Vicon V1300X-IA Programming manual

v
VICON
7c
NOTES SHEET REV.
SEC.
SUPERSEDES INSTRUCTION
MANUAL X849-894 X849 1297 11
INSTRUCTIONS FOR
L
INSTALLATION AND OPERATION
MODEL VI 300X-IA ALARM INTERFACE
1. INTRODUCTION
The information in this manual covers the installation, program, and displaying a special alarm message on the
operation and maintenance of the V13OOX-IA Alarm Inter-
alarm monitors. The green ALARM LED on the front
face. This unit should only be installed by a qualified panel of the
V13OOX-IA
illuminates when there is an
technician using approved materials and wiring practices in
active alarm in the unit, and the unit generates a warning
conformance with national, state, and local electrical codes.
tone. The tone may be disabled.
The
V13OOX-IA
Alarm Interface
allies
extkmal
alarm
devices to be connected to Vicon Nova (VPS ) systems.
In the basic configuration, up to 32 alarms may be con-
nected to a single
V13OOX-IA,
while an expanded unit
(V13OOX-IA-EX) accepts up to 64. Multiple V13OOX-IAs
may be cascaded together for further expansion. In this
manual, the model number
V13OOX-IA
is used to desig-
nate all models, unless specified otherwise. Refer to Table
1 for all model variations.
Acknowledging individual alarm inputs is performed
from the operator control panel. Enabling and disabling
individual alarm inputs can be done by software in the
system CPU. The V1300X-IA is compatible with all
Nova VPS digital control
CPUs.
It connects to them with
a parallel data interface.
Both models are compatible with the earlier V1200X-IA
alarm interface and with the current V1300X-IAF alarm
interface with relay follow. The V1300X-IAF provides
an individual relay closure output for each alarm input.
A single auxiliary relay output activates when any alarm
input goes active. This relay may be used to control some
external device, such as a VCR. In the case of multiple
cascaded X-IAs, only the auxiliary output on the X-IA
that received the alarm goes active. The aux outputs on
the other X-IAs do not go active.
Up to four
V13OOX-IA-EX
units may be cascaded in a
daisy-chain to provide a maximum of 256 alarm inputs on
a single CPU trunk line. Alternatively, up to eight of the
basic V13OOX-IAs may be cascaded to provide 256 inputs.
When used with the
VPS1300
system, up to four groups
of daisy-chained
V13OOX-IAs
may be connected to the
CPU, depending on the CPU configuration.
The alarm inputs may be configured as normally closed
or normally open using on-screen programming in the
Nova CPU. Alarm inputs are CMOS/TTL compatible.
The V1300X-IA complies with FCC rules for a Class A
digital device.
TABLE 1
MODELS AND PRODUCT CODES I
When the V13OOX-IA senses a change in the status of one
of its alarm inputs, it transmits the information to the Nova
CPU, which announces the alarm to the operator and which
may also execute a preprogrammed response to the alarm.
Such responses include displaying the video from the
camera associated with the alarm on selected alarm moni-
tors, causing a camera station to carry out a preset-position
Model
Number Product
Code Description I
WARNING: TO PREVENT RISK OF FIRE OR ELECTRIC SHOCK, DO NOT EXPOSE THIS UNIT TO RAIN OR MOISTURE.
Product specifications subject to change without notice. Vicon part number 8006-8849-01-00
Copyright
0
1997 Vicon Industries Inc. All rights reserved. Vicon and its logo are registered trademarks of Vicon Industries Inc.
VICON INDUSTRIES INC. 89 ARKAY DRIVE, HAUPPAUGE, N.Y. 11788. TEL:
516-952~CCTV
(2288). FAX:
516-951~CCTV
(2288)
TOLL FREE: i-800-645-91 16 l UK:
44/(O)
1489/566300
l INFOFAX: l-800-287-1207 l WORLD WIDE WEB:
www.vicon-cctv.com

