus
Terminal
Block Plugs
Terminating Device
on System Bus Segment
To N ex t
Device on
the System Bus
Segment
Daisy Chained Device
on System Bus Segment
SHD
+
COM
SHD
+
COM

Verasys® 32 Point 24 VAC Application Controller Installation Instructions
8
Wire the removable Sensor Bus terminal block plugs on the lower port of the Dual Stacked Connector to the
controller, and other Sensor bus devices in a daisy-chain configuration using 4-wire twisted, shielded cable as
shown in Figure 7. See Table 7 for more information on functions, ratings, requirements and cables.
Figure 7: Sensor Bus Terminal Block Wiring
Note: The Sensor BUS PWR terminal supplies 15 VDC. You can use the PWR terminal to connect, in a daisy-
chain configuration, the 15 VDC power leads on the Sensor bus.
Sensor Bus Port
The Sensor Busport on the middle left side of the controller (Figure 11) is an RJ-12, 6-position modular jack that
provides a connection for the SBH, the VAVBalancing Tool,specified network sensors, or other Sensor Bus devices
with RJ-12 plugs.
The Sensor port connects internally to the Sensor bus terminal block. See Table 7 for more information. The sensor
bus port pin assignment is shown in Figure 8.
Figure 8: Pin Number Assignments for Sensor Bus Ports on Verasys Application Controllers
Modbus Terminal Block
The Modbus terminal block is a green, removable, 3-terminal plug that fits into a board-mounted jack.
Wire the removable Modbus terminal block plugs on the controller, and wire the other field controllers in a daisy-
chain configuration using 3-wire twisted, shielded cable as shown in Figure 9. See Table 7 for more information on
functions, ratings, requirements and cables.
Stranded, 4-Wire (2 Twisted Pair) Shielded Cable
(One twisted pair is the and leads.
+ -
The second pair is COM and PWR.)
Cable Shield
Connection
To N ex t
Device on
the Sensor Bus
Sensor Bus
Terminal
Block Plugs
Terminating Device
on Sensor Bus
Daisy Chained Device
on Sensor Bus
To N ex t
Device on
the Sensor Bus
PWR
+
COM
PWR
+
COM
Power
(15 VDC)
Sensor Bus +
Sensor Bus
-
Bus and Power Common
Power
(15 VDC)
Sensor Bus Port
(RJ-12 Modular Jack)
Bus and Power Common
2
3
4
5
6
1

Verasys® 32 Point 24 VAC Application Controller Installation Instructions
9
The Modbus port communicates as a Modbus device and connects to the Modbus network which can consist of
one-to-many Modbus devices. Each Modbus device has a unique Modbus Register table and you must configure it
within the application of the Verasys Controller.
Figure 9: Modbus Terminal Block
+
COM
Cable Shield
Connection
To N ex t
Device on
the Modbus
Segment
Modbus
Terminal
Block Plugs
Terminating Device
on Modbus
Daisy Chained Device
on Modbus
To N ex t
Device on
the Modbus
Segment
+
COM

Verasys® 32 Point 24 VAC Application Controller Installation Instructions
10
Supply Power Terminal Block
The 24 VAC supply power terminal block is a gray,
removable,3-terminalplugthatfitsintoa board-mounted jack on
the top right of the controller.
Wirethe 24VACsupply powerwires fromthe transformer to the HOT and COM terminals on the terminal plug as
shown in Figure 10. The middle terminal on the supply power terminal block is not used. See Table 7 for more
information about the Supply Terminal Block.
Figure 10: 24VACSupplyPowerTerminalBlock
Note: The supply power wire colors may be different on transformers from other manufacturers. Refer to
the
transformer manufacturer’s instructions and theproject installation drawings for wiring details.
EOL Switch
The red end of line switch (EOL) is located under the cover of the controller. You can set the red EOL switch when
the device is located at the end of the trunk or at the start of the trunk..
To set the end of the line, complete the following steps:
1. Gently pull up on the side of the cover of the controller to access the switch. See ‘8’on figure 11 for the location
of the cover lift tabs. Ensure you do not to pull the ribbon cable from the display membrane that connects to the
display.
2. The red EOL switch is located near the system bus terminal. For location of the system bus terminal, see ‘15’
on Figure 11.
3. Set the switch to ON
Terminal Block
Plug
Wires from
Johnson Controls
24 VAC, Class 2
Power Transformer
Brown Wire
(COM)
Orange Wire
Disconnect supply power to controller by unplugging
Supply Power
Terminal Block
Jack
Supply Power
(24 VAC)
24V~
Supply Power Plug from Supply Power Jack.
HOT
COM
HOT
COM

