Visonic WST-400 User manual

DE3541 1
:67
Wireless Smoke Detector Installation Instructions
,1752'8&7,21
The WST-400 consists of a 9-Volt battery-operated smoke
detector to which a Visonic Ltd. RF transmitter has been added.
The transmitter is compatible with the Visonic Ltd. 1, 2, and 4
channel receivers of the WR-200 and WR-300 series.
Upon alarm (smoke detection), the detector keys the RF
transmitter. The transmitter in turn transmits a coded signal that
consists of a SYSTEM code and a CHANNEL code. Only a
receiver set to the same system code as that of the transmitter
will respond to the transmitted signal. If the system code is
correct, the channel code transmitted by the WST-400 will
activate the corresponding relay in the target receiver.
Smoke alarm transmissions will be sent once every 60 seconds
for a period of 1 - 2 seconds per transmission while the detector
is on alarm. An alarm is also indicated by sounding of the smoke
detector's built-in horn.
A notable advantage of the WST-400 is its ability to transmit
low-battery signals when the battery voltage drops below a preset
threshold. A low battery signal will be sent once every 45
seconds for 1 to 2 seconds per transmission, to activate the
buzzer output (BUZ) in receivers type WR-200/2B, WR-200/4B,
WR-300/2B and WR-300/4B. Simultaneously, the built-in
electronic horn will sound a short beep.
75$160,77(563(&,),&$7,216
Encoding: 8-bit digital word, 256 combinations, pulse width
modulation.
Channels: 4 channels, DIP switch selectable
Operating Frequency (MHz): 315, 404, 418, 433.92 MHz or
other frequencies according to local requirements.
Transmission Cycle: 1-2 second transmissions once every 60
seconds while in alarm.
Power Supply: 9 VDC alkaline battery, such as Eveready #522
or Duracell #MN1604
Current Consumption: 0.5 µA standby, 5 mA transmit
Battery Test: "Channel 0" code transmitted once every 45
seconds when the battery voltage goes below 7.5 Volts.
Compliance with Standards: Meets FCC Part 15, ETS300-220
and MPT1349
Operating Temperature Range: 0°C to 49°C (32°F to 120°F).
,167$//$7,21
6HWWLQJWKH6\VWHP&RGH
The WST-400 transmitter has an 8-key DIP switch marked 1 to 8
(see Figure 1). Each key may be set to ON or OFF to create a
unique digital code (256 possible combinations). Use a ball point
pen to set each one of the 8 switches to match the system code
setting of the target receiver. All wireless transmitters and
receivers in the system must be set to the same code.
Figure 1. WST-400 Code Selector
CAUTION! The code combination 2, 4, 5, 6, 7 ON / 1, 3, 8 OFF
is a factory test code which must not be used. Also avoid codes
which are often used: all keys ON, all keys OFF or alternating
ON/OFF settings.
6HWWLQJWKH&KDQQHO&RGH
Each WST-400 has a 4-key DIP switch marked 1 to 4 (Fig. 1).
This switch permits selecting one of 4 channel codes by shifting
the selected switch lever to the ON position. Figure 1 shows the
channel selector with channel No. 2 selected.
Setting all four channel selector keys to OFF (code "0") will
activate the buzzer (BUZ) output in the receiver and none of the
channel outputs.
In fact, the channel selector keys can be set to 15 ON/OFF
combinations - a useful feature in multiple zone applications. To
take advantage of this capability, the 4 outputs of the target
receiver must be connected to the optional WMX-16 output
multiplexer (refer to Publication D-4001-0 for more details).
0RXQWLQJ
Mount the WST-400 smoke detector in accordance with the
enclosed owner's manual. Be sure to read these instructions and
follow them in full.
7HVWLQJ
ATTENTION! Before proceeding, be sure to put the alarm
system into the test mode, or inform the central station that you
will be testing your smoke detectors.
To test proper activation of the smoke detector as well as
wireless transmission, press the test button located on the front
of the smoke detector for 20 seconds or until the alarm sounds.
Verify activation of the control panel's fire zone (the zone
designated for smoke detectors).
See the enclosed owner's manual for more information.