IMPORTANT SAFEGUARDS
GRAPHIC SYMBOL EXPLANATION
The lightning flash with arrowhead symbol, within an equilateral
triangle, is intended to alert the user to the presence of uninsulated
“dangerous voltage” within the product’s enclosure that may be of
sufficient magnitude to constitute a risk of electric shock.
Theexclamation pointwithin an equilateral triangle is intended
toalert
the user to the presence of important operating and maintenance
(servicing) instructions in the literature accompanying the unit.
I.
Read Instructions
-All the safety and operating instructions should
be read before the video product is operated.
2. Retain Instructions-All
the safety and operating instructions should
be retained for future reference.
3. Heed Warnings
-
All warnings on the video product and in the
operating instructions should be adhered to.
4. Follow Instructions -
All operating and use instructions should be
followed.
5. Cleaning
-
Step a applies to equipment that can be disconnected
from the CCTVsystem without seriously jeopardizin7security. Step b
applies to equipment that must operate continuous y such as video
switching equipment at military installations.
a. Disconnect this video product from its power source before
cleaning. Do not use caustic, abrasive, or aerosol cleaners. Use
a damp cloth for cleaning.
b. Use a damp cloth to clean the equipment. Do not allow
moisture or liquids to enter any vents. Do not use caustic,
abrasive, or aerosol cleaners.
6. Attachments -
Do not use attachments not recommended by Vicon
as they may cause hazards.
7. Water and Moisture
-
Do not use this video aroduct in anv location
where it may be exposed to water or moisture: This does ndt apply to
outdoor camera housings, outdoor pan-and-tilt drives, and other
equipment designed for direct exposure to outdoor environments.
8.Accessories-Donotplacethisvideoproductonanyunstablesurface
or table. The video product may fall, causing serious injury to a person
and serious damage to the video product. Use onl
accessory recommended by Vicon, or sold with t
1:
with a mounting
e video product.
Any mounting of the video product should fol low Vicon’s instructions,
and a mounting accessory recommended by Vicon should be used.
9. Ventilation
-
Slots and openings in the cabinet are provided for
ventilation and to ensure relrable operation of the video product and
to protect it from overheating, and ttieseopenin
or covered. The openings should never be b
ocked
by
placing the
P
smust not be blocked
video cp
roduct on a ru
shoul never be olace 8
&
other similar surface. This video product
near or over a radiator or heat register. This
video product should not be placed in a built-in installationvsuch as a
bookcase or rack unless proper ventilation is provided or Vicon’s
instructions have been adhered to.
10.
Power Sources
-This video product should be operated only from
the type of power source indicated on the marking label. If you are not
sureofthetypeofpowersupplied to your installatronsite,consuItyour
Vicon dealer or local power company. For video products intended to
operate from battery power, or other sources, refer to the operating
instructions.
11. Grounding-This
applies to video products equi ped with a
3-wire
grounding-type plug, a plug having a third fgroun rng) pm. This plugcl!
only fits into a groundin
you areunableto inserttI! -type power outlet. This is a safety feature. If
epluginto theoutlet, contactyourelectrician
to replace your obsolete outlet. Do not defeat the safety purpose of the
grounding-type plug.
12. Power-Cord Protection -
Power suoolv cords should be routed so
that they are not likely to be walked
on
or
pinched by items placed
upon or against them,
payin
convenience receptacles, an
B
particular attention to cords at plugs,
the porntwhere theyexitfrom
thevideo
product.
13.0utdoorCableGrounding-
Ifanoutsidecablesystem isconnected
to the video product, be sure the cable system is grounded so as to
provide some protection against voltage surges and built-up static
A
AL
CAUTION: TO REDUCE THE RISK OF ELECTRICAL SHOCK,
DO NOT REMOVE COVER (OR BACK). NO USER-
SERVICEABLE PARTS INSIDE. REFER SERVICING
TO QUALIFIED SERVICE PERSONNEL.
charges. Section 810 of the National Electrical Code,
ANSI/NFPA
70-l
984, provides information with respect to proper grounding of the
lead-in wire to an antenna discharge unit, size of grounding conduc-
tors, location of antenna-discharge unit, connection to grounding
electrodes, and requirements for the grounding electrode.
14. Lightnin7-
not used for For added protection for this video product when it is
ong periods of time, disconnect it from its power source
and from the cable system. This prevents damage to the video product
due to lightning and power-line surges.
15. Power Lines
-
An outside cable system should not be located in
the vicinity of overhead
P
ower lines or other electric light or ower
circuits, or where it can all
Into
such power lines or circuits.
R
hen
installing an outside cable system, extreme care should be taken to
kee from touching such power lines or circuits as contact with them
mrg t be fatal.
3
16. Overloading
-
Do not overload wall outlets and extension cords
as this can result in a risk of fire or electric shock.
17. Object and Liquid Entry
-
Never push objects of any kind into this
video product through openings as they may touch dangerous volta
e
points or short out
Never spill liquid o
Parts that could result in a fire or electric shot1
.
any kind on the video product.
18. Servicing
-
Do not attempt to service this video product yourself
as opening or removing covers may expose ou to dangerous voltage
or other hazards. Refer all servicing to qualr red service personnel.
4
19. Damage Requiring Service
-
Disconnect this video product from
its power source and refer servicing to qualified service personnel
under the following conditions. Note that step c does not apply to
outdoorcamera housings,
outdoorpan-and-tiltdrivesandotherequip-
ment specifically designed for direct exposure to outdoor environ-
ments.
a. When the power-supply cord or plug is damaged.
b.
If
Ii
%
uid has been spilled, or objects have fallen into the video
pro uct.
c. If the video product has been exposed to rain or water.
d. If the video product does not operate normally b following the
operatin
ered by t e operating instructions, as an impro
5
instructions. Adjust only those
contra
s that are
cov-
Y
er adjustment
of other controls may result in damage and WI I often require
.P
extensive work by a qualified technician to restore the
video
product to its normal operation.
e. If the video product has been dropped or the cabinet has been
damaged.
f. When the video product exhibits a distinct change in perform-
ance
-
this indicates a need for service.
20. Replacement Parts-When
replacement parts are required, be sure
the service technician has used replacement parts specrfied b Vicon
or that have the same characteristics as the original part. Unaut1onzed
substitutions may result in fire, electric shock, or other hazards.
21. Safety Check
-
Upon completion of any service or repairs to this
video product, ask the service technician to perform safety checks to
determine that the video product is in proper operating condition.
2
X849- 1297

