manuals.online logo
Brands
  1. Home
  2. •
  3. Brands
  4. •
  5. Viking
  6. •
  7. Irrigation System
  8. •
  9. Viking HORIZON MIRAGE Instruction manual

Viking HORIZON MIRAGE Instruction manual

1. PRODUCT NAME
Viking Horizon®Mirage®Quick Re-
sponse Extended Coverage Concealed
Pendent Sprinklers
•Model B-1 Standard Orifice Sprin-
kler Base Part No. 08498
Available since 1993
•ModelB-2LargeOrificeSprinklers:
A. Base Part No. 10485
Available since 1998
B. Base Part No. 10680
Available since 1999
•CoverPlateAssemblyPartNo.0980 4
Available since 1996
2. MANUFACTURER
The Viking Corporation
210 N. Industrial Park Road
Hastings, Michigan 49058 U.S.A.
Telephone:(616) 945-9501
(877) 384-5464
Fax:(616) 945-9599
e-mail: [email protected]m
3. PRODUCT DESCRIPTION
Viking Horizon®Mirage®Quick Re-
sponse Extended Coverage Concealed
PendentSprinklersaresmall,solderlink
and lever spray sprinklers designed for
installation on concealed pipe systems.
Equipped with a special deflector, the
sprinkler is designed to meet Light-Haz-
arddensityrequirementsforspecificex-
tended areas of coverage when the re-
quired minimum water supply is pro-
vided at the sprinkler.
After the sprinkler system has been
tested and the ceiling finish applied, the
sprinkler is hidden from view by a low-
profile, small diameter cover plate, in-
stalled flush to the ceiling. The cover
plate is available in several decorative
finishes to meet design requirements.
The “push-on”, “thread-off” design allows
foreasyinstallationofthecoverplate,with
up to 1/2" (12,7 mm) of vertical adjust-
ment.The“thread-off”featureis designed
to prevent unwanted disengagement of
the cover assembly. The cover assembly
can be removed and reinstalled to permit
temporary removal of ceiling panels with-
out taking the sprinkler system out of ser-
vice and removing the sprinkler .
Inside the body of the Horizon®Mirage®
Quick Response Extended Coverage
Concealed Sprinkler, the deflector and
sealing assembly are held in position by
a fast-acting heat-sensitive fusible link.
The sprinklers are listed as quick re-
sponse sprinklers when installed ac-
cordingtothelisted16ft.x16ft.(4,9mx
4,9 m) or 18 ft. x 18 ft. (5,5 m x 5,5 m)
spacing. (Refer to the approval chart on
page 58 d for additional listing.)
Duringfireconditions,when the temper-
ature around the sprinkler approaches
its operating temperature, the cover
plate detaches. Continued heating of
theexposedsprinklercausesthe fusible
link to disengage, releasing the deflec-
torand sealing assembly. Water flowing
through the sprinkler orifice strikes the
deflector, forming a uniform spray pat-
tern to extinguish or control the fire.
4. TECHNICAL DATA
LISTINGS: UL Listed, Guide No. VNIV for
Light-Hazard occupancies with
smooth, flat, horizontal ceilings only.
Refer to Table 1 on page 58 d.
Ratedto175psi(1207kPa)waterworking
pressure.
Factory tested pneumatically to 95 psi
(655 kPa).
Spring: U.S.A. Patent No. 4,570,720
Thread Sizes:
Part Nos. 08498 and 10485: 1/2" (15
mm) NPT
Part No. 10680: 3/4" (20 mm) NPT
Orifice Sizes:
Part No. 08498: Standard Orifice
Part Nos. 10485 and 10680: Large
Orifice
K-factors:
Part No. 08498: Nominal 5.5 U.S.
(7,9 metric*)
Part Nos.10485 and10680: Nominal
8.0 U.S. (11,5 metric*)
* MetricK-factor shownis foruse when pressure
is measured in kPa. When pressure is mea-
sured in BAR, multiply the metric K-factor
shown by 10.0.
Minimum operating pressure: 7 psi (48,3
kPa)
Maximum distance from sprinklers to
walls:One-halfthesprinklerspacingindi-