Verasys® 32 Point 24 VAC Application Controller Installation Instructions
11
Figure 11: LC-VAC300x-0 Physical Features
Table 1: LC-VAC300x-0 Physical Features
Callout Physical Feature: Description and Reference
1USB host port
2Three configurable outputs: 0 to 10 VDC, 10 mA, 24 VAC externally sourced Triac outputs 0.5A(maximum) output
current
3Three mounting clips
4Four Binary Outputs: Relays SPST 5 (3A) (240 VAC), externally powered. Two relays support the selectable
hardware interlocking function. Each relay contact is independent with its own terminal.
5Two binary outputs: 0.5 A Triac (24 or 240 VAC, externally powered). See Table 5
624 VAC utility output power for actuator supply
724 VAC, class 2 power supply terminal block. See the Supply Power Terminal Block section
8Cover lift tabs.
9Sensor Bus Port (RJ-12 6-pin Modular Jack) See Sensor Bus Port section.
10 LED status indicators. See Table 9.
11 Four keypad buttons.
12 Display with backlight.
13 Six Binary Inputs Terminal blocks (IN1–IN6). Dry contact maintained or pulse counter and accumulator mode. See
Table 5.
14 Six Universal Inputs (UI) terminal blocks. Voltage analog input 0–10 VDC. Current analog input 4–20 mA. Resistive
Analog Inputs (0 to 600 ohms) or Dry Contact Binary Input. See Table 5.
15 Dual-Stacked Connector. See the Stacked System and Sensor Bus Terminal Block section.
16 Modbus Communication Port. See Modbus Terminal Block section.
17 PWM 0 to 15 VDC selectable 5V, 12V, and 15V at 10 mA, 100 Hz.
15
4
36
2
8
9
10
8
11
12
314 316
15
7
13

Verasys® 32 Point 24 VAC Application Controller Installation Instructions
12
Termination Details
A set of termination diagrams provide details for wiring inputs and outputs to the controllers. See the tables in this
section for the applicable termination diagrams.
Table 2: Termination Details (Part 1 of 6)
Type of Field
Device Type of Input/Output Termination Diagrams
Resistive Input –
resistance
temperature
detector (RTD)
Monitor
UI
Voltage Input –
External Source UI
Voltage Input –
Internal Source UI
Voltage Input
(Self-Powered) UI
Current Input –
External Source
(Isolated)
UI
RTD
Temperature
Element
Controller
IN#
ICOM#
+
-
FIELD
DEVICE
OUT
COM
POWER
SUPPLY
Controller
IN#
ICOM#
Controller
IN#
ICOM#
+15V
+
-
FIELD
DEVICE
+VDC
Controller
IN#
ICOM#
FIELD
DEVICE
OUT
COM
IN#
ICOM#
Controller
FIELD DEVICE
Signal
Output
+
-
+
-
Power
-
+
Power
Supply

Verasys® 32 Point 24 VAC Application Controller Installation Instructions
13
Current Input –
Internal Source
(2 wire)
UI
Current Input –
Internal Source
(3 wire)
UI
Current Input –
External Source
(in Loop)
UI
Feedback from
EPP-100 UI
Dry Contact
(Binary Input) UI/BI
Table 2: Termination Details (Part 2 of 6)
Type of Field
Device Type of Input/Output Termination Diagrams
Controller
FIELD
DEVICE
+ VDC
Output
+15V
IN#
IN#
ICOM#
+
-
FIELD
DEVICE
+VDC +15V
+
-
Controller
IN#
ICOM#
FIELD
DEVICE
Power
Supply
+
-
ICOM#
IN#
+15V
EPP - 1000
Retracted
Stroked
Wh/Vio
Wh/Org
Wh/Bm
Controller
FIELD DEVICE
ICOM#
IN#
DRY CONTACT
(N.O. N.C.
)
or as
required
Controller

Verasys® 32 Point 24 VAC Application Controller Installation Instructions
14
Binary Inputs
(24V Non-
Critical)
BI
0–10 VDC
Output to
Actuator
(External
Source)
CO
0–10 VDC
Output to
Actuator
(Internal Source)
CO
0–20 mA Output
to Actuator CO
Table 2: Termination Details (Part 3 of 6)
Type of Field
Device Type of Input/Output Termination Diagrams
24VAC
IN #
IC O M #
CONTROLLER
FIELDDEVICE
24VACExternal
PowerSupply
ValidforIN7–IN12
Note: Ifth e24VACExternalPow erSupplyandth e Verasys24VACSupply
arebothgroundedto FunctionalEarth,ensureth a tthephasingbetw eenth e
tw osuppliesarealigned.
HOT
Common
Power
Calibration Output
Current Input
Voltage Input
Feedback
Terminal Block 1
1
2
3
4
5
6
OCOM#
OUT#
Controller
24 VAC COM
24 VAC HOT
Common
Power
Calibration Output
Current Input
Voltage Input
Feedback
Terminal Block 1
1
2
3
4
5
6
OCOM#
OUT#
Controller
24 VAC Com
24 VAC Hot
Add Jumper from 24 VAC COM to
only one AO COM per Transformer
Common
Power
Calibration Output
Current Input
Voltage Input
Feedback
Terminal Block 1
1
2
3
4
5
6
OCOM#
OUT#
Controller
24 VAC Com
24 VAC Hot
Add Jumper from 24 VAC COM to
only one AO COM per Transformer