2DE3541
0,6&(//$1286&200(176
3URGXFW/LPLWDWLRQ
Visonic Ltd. wireless systems are very reliable and are tested to
high standards. However, due to low transmitting power and
limited range (required by FCC and other regulating authorities),
there are some limitations to be considered:
A. Receivers may be blocked by radio signals occurring on or
near their operating frequencies, regardless of the digital code
used.
B. A receiver can only respond to one transmitted signal at a
time.
C. Wireless equipment should be tested regularly to determine
whether there are sources of interference and to protect
against faults.
&RPSOLDQFHZLWK6WDQGDUGV
The user is cautioned that changes or modifications to the unit,
not expressly approved by the party responsible for compliance,
could void the user's authority to operate the equipment.
The 315 MHz model of this device complies with Part 15 of the
FCC Rules and RSS-210 of Industry and Science Canada.
Operation is subject to the following two conditions: (1) This
device may not cause harmful interference, and (2) this device
must accept any interference received, including interference that
may cause undesirable operation.
The 433.92 MHz model of this device complies with CE
requirements for Europe and bears the CE mark and certification.
:$55$17<
:$55$17<
Visonic Ltd. and/or its subsidiaries and its affiliates ("the Manufacturer") warrants its
products hereinafter referred to as "the Product" or "Products" to be in conformance with
its own plans and specifications and to be free of defects in materials and workmanship
under normal use and service for a period of twelve months from the date of shipment by
the Manufacturer. The Manufacturer's obligations shall be limited within the warranty
period, at its option, to repair or replace the product or any part thereof. The Manufacturer
shall not be responsible for dismantling and/or reinstallation charges. To exercise the
warranty the product must be returned to the Manufacturer freight prepaid and insured.
This warranty does not apply in the following cases: improper installation, misuse,
failure to follow installation and operating instructions, alteration, abuse, accident or
tampering, and repair by anyone other than the Manufacturer.
This warranty is exclusive and expressly in lieu of all other warranties, obligations or
liabilities, whether written, oral, express or implied, including any warranty of
merchantability or fitness for a particular purpose, or otherwise. In no case shall the
Manufacturer be liable to anyone for any consequential or incidental damages for breach
of this warranty or any other warranties whatsoever, as aforesaid.
This warranty shall not be modified, varied or extended, and the Manufacturer does not
authorize any person to act on its behalf in the modification, variation or extension of this
warranty. This warranty shall apply to the Product only. All products, accessories or
attachments of others used in conjunction with the Product, including batteries, shall be
covered solely by their own warranty, if any. The Manufacturer shall not be liable for any
damage or loss whatsoever, whether directly, indirectly, incidentally, consequentially or
otherwise, caused by the malfunction of the Product due to products, accessories, or
attachments of others, including batteries, used in conjunction with the Products.
The Manufacturer does not represent that its Product may not be compromised and/or
circumvented, or that the Product will prevent any death, personal and/or bodily injury
and/or damage to property resulting from burglary, robbery, fire or otherwise, or that the
Product will in all cases provide adequate warning or protection. User understands that a
properly installed and maintained alarm may only reduce the risk of events such as
burglary, robbery, and fire without warning, but it is not insurance or a guarantee that such
will not occur or that there will be no death, personal damage and/or damage to property
as a result.
The Manufacturer shall have no liability for any death, personal and/or bodily injury
and/or damage to property or other loss whether direct, indirect, incidental,
consequential or otherwise, based on a claim that the Product failed to function.
However, if the Manufacturer is held liable, whether directly or indirectly, for any loss or
damage arising under this limited warranty or otherwise, regardless of cause or origin, the
Manufacturer's maximum liability shall not in any case exceed the purchase price of the
Product, which shall be fixed as liquidated damages and not as a penalty, and shall be the
complete and exclusive remedy against the Manufacturer.
Warning: The user should follow the installation and operation instructions and among
other things test the Product and the whole system at least once a week. For various
reasons, including, but not limited to, changes in environmental conditions, electric or
electronic disruptions and tampering, the Product may not perform as expected. The user
is advised to take all necessary precautions for his /her safety and the protection of
his/her property. 6/91
VISONIC LTD. (ISRAEL): P.O.B 22020 TEL-AVIV 61220 ISRAEL. PHONE: (972-3) 645-6789, FAX: (972-3) 645-6788
VISONIC INC. (U.S.A.): 10 NORTHWOOD DRIVE, BLOOMFIELD CT. 06002-1911. PHONE: (860) 243-0833, (800) 223-0020 FAX: (860) 242-8094
VISONIC LTD. (UK): UNIT 1, STRATTON PARK, DUNTON LANE, BIGGLESWADE, BEDS. SG18 8QS. PHONE: (01767) 600857 FAX: (01767) 601098
VISONIC LTD. 1998 WST-400 D-3541-0 NEW : DE3541- (REV. 3 , 4/98)
Table of contents
Other Visonic Smoke Alarm manuals

Visonic
Visonic MCT-426 User manual

Visonic
Visonic SMD-426 User manual

Visonic
Visonic MCT-425 User manual

Visonic
Visonic MCT-427 User manual

Visonic
Visonic :67 User manual

Visonic
Visonic SMD 426 PG2 User manual

Visonic
Visonic MCT-425 User manual

Visonic
Visonic SMD-429 PG2 Series User manual

Visonic
Visonic MCT-423 User manual

Visonic
Visonic SMD-426 User manual
Popular Smoke Alarm manuals by other brands

CENTRAL
CENTRAL Omega C-1A manual

Alecto
Alecto SA-18 manual

Honeywell
Honeywell Fire-Lite Alarms BEAM355A Installation and maintenance instructions

System Sensor
System Sensor B401BH-2 Installation and maintenance instructions

Red Arrow Trading
Red Arrow Trading SMAB-2 installation instructions

SMC Networks
SMC Networks SMCSD10-Z Guide