cated in Table 1 for the “Minimum Water
Supply Requirement” used .
Available Cover Plate Vertical Adjustment:
1/2" (12,7 mm) +/- 1/4" (6,4 mm)
SPRINKLER MATERIALS
Body: Brass Casting UNS-C84400
Body Cap: Brass UNS-C26000
Deflector: Copper UNS-C19500
Deflector Pins: Stainless Steel UNS-
S30300
Lever Bar: Copper Alloy UNS-C72500
CompressionScrew:BrassUNS-C36000
Fusible Link Assembly**: Nickel Alloy and
Eutectic Solder
**Fusible links of Horizon®Mirage®Quick Re-
sponse Extended Coverage Concealed Pen-
dentSprinklers aremarked with ayellowstripe
or dot for identification purposes only.
Fusible Link Levers: Stainless Steel
UNS-S31600
Seal: Teflon ®Tape
Spring: Nickel Alloy
COVER PLATE ASSEMBLY MATE-
RIALS
Cover Plate Assembly: Brass UNS-
C26000
Spring: Nickel Alloy
Solder: Eutectic
COVER FINISHES
Bright Brass
Polished Chrome
Painted 1White (No. 1004 2)
Painted 1Ivory (No. 16342)
Painted 1Black (No. 1007 2)
1Painted finish consists of PolyesterBaked
Enamel.
2Sherwin-Williams®Color Answers™ In terior
ColorNumber. Othercolors are available onre-
quest. SeeSherwin-Williams ®Color An-
swers™In teriorColorSelectioncolornumbers .
ORDERING INSTRUCTIONS
Horizon ®Mirage®Sprinklers and cover
plates must be ordered separately.
To order the Horizon ®Mirage ®Quick
Response Extended Coverage Con-
cealed Pendent Sprinkler, refer to:
1. Model B-1 Standard Orifice Sprinkler
Base Part No. 08498 or
2. Model B-2 Large Orifice Sprinkler:
May 25, 2000Sprinkler 58 a
Form No. F_050493
Note:Unitsofmeasureinparentheses may beapproximations.Replaces page 58 a-d, dated October 20, 1999. (These
sprinklers are available with 220 °F temperature rating).
Cover Plate Assembly:P/N 09804
1/2" NPT Sprinklers:
P/N 08498 (std. orifice)
P/N 10485 (large orifice)
3/4" NPT Sprinkler:
P/N 10680
(large orifice)
For Light Hazard Occupancies Only
TECHNICAL DATA
HORIZON®MIRAGE®
QUICK RESPONSE
EXTENDED COVERAGE
CONCEALED SPRINKLERS
Horizon®Mirage ®Concealed Sprinkler
Installed in Acoustical Ceiling
OBSOLETE
a. Base Part No. 10485 with 1/2"
(1 5 mm) NPTor
b. Base Part No. 10680 with 3/4"
(20 mm) NPT
To order the Cover Plate Assembly, re-
fer to: Part No. 09804.
NOTE:Specify temperature rating of
sprinklerandtemperatureratingandfin-
ishofcoverplateassembly(seeTable1
on page 58 d).
ACCESSORIES
Sprinkler Cabinet: Part No. 01731A
Capacity: six (6) sprinklers
Available since 1971.
Concealed Sprinkler Wrenches *:
A. Heavy Duty: Part No. 08336W/B
Available since 1993
B. Light Duty: Part No. 10366W/B**
Available since 1998
* A1/2"ratchetisrequired(notavailablefromVi-
king).
** Ideal for sprinkler cabinets.
5. AVAILABILITY AND SERVICE
Viking products are available through a
network of domestic, Canadian, and in-
ternational distributors. See the Yellow
Pagesofthetelephonedirectoryforalo-
cal distributor (listed under “Sprinklers-
Automatic-Fire”) or contact Viking.
Viking Technical Data may be found on
The Viking Corporation’s Web site at:
http://www.vikingcorp.com
The Web site may include a more recent
edition of this Technical Data page.
6. GUARANTEES
For details of warranty, refer to Viking’s
current price schedule or contact The
Viking Corporation directly.
7. INSTALLATION
WARNING: Viking sprinklersaremanu-
factured and tested to meet the rigid re-
quirements of the approving agency.
The sprinklers are designed to be in-
stalled in accordance with recognized
installation standards. Deviation from
the standards or any alteration to the
sprinkler or cover plate assembly after it
