
NOTE: After return tonormal operation, change
the set point to the desired roomtemperature,
otherwise the default set point ( 70 °F or21°C)
will be used.
Table 4. Recommended cycle rate (CPH).
SYSTEMCPH SETTING
SteamGravity1
Hydronic heat3
Gas or Oilforced air6
Electric heat9
Note: Ifthe equipment manufacture recommends
a different rateuse the ratespecified by the
equipment manufacture.
Setting Heating Cycle Rate. (OP:03)
In cooling, the cycle rate is fixed at 3 Cycles per
hour. To set the cycle rate in heating; while in
installer setup,
a. Press D key, the displaywill
show the heat cycle rate.
b. Press Ñ keyto change the heat
cycle rate to 1,3,4,5,6,9 or 12
cycles per hour.
Note: Thedefault is set at 6cycle per hour.
Table 4 is the recommended cycle rate. The
installer should consult with the heating
equipment manufacturer for proper use.
Setting cooling algorithm. (OP:04)
Thecoolingalgorithmcan be selected as normal or
aggressive. For aggressive, the systemwill cool down
the roomto settingpoint faster than normal algorithm.
However, an overshoot might occurred in some
situations.
a. Press
keyto show the cooling
algorithm.
b. Press
keyto change algorithm.
0 = Normal algorithm(default).
1 = Aggressive algorithm.
Setting CoolingDelayTime. (OP:05)
In some case there is a necessityto delaythe
operation of the coolingequipment for protection
purpose. While in the installer setup,
a. Press D key. The displaywill
show coolingdelaytime.
b. Press Ñ keyto select the cooling
delaytime (0,3,5 minutes).
NOTE : The default settingis 3
minute.
Configuration Checkout. (OP:06)
Press D key, the current
configuration is displayed.
This information is for factoryuse
only.
Exit Installer Setup.
a. Press D keyagain to save all
settings and exit to the normal