Verasys® 32 Point 24 VAC Application Controller Installation Instructions
15
0–20 mA Output
to Actuator CO
24 VAC Triac
Output CO
240 VAC Triac
Output BO
24 VAC Triac
Output BO
Table 2: Termination Details (Part 4 of 6)
Type of Field
Device Type of Input/Output Termination Diagrams
Common
Power
Calibration Output
Current Input
Voltage Input
Feedback
Terminal Block 1
1
2
3
4
5
6
OCOM#
OUT#
Controller
24 VAC COM
24 VAC HOT
24VAC
Load
OUT#
OCOM#
CONTROLLER
COM Note: Rated loads of 0.5A
resistive (max)
FIELD DEVICE
240VAC
Load
OUT#-A
OUT#-B
CONTROLLER
COM Note: Rated loads of 0.5A
resistive (max)
FIELD DEVICE
24VAC
Load
OUT#-A
OUT#-B
CONTROLLER
COM Note: Rated loads of 0.5A
resistive (max)
FIELD DEVICE

Verasys® 32 Point 24 VAC Application Controller Installation Instructions
16
240 VAC Relay
Output (SPST)
Note: Specific to
BO 8 and BO 9
BO
240 VAC Relay
Output (SPST)
Note: Specific to
BO 6 and BO 7
(Hardware
Interlock Relays)
BO
See Table 3 for Selectable Operating Modes.
Table 2: Termination Details (Part 5 of 6)
Type of Field
Device Type of Input/Output Termination Diagrams
240VAC
Load
OUT#NO
OCOM#
CONTROLLER
COM Note:RatedloadsperTable.
RefertoBinaryOutput
(Relays).
FIELDDEVICE
240VAC
Load
OUT#
OCOM#
CONTROLLER
COM Note:Ratedloadsof0.5A
resistive(max)
FIELDDEVICE

Verasys® 32 Point 24 VAC Application Controller Installation Instructions
17
240 VAC Relay
Output (SPDT)
Note: Specific to
BO 10
BO
PWM Output to
Drive an EEV PWM
See Table 4 for PWM Output Voltages.
Table 3: Selectable Operating Mode
BO Relay
Number Hardware Jumper State Relay Operating Mode
6 J1.1 and J1.2 J1.2 and J1.3
Open Open BO Relays #6 remains de-energized in default state
(NO), cannot be controlled.
Short Open Normal Operating BO Relay #6
Open Short BO Relay #6 energizes when BI11 is Active
(24 VAC present on BI11).
7 J2.1 and J2.2 J2.2 and J2.3
Open Open BO Relays #7 remains de-engerized in default state
(NO), cannot be controlled.
Short Open Normal Operating BO Relay #7
Open Short BO Relay #7 energizes when BI12 is Active (24
VAC is present on BI12).
Table 2: Termination Details (Part 6 of 6)
Type of Field
Device Type of Input/Output Termination Diagrams
240VAC
Load
OUT#NO
OCOM#
CONTROLLER
COM Note:RatedloadsperTable.
RefertoBinaryOutput(Relays).
FIELDDEVICE
OUT#NC
OUT5PWM
PWMCOM
CONTROLLER
Note:RatedloadsperTable.
RefertoPWMOutput.
FIELDDEVICE

Verasys® 32 Point 24 VAC Application Controller Installation Instructions
18
Terminal Wiring Guidelines, Functions, Ratings, and Requirements
Input and Output Wiring Guidelines
Table 5 and Table 6 provide information and guidelines about the functions, ratings, and requirements for the
controller input and output terminal guidelines for determining proper wire sizes and cable lengths.
In addition to the wiring guidelines in Table 5 and Table 6, use these guidelines when wiring controller inputs and
outputs:
• Run all low-voltage wiring and cables separate from high-voltage wiring.
• All input and output cables, regardless of wire size or number of wires, must consist of stranded, insulated, and
twisted copper wires.
• Shielded cable is not required for input or output cables.
• It is best practice to use shielded cable for input and output cables that are exposed to high electromagnetic or
radio frequency noise.
• Inputs/outputs with cables less than 30 m (100 ft) typically do not require an offset in the software setup. Cable
runs over 30 m (100 ft) may require an offset in the input/output software setup.
Table 4: Selectable PWM Output Voltage
Hardware Jumper State PWM Output Voltage
J3.1 and J3.2 J3.2 and J3.3
Open Open 5 V
Short Open 12 V (Default)
Open Short 15 V