leaves the factory including, but not lim-
itedto: painting, plating, coating or mod-
ification, may render the sprinkler inop-
erative and will automatically nullify the
approval and any guarantee made by
The Viking Corporation.
A. Sprinklers must be installed in accor-
dance with the latest published stan-
dards of the National Fire Protection
Association, Factory Mutual, Loss Pre-
vention Council, Assemblee Pleniere,
Verband der Sachversicherer or other
similar organizations, and also with the
provisions of governmental codes, ordi-
nances, and standards whenever appli-
cable. Concealedsprinklers are decora-
tive sprinklers and may be considered
special purpose. Refer to the Authority
Having Jurisdiction prior to installation .
NOTE: Previous Model B-1 Cover Plate
Assembly Part Number 08310 may still be
used for ULC/UL installations .
B. Sprinklers must be handled with care.
Concealedsprinklers areprotected witha
plasticshell,whichshouldremaininplace
overthe sprinkler body during installation,
testing, and any time the sprinkler is han-
dled or shipped. The plastic protective
shellmustberemovedprior toplacing the
systeminservice. Seesection“I”belo w.
Prior to installation, sprinklers must be
stored in a cool, dry place in their origi-
nal shipping container. Never install
sprinklers that have been dropped,
damaged in any way, or exposed to
temperatures in excess of maximum
ambient temperature allowed. Such
sprinklers should be destroyed immedi-
ately .
C. Horizon®Mirage®Quick Response
ConcealedSprinklersmustbeinstalled
in neutral or negative pressure ple-
nums only.
D. U se care when locating sprinklers near
fixtures that can generate heat. Do not
installsprinklerswheretheywouldbeex-
posed to temperatures that exceed the
maximum recommended ambient tem-
peratureforthetemperatureratingused .
E. Horizon®Mirage ®Concealed Sprin-
klers are not intended for use in corro-
sive environments. Use only sprinklers
listed for corrosive environments when
subject to corrosive atmospheres.
F. Adequate heat must be provided when
Horizon ®Mirage®QuickResponse Ex-
tended Coverage Concealed Sprin-
klersare installedon wetpipe systems.
When installing sprinklers on dry sys-
tems, refer to appropriate installation
guides and the Authority Having
Jurisdiction.
G. Sprinklers must be installed after the
piping is in place to preventme chanical
damage. Before installation, be sure to
have the appropriate sprinkler model
and style, with the correct orifice size,
temperature rating, and response char-
acteristics. Install the sprinklers accord-
ing to the following steps :
1. Installallpipingand cutthe sprinkler
drop nipple to position the 1/2" or
3/4" (depending on the sprinkler)
NPT outlet of the reducing coupling
at the desired elevation. The drop
nipple must be perpendicular to the
ceilingand centeredin a2" (50mm)
diameter opening in the ceiling.
2. With the sprinkler in the plastic pro-
tectiveshell,applyasmallamountof
pipe-joint compound or tape to the
external threads of the sprinkler
only, taking care not to allow a
build-up inside the sprinkler inlet .
3. Use only the special wrenches de-
signed for installing Horizon ®Mirage ®
Concealed Sprinklers. With the sprin-
kler in the plastic protective shell,
place the unit into the wrench .
4. Turn the unit clockwise to thread the
sprinkler into the 1/2" or 3/4" (de-
pending on the sprinkler used) NPT
outlet of the coupling. DO NOT use
the fusible link to start or thread the
sprinkler into a fitting.
H.Afterinstallation,theentiresystemmust