This equipment generates and uses radio frequency en-
ergy
andif
not installed and used properly, that is, in strict
accordance with the manufacturer’s instruction, may
cause interference to radio and television reception. It has
been type tested and found to comply with the limits for
a Class A digital device in accordance with the specifi-
cation in subpart B of part 15 of the FCC rules, which are
designed to provide reasonable protection against such
interference in a commercial installation. However, there
is no guarantee that interference will not occur in a
particular installation, If this equipment does cause inter-
ference to radio and television reception, which can be
determined by turning equipment off and on, the user is
encouraged to try and correct the interference by one or
more of the following measures:
Reorient the receiving antenna.
Relocate the equipment with respect to the receiver.
If necessary, the user should consult the dealer or an
experienced radio/television technician for additional
suggestions.
The user may find the following booklet prepared by the
Federal Communications Commission helpful:
“How to identify and resolve radio-TV interference
problems” This booklet is available from the U.S. Gov-
ernment Printing Office, Washington D.C. 20402, Stock
No. 004-000-00345-4.
WARNING: Power must be removed from this
A
unit before removing circuit modules or ribbon
cables.
CAUTION:
This unit contains circuit cards with
A
integrated circuit devices that can be damaged
2. INSTALLATION
2.1 Unpacking and Inspection
All Vicon Equipment is inspected and tested before 2.1.2 INSPECTION FOR CONCEALED
leaving the factory. It is the carrier’s responsibility to
DAMAGE
FCC NOTICE
WARNING
NOTE: Complies with Federal Communications
Commission Rules
&
Regulations Part
15,
Subpart
B for a Class A digital device.
Relocate the equipment away from the receiver.
Plug the equipment into a different electrical outlet so
that the equipment and receiver are on different branch
circuits.
deliver the equipment in the same condition in which it
left the factory.
2.1.1 INSPECTION FOR VISIBLE DAMAGE
Immediately inspect the cartons upon delivery. On all
copies of the carrier’s freight bill, make a note of any
visible damage.
Make sure the carrier’s agent (the person making the
delivery) signs the note on all copies of the bill. If the
agent does not have claim forms, contact the carrier’s
office.
As soon as possible after delivery, unpack the unit and
inspect it for concealed damage. Do not discard the carton
or packing materials. If the unit is damaged, contact the
carrier immediately and request forms for filing a damge
claim. Make arrangements for a representative of the
carrier to inspect the damaged equipment.
If the equipment must be returned for repair, follow the
Shipping Instructions at the end of this document.
2.1.3 ACCESSORY KIT
Table 2 lists the
accesories
included with the unit. Verify
that all the listed accessories are present. In addition to
these accessories, four screws of a type suitable to attach
the unit to the EIA rack are required. These are com-
monly No. lo-32 screws, but individual rack manufac-
turers may use other types.
X849-1297
3

