Installation Instructions
6210/6210DS Electric Strike
®
Notes: Deadbolt will not function with this strike.
Checkwithfactoryforretrofitapplications.
1. Forlockordevicepreparation,seetheirdirections.
2. Prepare frame for strike (see other side).
3. Wire strike (Figure 1). (Switches on 6210DS only.)
4. Installinsertforauxiliary bolt operation (Figure 2).
5. Teststrike: Apply solenoid power.Fail secure (FSE) lipunlocks.
Fail safe (FS) lip locks. Figure 1 shows status of switches.
6. Installstrikewith two #12-24 screws. Make sure clearance
between latch bolt and strike lip is 1/32” (Figure 3). If not,
uninstallstrike, adjust (Figure 4), and reinstall.
7. Testdoor:With strike unlocked, door opens with latchbolt
extended. When door closes, latch bolt rides over strike lip.
931001_00(7) Copyright © 2004 Ingersoll-Rand. All rights reserved.
89/336/EEC
Figure 1
Single Door Mortise Application
Figure 3
Topview;
faceplatenot
shownforclarity
1/32”
Latchbolt
Strike lip
Figure 2
Insertandlocation
forVonDuprin
mortiselocks
Insertandlocation
for Schlage
mortiselocks
Insertandlocation
for Yale, Best, and
Sargentmortise
locks Figure 4
A
BC
Toadjuststrike,loosen screws
A, B, and Cand move backbox
sidewaysasnecessary
DC input is
nonpolarized
NOTE
!
J1
P1
P1 J1A P1A
SO-12or SO-24
12VDC
or
24VDC
12 VAC SO-12 12 VDC
or
24 VAC SO-24 24 VDC
{
{
Wiring
for DC
supply
Wiring
for AC
supply
Solenoid
Usecrimp
connectorsto
splice field wiring
toP1 leads
Yellow solenoid wires: 12 VDC, 0.57 A
Black solenoid wires: 24 VDC, 0.29 A
(alsoshownon strike label)
SOLENOID POWER REQUIREMENTS
Usecrimpconnectorsto
splice field wiring to P2
leads;insulateunusedleads
Switches shown with tripper
depressed, strike lip closed and locked
(switches and tripper on 6210DS only)
J2
Fail safe (FS)
J2
Fail secure (FSE)
S1
S2
1
2
3
4
5
6
S1
S2
1
2
3
4
5
6
Standard: 5 A, 30 VDC
Gold: 0.25 A, 30 VDC
SWITCH RATINGS
}
P2
Red (C)
Blue
Yellow
White (C)
Gray
Violet }
S1
(monitors
tripper)
S2
(monitors
strike lip)
J2 P2
931001-00