be tested in accordance with recog-
nizedinstallationstandards.Thetestis
appliedaftersprinklerinstallationtoen-
sure that no damage has occurred to
thesprinklerduringshippingandinstal-
lation, and to make sure the unit has
beenproperlytightened.Ifathreadleak
occurs, normally the unit must be re-
moved, new pipe-joint compound or
tape applied, and then reinstalled. This
is due to the fact that when the joint seal
leaks, the sealing compound or tape is
washed out of the joint .
I. After testing, repairing of all leaks, and
installation and painting of the ceiling,
the cover plate assembly may be at-
tached.
Sprinkler 58 b
1/2" NPT Sprinklers:
P/N 08498 (std. orifice)
P/N 10485 (large orifice)
3/4" NPT
Sprinkler:
P/N 10680
(large orifice)
Protective
Shell
May 25, 2000
TECHNICAL DATA
HORIZON®MIRAGE®
QUICK RESPONSE
EXTENDED COVERAGE
CONCEALED SPRINKLERS
Figure 1
Concealed Sprinkler Wrench** Part No.
08336W/B (shown) or Part No. 10366W/B
**A 1/2" ratchet is required (not available through Viking).
OBSOLETE
1. Remove the cover from the protec-
tive box, taking care not to damage
the cover plate assembly.
2. Remove and discard the plastic pro-
tectiveshellfrom thesprinkler.Rec-
ommendation: retain a protective
shell in the spare sprinkler cabinet.
The internal diameter of the special
Horizon ®Mirage ®ConcealedSprin-
kler Installation Wrenches are de-
signed for use with the sprinkler
contained in a protective shell.
3.Frombelowtheceiling,gentlyplacethe
baseofthecoverplate assembly over
thethreadedbodyofthe sprinklerpro-
trudingthroughthe 2"(50mm) diame-
ter hole in the ceiling .
4. Push the cover plate assembly onto
the sprinkler until the unfinished
brass flange of the cover plate base
touches the ceiling.
The maximum adjustment avail-
able, is 1/2" (12,7 mm). DO NOT
MODIF Y THE UNIT. If necessary,
re-cut the sprinkler drop nipple.
J. DISASSEMBLY:
The “thread-off” design of the cover
plate assembly allows the cover plate
assembly to be removed and rein-
stalled to permit temporary removal of
ceiling panels without taking the sprin-
kler system out of service and remov-
ing the sprinkler. To remove the cover
plate assembly:
1. From below the ceiling, grasp the
cover plate and gently turn it coun-
terclockwise.
Ifitisnecessarytoremovetheen-
tire sprinkler, the system must be
removed from service. See Main-
tenanceinstructionsandfollowall
warnings and instructions.
K. RE-ASSEMBLY: The “push-on” feature
of the cover plate assembly allows easy
installation of the cover plate .
1.Frombelowtheceiling,gentlyplacethe
baseofthecoverplate assembly over
the threaded body of the sprinkler .
2. Push the cover plate assembly onto
the sprinkler until the unfinished
brass flange of the cover plate base
touches the ceiling.
8. MAINTENANCE
NOTICE: The owner is responsible for
maintaining the fire protection system
and devices in proper operating
condit ion. For minimum maintenance
and inspection requirements, refer to the
appropriate National Fire Protection As-
sociation’s pamphlet that describes care
andmaintenanceofsprinklersystems.In
addition, the Authority Having Jurisdic-
tion may have additional maintenance
requirements that must be followed .
A.Sprinklers mustbe inspectedona regu-
lar basis for corrosion, mechanical
damage, obstructions, paint, etc. The
frequencyofinspectionsmayvarydueto
corrosive atmospheres, water sup-
plies, and activity around the device .
B. Sprinklers or cover plate assemblies
that have been field painted or me-