TABLE 2
ACCESSORIES
2.2 Setting Addresses
CAUTION: Make sure there is no power to the
A
V13OOX-IA
before performing the following
procedure.
Each
V1300X-IA
must be addressed. This process iden-
tifies the range of alarm numbers to be input into each
unit. Defining the address of the unit is done by setting
DIP switches inside the unit.
To access the addressing DIP switches, remove the top
cover of the unit. Remove five screws from the top of
the cover and six screws from the rear of the cover to
free the cover. Refer to Figure 1. There may be two or
four DIP switches. The basic 32-input model has one
large printed circuit board (PC board), while the ex-
panded 64-input model has two large PC boards. The
lower board is designated the master, and the upper
board is the slave or expansion board. The address DIP
switches are mounted on these boards, each board hav-
ing two address switches. Refer to Figure 2 for the
location
ofthe
switches. The switches on the lower board
are labelled ADDRESS 1 and ADDRESS 2 on the PC
board next to the switch. The switches on the upper board
are labelled ADDRESS 3 and ADDRESS 4.
DIP switches may be labelled in different ways. Some-
times the words OPEN and/or CLOSED are used, but
ON and/or OFF are used more often, These terms are
defined:
ON = CLOSED
OFF = OPEN
0 0 0
TOP
Figure 1
V1300X-IA Top and Rear Covers
X849- 1297

Master PC Board
0
ADDRESS 2
III
ADDRESS 1
Front
Slave or expansion
PC board
(
ADDRESS4n
~A-=(
Front
Figure 2
Location of DIP Switches
An arrow is often marked on the switch to indicate the
direction of the
labelled
switch status (ON, OFF, OPEN,
CLOSED). Each address DIP switch has four individual
poles that must be set, and the poles are numbered
l-
4.
The location of pole 1 is marked on the PC board next
to the switch. Refer to Tables 3 through 6 for the correct
settings for the address DIP switches. To keep the tables
as simple and clear as possible, only the ON status is
marked. A dash means OFF or OPEN.
TABLE 3
SETTING ADDRESS SWITCH 1
CAUTION:
A
Do not set any two of the switches the
same. The unit will not function.
When the address DIP switches have been set, replace
the cover on the
V13OOX-IA.
TABLE 4
SETTING ADDRESS SWITCH 2
Address Pole Number
Range
1
2 3 4
Address Pole Number
Range
1
234
I
l--lfi
I
----
I
33-48
-
ON
--
65-80
--
ON
-
97-112
-
ON
ON
-
129-144
-- -
ON
181-176
-
ON
-
ON
193-208
--
ON
ON
225-240
-
ON
ON ON
TABLE 5
SETTING ADDRESS SWITCH 3
Address Pole Number
Range
11
2
3
4
17-32 ON
- -
-
49-64 ON ON
--
81-96 ON
-
ON
-
113-128 ON ON ON
-
145-160 ON
-
-
ON
177-192 ON ON
-
ON
209-224 ON
-
ON ON
241-256 ON ON ON ON
TABLE 6
SETTING ADDRESS SWITCH 4
X849-1297
5

