STANDARD RESPONSE
FUSIBLE LINK PENDENT
SPRINKLER VK206 (K8.0)
TECHNICAL DATA
Page 4 of 6
Form No. F_060514 20.05.26 Rev 20.1
The Viking Corporation, 210 N Industrial Park Drive, Hastings MI 49058
T
elephone:
269-945-9501
T
echnical
Services:
877-384-5464
Fax:
269-818-1680
Email:
[email protected]Visit the Viking website for the latest edition of this technical data page www.vikinggroupinc.com.
Approval Chart 1 (UL)
Standard Response Pendent Sprinkler VK206
Maximum 175 PSI (12 bar) WWP
Sprinkler
Base Part
Number1
SIN Thread Size Nominal K-Factor Overall Length Listings and Approvals3
(Refer also to UL Design Criteria.)
NPT BSPT U.S. metric2Inches mm cULus4
Standard Orifice
18254 VK206 3/4” 20 mm 8.0 115.2 2-1/4” 58 A2, B1, B3X, A4, B4Y
182567VK206 1/2” 15 mm 8.0 115.2 2-1/4” 58 A2, B1, B3X, A4, B4Y
NOTICE - Product Below - Limited Availability (Contact Local Viking Office)
05516 VK206 3/4” 20 mm 8.0 115.2 2-1/4” 58 A2, B1, B3X -- -- --
055787VK206 1/2” 15 mm 8.0 115.2 2-1/4” 58 A2, B1, B3X -- -- --
Approved Temperature Ratings
A - 165 °F (74 °C), 220 °F (104 °C), and 286 °F
(141 °C)
B - 165 °F (74 °C) and 220 °F (104 °C)
Approved Finishes
1 - Wax-Coated Brass (corrosion re-
sistant)
2 - Brass, Chrome, White Polyester5,6,
and Black Polyester5,6
3 - Brass and Chrome
4 - ENT5
Approved Escutcheons
X - Installed with standard surface-mounted escutch-
eons or or recessed with the Viking Micromatic®Model
E-1 or E-2 Recessed Escutcheon.
Y - Installed with standard surface-mounted escutch-
eons or or recessed with the Viking Micromatic®Model
E-1 Recessed Escutcheon.
Footnotes
1 Base part number is shown. For complete part number, refer to Viking’s current price schedule.
2 Metric K-factor shown is for use when pressure is measured in bar. When pressure is measured in kPa, divide the metric K-factor shown by 10.0.
3 This table shows the listings and approvals available at the time of printing. Check with the manufacturer for any additional approvals.
4 Listed by Underwriters Laboratories Inc. for use in the U.S. and Canada.
5cULus Listed as corrosion resistant.
6Other colors are available on request with the same Listings and Approvals as the standard colors.
7The 1/2” NPT Large Orifice Sprinkler is Listed and Approved for retrofit only.
DESIGN CRITERIA - UL
(Also refer to Approval Chart 1.)
cULus Listing Requirements:
Viking Standard Response Fusible Link Pendent Sprinkler VK206 is cULus Listed as indicated in Approval Chart 1 for installation in accordance with
the latest edition of NFPA 13 for standard spray sprinklers.
Designed for use in Light, Ordinary, and Extra Hazard occupancies.
The sprinkler installation rules contained in NFPA 13 for standard spray pendent sprinklers must be followed.
IMPORTANT: Always refer to Bulletin Form No. F_091699 - Care and Handling of Sprinklers. Also refer to Form No. F_080614
for general care, installation, and maintenance information. Viking sprinklers are to be installed in accordance with the latest
edition of Viking technical data, the appropriate standards of NFPA, LPCB, APSAD, VdS or other similar organizations, and
also with the provisions of governmental codes, ordinances, and standards, whenever applicable.