chanically damaged must be replaced
immediately. Sprinklers showing signs
of corrosion shall be tested and/or re-
placed immediately as required. Instal-
lation standards require sprinklers to
be tested and, if necessary, replaced
immediately after a specified term of
service. Refer to the installation stan-
dards and the Authority Having Juris-
diction for the specified period of time
after which testing and/or replacement
is required. Sprinklers and cover plate
assemblies that have operated cannot
bereassembled orre-used, butmustbe
replaced. When replacement is neces-
sary, use only new sprinklers and cover
plate assemblies .
C. The sprinkler discharge pattern is criti-
cal for proper fire protection. Nothing
should be hung from the sprinkler, at-
tached to it, or otherwise obstruct the
discharge pattern. All obstructions must
be immediately removed or, if neces-
sary, additional sprinklers installed .
D. When replacing existing sprinklers, the
system must be removed from service.
Refer to the appropriate system de-
scription and/or valve instructions.
Prior to removing the system from ser-
vice, notify all Authorities Having Juris-
diction. Consideration should be given
to employment of a fire patrol in the af-
fected area.
1. Remove the system from service,
drain all water, and relieve all pres-
sure on the piping.
2. Remove the cover plate assembly:
a.From belowthe ceiling, graspthe
cover plate and gently turn it
counterclockwise.
3. Place a plastic protective shell (from
thesparesprinklercabinet)overthe
sprinkler to be removed. The inter-
naldiameterof thespecialHorizon ®
Mirage ®ConcealedSprinklerInstal-
lation Wrenches are designed for
use with the sprinkler contained in
the shell.
4. Remove the sprinkler from the fitting
in which it is installed:
a.Using one of the specialsprinkler
wrenches, turn the unit counter-
clockwise to remove the old
sprinkler.
5.Installthenewunit.Caremustbetaken
to ensure that the replacement sprin-
kleristhe propermodel andstyle, with
the correct orifice size, temperature
rating, and response characteristics.
A fully stocked spare sprinkler cabinet
should be provided for this purpose .
Use of the correct Horizon ®Mirage ®
Sprinkler 58 c
May 25, 2000
Figure 3:Installation of 3/4" (20 mm) NPT Sprinkler
Figure 2: Installation of 1/2" (15 mm) NPT Sprinkler
2" (50 mm)
diameter hole
required
2-7/16"
(61,9 mm)
Minimum
2-3/4"
(69,8 mm)
3/4"
(20 mm)
NPT
2-7/16"
(61,9 mm)
2-15/16"
(74,6 mm)
Maximum
TECHNICAL DATA
2-3/4"
(69,8 mm)
1/2"
(15 mm)
NPT
2-1/4"
(57,2 mm)
2-1/4"
(57,2 mm)
Minimum
2" (50 mm)
diameter hole
required
2-3/4"
(69,8 mm)
Maximum
HORIZON®MIRAGE®
QUICK RESPONSE
EXTENDED COVERAGE
CONCEALED SPRINKLERS
OBSOLETE
Concealed Sprinkler can be verified
by checking the fusible link for the fol-
lowing identification scheme :
Standard Response: No stripe or
dot.
Quick Response:Purple stripe or
dot.
EC&QREC:Yellowstripeordot.
Follow instructions provided in “IN-
STALLATION” paragraph 7 .
6. Place the system back in service and
secure all valves. Check the replaced
sprinklers and repair all leaks .
E. Sprinkler systems that have been sub-
jected to a fire must be returned to ser-
vice as soon as possible. The entire
system must be inspected for damage
andrepairedorreplacedasnecessary.
Sprinklers that have been exposed to
corrosive products of combustion or
high ambient temperatures, but have
not operated, should be replaced. Re-
fer to the Authority Having Jurisdiction
for minimum replacement require-
ments.
FormNo.F_050493