2.3 Physical Installation
This unit may be installed in an EIA-standard
19-inch
(48.3-cm)
instrument rack or it may be mounted on a
desktop or other flat surface.
2.3.1 RACK MOUNTING
2.3.1.1 General Considerations
Observe the following guidelines when mounting this
unit in an instrument rack:
1.
Plan the layout of the equipment in the racks before
installing equipment.
2.
Take an inventory of all rack equipment including
hardware, brackets, blank panels, etc. Reorder any
missing parts immediately. This avoids delays in the
middle of the assembly process.
3. Provide a minimum of 1.75 inches (4.4 cm) of
empty space between each piece of equipment for
ventilation.
4.
Use at least one blower/fan per rack. Place it in the
bottom of the rack. Thus, air is drawn in at the
bottom of the rack and vented at the top.
2.4 Wiring the Alarm Inputs
Make sure there is no power to the
V13OOX-IA
before performing the following
procedure.
Alarm inputs are wired to removable 16-pin screw terminal
blocks on the rear of the V13OOX-IA. Units with 32 inputs
have one row of four of these connectors along the lower
part of the rear panel
(TBl-TB4).
Expanded units with 64
inputs have two rows of connectors, the upper row being
numbered from 33
-
64
(TB7-TBlO).
Wiring of these
connectors may be done with the terminal block either
mounted on the unit or removed from it. Refer to Figure 3.
Each alarm input has two wires, one of which is a ground.
Note on the rear panel that each alarm number has a +
2.3.1.2 Installing the Unit in a Rack
1.
2.
3.
Find the two rack-mounting brackets (Table 2, item
2) and the four flat-head screws (item 1) in the
accessory kit.
Attach one of the brackets at each end of the unit
with two screws. The long side of the bracket goes
against the side of the unit. Repeat for the other
bracket.
Slide the unit and secure it in place with four screws.
These screws must be supplied by the installer, as
different racks have different screw requirements.
2.3.2 Desk-Top Installation
In desk-top installations, the rack-mounting brackets in
the accessory kit are not used.
1.
Turn the unit upside-down on a soft surface so that
the top of the unit is not scratched.
2.
Find the four rubber feet in the accessory pack. Peel
the covering paper from one of the feet and attach
to the bottom of the unit near one corner. Place it
about l-inch in from the two edges. Repeat for the
other 3 rubber feet.
3.
Turn the unit right-side up and place it where desired.
terminal and a
-
terminal. The plus (+) terminal should
receive the active or “hot” wire from the alarm device,
and the ground wire should be connected to the adjacent
terminal marked minus
(-).
Back out the appropriate
screw on the terminal block one or two turns and insert
the wire in the opening toward the bottom of the block.
Tightening the screw clamps the wire in place. Repeat
for all alarm inputs.
All card cages have the same numbering ranges, 1
-
32 for
the lower connectors and 33
-
64 for the upper connectors.
If more than one
V13OOX-IA
are cascaded together, the
additional units have higher-numbered input ranges. Tables
7 and 8 show the alarm address number versus the
labelled
number on the connector.
6
X849-1297

0
6
0
2
0
IAlarm input connectors V1300X-IA. 0
4Control IN from CPU or previous V1300X-IA
@
Additional alarm input connectors for VI 300X-IA-EX.
@
Control OUT to next V1300X-IA
Shown with cover plate in place. 0
6IEC320 power cord socket and fuse tray
0
3Dry contact relay connector
Figure 3
V13OOX-IA
Rear Panel
2.5 Wiring the Relay Output
The connector for the dry contact relay output is located
on the lower right-hand side of the rear panel and is
marked TB6. Refer to Figure 3. It is the same type of
connector used for the alarm inputs, except smaller. It
may be wired in a normally closed or normally open
configuration. The electrical specifications of the dry
contact relay are 1 .O amp at 24 VDC or 0.5 amp at 120
VAC. The labelling on the rear panel for the relay output
has the following meaning:
NC: Normally closed
C: Common or ground
NO: Normally open
Connect the two wires from the auxiliary equipment
(such as a VCR) to two of the three terminals depending
on the action required by the auxiliary equipment. C is
connected in both configurations.
2.6 Control Cable Connection
The V1300X-IA and V1300X-IA-EX are compatible
with all Vicon Nova CPUs. The two models may be
mixed in a system, and they may also be used with the
older V 1200X-IA alarm interface units.
2.6.1 CONNECTING THE V1300X-IA TO
THE CPU
The V1300X-IA is controlled by an external CPU and
is connected to it with a cable supplied with the CPU.
CAUTION:
A
Make certain there is no power to the
VI
300X-IA or to the CPU before performing the
following procedures.
NOTE: Use only the cable supplied with the CPU
for connection to the first
VI
300X-IA.
X849-1297
7