Verasys® 32 Point 24 VAC Application Controller Installation Instructions
19
Table 5: Controller Terminal Blocks, Functions, Ratings, Requirements, and Cables (Part 1 of 4)
Terminal Block
Label Terminal Label Function, Ratings, Requirements Determine Wire Size and Maximum
Cable Length1
Universal
(Inputs) +15 V 15 VDC Power Source for active
(3-wire) input devices connected to
the Universal INnterminals;
provides 80 mA total current.
Note: 80mA current limit is shared
between the BI + 15V supply and the
UI + 15V supply.
Same as (Universal) INn
Note: Use 3-wire cable for devices
that source power from the +15V
terminal.
COM 15 VDC Power Source for active
(3-wire) input devices connected to
the Universal INnterminals;
provides 80 mA total current.
Note: 80mA current limit is shared
between the BI + 15V supply and the
UI + 15V supply.
Same as (Universal) INn
INnAnalog Input - Voltage Mode (0–10
VDC)
10 VDC maximum input voltage
Internal 67k ohm pull-down
See Guideline Ain Table 6.
Analog Input - Current Mode
(4–20 mA)
Internal 100 ohm load impedance
See Guideline Bin Table 6.
Analog Input - Resistive Mode
(0–600k ohm)
Internal 12 V.15k ohm pull-up
Qualified Sensors: 0–2k ohm
potentiometer
RTD (1k Nickel [Johnson Controls
sensor] 1k Platinum, and A99B
Silicon Temperature Sensor)
Negative Temperature Coefficient
(NTC)Sensor(10kType L, 10k JCI
Type II, 2.252k Type II)
See Guideline Ain Table 6.
Binary Input - Dry Contact
Maintained Mode
1 second minimum pulse width
Internal 12 V. 15k ohm pull up
See Guideline A in Table 6.
ICOMnUniversal Input Common for all
Universal Input terminals Same as (Universal) INn

Verasys® 32 Point 24 VAC Application Controller Installation Instructions
20
BINARY
(Inputs)
(Dry)
INnBinary Input - Dry Contact
Maintained Mode
0.01 second minimum pulse width
Internal 17 V. 100k ohm pull-up
See Guideline Ain Table 6.
Binary Input - Pulse Counter/
Accumulator Mode
0.01 second minimum pulse width
(50 Hz at 50% duty cycle)
Internal 17 V. 100k ohm pull-up
ICOMnBinary Input Common for all Binary
Input (IN) terminals
Note: Binary ICOMnare all internally
interconnection and interconnected
with the controller’s power supply
COM. (ICOM1-2-3, ICOM4-5-6,
ICOM7-12, and COM).
BINARY
(Inputs)
(24VAC non-
critical)
INnBinary Input - 24 VAC Non-Critical
Mode
24 VAC Input Present: Logic 1
(Active)
ICOMnBinary Input Common for all Binary
Input (IN) terminals
+15 V 15 VDC Power Source for active
(3-wire) input devices connected to
the Universal INnterminals;
provides 80 mA total current.
Note: 80mA current limit is shared
between the BI + 15V supply and the
UI + 15V supply.
Same as Binary INn
Note: Use 3-wire cable for devices
that source power from the +15V
terminal.
COM 15 VDC Power Source for active
(3-wire) input devices connected to
the Universal INnterminals;
provides 80 mA total current.
Note: 80mA current limit is shared
between the BI + 15V supply and the
UI + 15V supply.
Same as Binary INn
Table 5: Controller Terminal Blocks, Functions, Ratings, Requirements, and Cables (Part 2 of 4)
Terminal Block
Label Terminal Label Function, Ratings, Requirements Determine Wire Size and Maximum
Cable Length1
Table of contents
Other Verasys Controllers manuals
Popular Controllers manuals by other brands

Shenzhen FeiCan Technology Co.
Shenzhen FeiCan Technology Co. FC-PB-WIFI03 user manual

Deltran
Deltran Battery Tender Solar Charger Controller instruction manual

Ltech
Ltech LT-3900 quick start guide

Swagelok
Swagelok TBVS4 user manual

SM Pro
SM Pro Active-1 operating manual

Belimo
Belimo LF24-SR US quick start guide

TechWind
TechWind SDK-500 user manual

O. Thompson
O. Thompson Microflite Ultra 2000 Installation & Adjustment Manual

Siemens
Siemens RWD44U Installation and commissioning guide

BRT Systems
BRT Systems PANL user guide

Hayward
Hayward Aqua Plus® installation manual

Johnson Controls
Johnson Controls Penn P216 Series installation instructions