Sprinkler 58 dMay 25, 2000
TECHNICAL DATA
HORIZON®MIRAGE®
QUICK RESPONSE
EXTENDED COVERAGE
CONCEALED SPRINKLERS
Replaces page 58 a-d, dated October 20, 1999. (These
sprinklers are available with 220 °F temperature rating).
Sprinkler Temperature
ClassificationNominal Temperature Rating1Highest Ambient Temperature
Allowed at Ceiling2Required Cover Assembly
Temperature Rating
Ordinary165 °F (74 °C)100 °F (38 °C)165 °F (74 °C)
Intermediate220 °F (104 °C)150 °F (65 °C)165 °F (74 °C)
Approval Chart
Model B-1 Standard Orifice Horizon®Mirage ®Quick
Response Extended Coverage Concealed Pendent Sprinkler
Sprinkler Part
Number3NPT Thread
SizeMaximum Areas
of Coverage 5Nominal
K-FactorMinimum Water
Supply Requirements 5Listings and Approvals4
UL7C-UL 7NYC 8
InchesmmLength x WidthU.S.metric 6
084981/21516 ft. x 16 ft.
(4,9 m x 4,9 m)5.57,926 gpm @ 22.3 psi
(98,4 L/min @ 155 kPa)A1A1A1
084981/21518 ft. x 18 ft.
(5,5 m x 5,5 m)5.57,933 gpm @ 36.0 psi
(124,9 L/min @ 250 kPa)A1A1A1
084981/21520 ft. x 20 ft.
(6,1 m x 6,1 m)5.57,9Listed for this spacing as standard response extended coverage
sprinklers. See extended coverage sprinkler page 87 a-d.
Model B-2 Large Orifice Horizon ®Mirage ®Quick Response Extended Coverage Concealed Pendent Sprinklers
Sprinkler Part
Numbers3NPT Thread
SizeMaximum Areas
of Coverage 5Nominal
K-FactorMinimum Water
Supply Requirements 5Listings 4
Length x WidthUL 7C-UL 7NYC
InchesmmU.S.metric 6
104851/21516 ft. x 16 ft.
(4,9 m x 4,9 m)8.011,526 gpm @10.6 psi
(98,4 L/min @ 75 kPa)A1A1–
106803/420
104851/21518 ft. x 18 ft.
(5,5 m x 5,5 m)8.011,533 gpm @ 17.0 psi
(124,9 L/min @ 118 kPa)A1A1–
106803/420
104851/21520 ft. x 20 ft.
(6,1 m x 6,1 m)8.011,5Listed for this spacing as standard response extended coverage
sprinklers. See extended coverage sprinkler page 87 a-d.
106803/420
Available Temperature Ratings 9
A - 165 °F (74 °C)
B - 220 °F (104 °C)
Approved Cover Finishes
1 - Bright Brass, Polished Chrome, Painted White, Painted Ivory, or Painted Black 10
Footnotes
1Temperature rating of the Horizon ®Mirage ®Concealed Sprinkler is stamped on the sprinkler body.
2Basedon NFPA-13. Otherlimits may apply, dependingonfireloading,sprinkler location, a ndother requirementsof theAuthority Having Juris-
diction. Refer to specific installation standards.
3Base part number is shown. For complete part number, refer to Viking's current price list.
4Thischart shows listingsand approvals available at timeof printing.Other approvals may be inprocess. Checkwith the manufacturer for addi-
tional approvals.
5For areas of coverage smaller than shown, use the "Minimum Water Supply Requirement" for the next larger "Area of Coverage" listed for the
sprinkler used. The distance from sprinklers to walls shall not exceed one-half the sprinkler spacing indicated for the "Minimum Water Supply
Requirement" used.
6MetricK-factorshownisforusewhenpressureismeasuredinkPa.Whenpressureismeasure dinBAR,multip lythemetricK-factorshownb y10.0 .
7Listing is limited to Light-Hazard occupancies with smooth, flat, horizontal ceilings.
8Accepted for use, City of New York Department of Buildings, MEA 89-92, Volume IX.
9Availabletemperatureratingsare165°F (74 °C) and 220°F(104°C),however,the 220 °F (1 04°C)temperatureratedsprinkler has no Listings
or Approvals at the time of this printing.
10 Other paint colors are available on request with the same Listings and Approvals as the stand ard paint finishes .
Table 1
Temperature KEY
Finish
A1XEscutcheon (if applicable)
OBSOLETE