1.
Find the cable with two 37-pin D-shell connectors
in the CPU’s accessory kit.
NOTE:
Check the cable supplied with the CPUfor
labels indicating which end is to be connected to the
CPU and which is to be connected to the X-IA. Cables
supplied with some CPUs are not marked this way,
and in these cases, either end may be connected to
either device.
2. Connect one end of the cable to the control IN
connector on the V1300X-IA, and secure it with
two screws. See Item 4 on Figure 3.
3.
Connect the other end of the alarm interface con-
nector on the CPU, and secure it with two screws.
The screws may be installed on the cable already or
may be supplied as a separate item. Refer to the
CPU manual for the location of the CPU’s alarm
interface connectors.
2.6.2 CONNECTING THE V1300X-IA TO
ADDITIONAL V1300X-IAS
1. Connect the end of the adapter with the 34-pin
rectangular connector to the
V1200X-IA
and secure
it with the locking screw.
If more than one X-IAs are cascaded together, the cable
2.
Connect one of the 37-pin D-shell connectors on the
supplied with each X-IA is used to connect the X-IA cable to the outboard end of the cable adapter and
card cages to each other. secure it with two screws.
1.
Find the control cable in the X-IA accessory kit. It
has a 37-pin D-shell connector on each end.
2.
Connect one end of the cable to the 37-pin D-shell
connector labeled “OUT’ on the X-IA that is closer
to the CPU. Refer to Figure 3, Item 5. Secure it with
two screws.
3.
Connect the other end of the cable to the 37-pin
D-shell connector labeled “IN” on the next unit in
line and repeat for all units. No more than eight
V1300X-IAs or four V1300X-IA-EXs can be con-
nected together on a single trunk line. Some CPUs
have more than one trunk line for alarm interface
units.
2.6.3 CONNECTING V1300X-IA UNITS TO
V1200X-IA UNITS
A connector adapter is required to connect the V13OOX-
IA to V1200X-IA alarm interface units. This connector
is provided in the accessory kit of the V1300X-IA.
3.
Connect the other end of the control cable to the
V1300X-IA
and secure with two screws.
2.7 Power Cable Connection
The V1300X-IA is provided with an IEC320 recessed
power connector and a detachable power cord. Locate
the IEC320 connector on the upper left side of the rear
panel, and securely plug the power cable into it. Connect
the other end of the power cable to an appropriate power
source.
3. OPERATION
The V1300X-IA is not operated directly, except for
enabling or disabling the alarm tone. However, it is very important to program the CPU as described in the next
section before the unit is put into use.
3.1 Programming the CPU
When using one or more
V13OOX-IA
units with any of
the VPS
NovaCPUs,
it is necessary to disable the remote
acknowledge function in the CPU on-screen menus.
This must be done for any system using a V1300X-IA
or V1300X-IA-EX, even if there is a mixture of alarm
interfaces including the older V1200X-IA.
(The previous alarm interface model, the V1200X-IA,
had a front-panel button that allowed alarms to be
acknowledged at the V1200X-IA. In contrast, all alarm
inputs to the V1300X-IA and V1300X-IA-EX are
ac-
knowledged through the operator keypad or automat-
ically by the CPU, so that no acknowledgement button
is provided.)
8
X849-1297

3.1.1 Programming with On-Screen Menus
1.
2.
I
3.
4.
To perform this programming function, bring the
Main Menu up on screen following instructions in
the CPU Programming Manual. Different CPU
models may display this information in slightly
different formats.
Select ALARM FUNCTIONS, which will display
the Alarm Functions Menu.
Select X-IA ENABLE/DISABLE, which will dis-
play the X-IA Enable/Disable Menu.
Select SET ACK. ENA/DIS to display the program-
ming screen for the acknowledge enable/disable.
Follow the on-screen instructions to change EN-
ABLED to DISABLED.
3.1.2 Programming With ProTech Graphic
Configurator
The menu bar in the
ProTech
Graphic Configurator
conforms to standard
WindowsTM
operational proce-
dures.
1.
Click on CONFIGURATION in the menu bar, then
click on ALARM. A list of three alarm screens will
be displayed.
2.
Click on SET AND EXPLAIN ALARM MODES.
3.
In the area labeled ALARM OPTIONS, if there is
an X in the box labeled ENABLE XIA ACKNOW-
LEDGE, click on the box to make the X disappear.
This disables X-IA acknowledgement.
3.2 Front Panel Features
The V1300X-IA has two LEDs and one slide switch on
its front panel. Their functions are: Red LED: indicates
that power is supplied to the unit; Green LED: indicates
that one or more alarms is in progress; Slide Switch:
turns the audio alarm tone on or off.
4. MAINTENANCE
The V1300X-IA requires no scheduled maintenance. If
it is necessary to change the fuse, locate the IEC320
connector on the rear panel (Figure 3). Remove the
power cord from the connector and slide out the fuse
drawer using a fingernail or small screwdriver.
Remove the old fuse and place a new fuse in the clip.
Replace the fuse drawer and reconnect the power cord.
The correct fuse value is indicated in a triangle on the
rear panel next to the fuse drawer. One triangle shows
the rating for a fuse used with a
120-VAC
unit; the other
triangle shows the fuse rating for 230-VAC units.
5. SPECIFICATIONS
OPERATIONAL
Alarm Inputs:
Alarm Input Mode:
Alarm Outputs:
V1300X-IA:
32.
Vi
300X-IA-EX: 64.
When used with
VPS1300
or
VPS1344CPU: normally closed (NC).
When used with VPS1444, VPS1466,
or VPS1400 CPU: software program-
mable through the CPU as normally
closed (NC) or normally open (NO).
(1) Signal sent to CPU when alarm
input is detected.
(2) Dry contact relay activated.
(3)
Green LED on front panel illumi-
nates.
(4) Au;;b$tone is generated, if
Dry Contact Relay
Output Mode:
ELECTRICAL
Input Power:
Power Consumption:
Input Signal:
Dry Contact Relay Rating:
Can be wired either NO or NC.
V1300X-IA:
120
V,
60 Hz.
V1300X-IA-230: 230 V, 50 Hz.
15w.
Secured: contacts closed (NC) or TTL
active low.
Active low = 0.0 to 0.7
V.
Alarmed: contacts open (NO) or TTL
active high.
Active high
=
2.7 to 5.3
V.
Dry contacts rated at: 1
.O
A at 24 VDC
or 0.5 A at 120 VAC.
X849-1297
9

Fuse:
Fuse location:
Radio Frequency
Emission Standard:
INDICATORS
Power:
Active Alarm:
CONNECTORS
Alarm Inputs:
Control Input/Output:
120 VAC model: 0.75 A, 250
V,
5x20mm.
230 VAC model: 0.5 A, 250
V,
5 x 20 mm.
In drawer built into power cord con-
nector on rear panel.
FCC Class A.
Red LED on front panel.
Green LED on front panel and
audible tone.
Four or eight 16-pin removable screw Operating Humidity
terminal blocks.
Range:
Two 37-pin D-shell connectors.
Dry Contact Relay Output:
Power:
MECHANICAL
Dimensions:
Weight:
Construction:
ENVIRONMENTAL
Operating Temperature
Range:
3-pin removable screw terminal block.
Detachable 3-conductor cable with
grounded plug.
Height: 3.47 in. (8.81 cm).
Width: 19.0 in. (48.3 cm).
Depth: 7.00 in. (17.8 cm).
8.4 lb (3.8 kg).
Steel.
32 to 122” F (0 to 50” C).
Up to 90% relative, noncondensing.
Shipping Instructions
Use the following procedure when returning a unit
to the factory: 2.
Attach a sheet of paper to the unit with the fol-
lowing information:
1.
Call or write Vicon for a Return Authorization
(R.A.) at one of the locations listed below. Record a.
the name of the Vicon employee who issued the
R.A.
b.
VICON INDUSTRIES INC.
89 Arkay Drive C.
Hauppauge, New York 11788
5 16-952-CCTV (2288) or toll free l-800-645-91 16
Fax: 5 16-95 l-CCTV (2288)
For service or returns from countries in Europe,
contact
VICON INDUSTRIES (U.K.) LTD
Name and address of the company returning
the unit
Name of the Vicon employee who issued the
R.A.
R.A. number
Brief description of the installation
Complete description of the problem and
circumstances under which it occurs
Unit’s original date of purchase, if still under
warranty
Brunel Way
Fareham, PO15 5TX
United Kingdom
44/(O)
1489/566300 Fax:
44/(O)
14891566322
3. Pack the unit carefully. Use the original shipping
carton or its equivalent for maximum protection.
4. Mark the R.A. number on the outside of the
carton on the shipping label.
10
X849-1297

TABLE 7
CONNECTOR NUMBER VS. ALARM ADDRESS, LOWER CONNECTOR ROW (TBI-TB4)
X849-1297
11

TABLE 8
CONNECTOR NUMBER VS. ALARM ADDRESS, UPPER CONNECTOR ROW (TB7-TBlO)
IConnector Number IAlarm Nos. IAlarm Nos. Alarm Nos.
97-128
181
-
192 225
-
256
I
12 X849-1297
This manual suits for next models
3
Table of contents
Other Vicon Security System manuals
Popular Security System manuals by other brands

Whelen Engineering Company
Whelen Engineering Company 295HFSC9 installation guide

Vacron
Vacron SA-650CF user manual

Skov
Skov DOL 2300 Technical user guide

Whelen Engineering Company
Whelen Engineering Company RB6T installation guide

Uniden
Uniden UDVR45x4 user guide

Tunstall
Tunstall Premier 1000 user manual