This manual suits for next models

3

Other Viking Irrigation System manuals

Viking MIRAGE VK632 Instruction manual

Viking

Viking MIRAGE VK632 Instruction manual

Viking QR1 Operating manual

Viking

Viking QR1 Operating manual

Viking VK506 Instruction manual

Viking

Viking VK506 Instruction manual

Viking FREEDOM VK467 Instruction manual

Viking

Viking FREEDOM VK467 Instruction manual

Viking MICROFAST VK345 Instruction manual

Viking

Viking MICROFAST VK345 Instruction manual

Viking MICROFAST VK327 User manual

Viking

Viking MICROFAST VK327 User manual

Viking MICROFAST VK302 Instruction manual

Viking

Viking MICROFAST VK302 Instruction manual

Viking VK1021 Instruction manual

Viking

Viking VK1021 Instruction manual

Viking MicrofastHP VK340 Instruction manual

Viking

Viking MicrofastHP VK340 Instruction manual

Viking MIRAGE VK461 Instruction manual

Viking

Viking MIRAGE VK461 Instruction manual

Viking VK3541 Instruction Manual

Viking

Viking VK3541 Instruction Manual

Viking ESFR User manual

Viking

Viking ESFR User manual

Viking VKFD25U Instruction manual

Viking

Viking VKFD25U Instruction manual

Viking SIN VK520 Instruction manual

Viking

Viking SIN VK520 Instruction manual

Viking MICROMATIC VK104 Instruction manual

Viking

Viking MICROMATIC VK104 Instruction manual

Viking VK680 Instruction manual

Viking

Viking VK680 Instruction manual

Viking MICROFAST VK311 Instruction manual

Viking

Viking MICROFAST VK311 Instruction manual

Viking MicrofastHP VK317 Instruction manual

Viking

Viking MicrofastHP VK317 Instruction manual

Viking MICROFAST VK328 Instruction manual

Viking

Viking MICROFAST VK328 Instruction manual

Viking M User manual

Viking

Viking M User manual

Viking VK449 Instruction Manual

Viking

Viking VK449 Instruction Manual

Viking VK506 Service manual

Viking

Viking VK506 Service manual

Viking HQR-2 Instruction manual

Viking

Viking HQR-2 Instruction manual

Viking HQR-2 User manual

Viking

Viking HQR-2 User manual

Popular Irrigation System manuals by other brands

Tyco Fire Product CENTRAL Ultra K17 instruction manual

Tyco Fire Product

Tyco Fire Product CENTRAL Ultra K17 instruction manual

Tyco Fire Product CENTRAL S176 instruction manual

Tyco Fire Product

Tyco Fire Product CENTRAL S176 instruction manual

Globe GL Series quick start guide

Globe

Globe GL Series quick start guide

Homesafe F1 Res 44 quick guide

Homesafe

Homesafe F1 Res 44 quick guide

Globe GL-QR Series manual

Globe

Globe GL-QR Series manual

Westfalia Sun 91 98 04 Original instructions

Westfalia

Westfalia Sun 91 98 04 Original instructions

ATIKA VT 32 operating manual

ATIKA

ATIKA VT 32 operating manual

Ryobi ONE+ P2704 Operator's manual

Ryobi

Ryobi ONE+ P2704 Operator's manual

FLORABEST 273587 Assembly and Safety Advice

FLORABEST

FLORABEST 273587 Assembly and Safety Advice

Tyco ESFR-14 quick guide

Tyco

Tyco ESFR-14 quick guide

Gardena A 1020 Sensor user manual

Gardena

Gardena A 1020 Sensor user manual

Tyco Fire Product CENTRAL DS-2 instruction manual

Tyco Fire Product

Tyco Fire Product CENTRAL DS-2 instruction manual

Eden 96998EDAMZ quick start guide

Eden

Eden 96998EDAMZ quick start guide

DIG 12 Outlet Drip Manifold instruction manual

DIG

DIG 12 Outlet Drip Manifold instruction manual

Martha Stewart MTS-IDSPR Operator's manual

Martha Stewart

Martha Stewart MTS-IDSPR Operator's manual

Tyco TY-FRB Series manual

Tyco

Tyco TY-FRB Series manual

Tyco Fire Product Gem ISSUE D QUARTZOID instruction manual

Tyco Fire Product

Tyco Fire Product Gem ISSUE D QUARTZOID instruction manual

Rain Bird 11000 Series Operation & maintenance manual

Rain Bird

Rain Bird 11000 Series Operation & maintenance manual

manuals.online logo
manuals.online logoBrands
  • About & Mission
  • Contact us
  • Privacy Policy
  • Terms and Conditions

Copyright 2025 Manuals.Online. All Rights Reserved.