manuals.online logo
Brands
  1. Home
  2. •
  3. Brands
  4. •
  5. WAGO
  6. •
  7. Control Unit
  8. •
  9. WAGO 750-655 User manual

WAGO 750-655 User manual

Other WAGO Control Unit manuals

WAGO SPEEDWAY 767 Series User manual

WAGO

WAGO SPEEDWAY 767 Series User manual

WAGO 750-523 User manual

WAGO

WAGO 750-523 User manual

WAGO 750-450 User manual

WAGO

WAGO 750-450 User manual

WAGO 753-466 User manual

WAGO

WAGO 753-466 User manual

WAGO 750-535/040-000 User manual

WAGO

WAGO 750-535/040-000 User manual

WAGO 750-458 User manual

WAGO

WAGO 750-458 User manual

WAGO WAGO-TO-PASS 761 User manual

WAGO

WAGO WAGO-TO-PASS 761 User manual

WAGO 750-563/040-000 User manual

WAGO

WAGO 750-563/040-000 User manual

WAGO 750-632 User manual

WAGO

WAGO 750-632 User manual

WAGO 750-457/040-000 User manual

WAGO

WAGO 750-457/040-000 User manual

WAGO 750-517/040-000 User manual

WAGO

WAGO 750-517/040-000 User manual

WAGO 750-651 User manual

WAGO

WAGO 750-651 User manual

WAGO TECHDOCS 750-600/000-001 User manual

WAGO

WAGO TECHDOCS 750-600/000-001 User manual

WAGO 750-494 Series User manual

WAGO

WAGO 750-494 Series User manual

WAGO 750-405 User manual

WAGO

WAGO 750-405 User manual

WAGO 761-214 User manual

WAGO

WAGO 761-214 User manual

WAGO 750-527 User manual

WAGO

WAGO 750-527 User manual

WAGO WAGO-I/O-SYSTEM 750 750-481/003-000 User manual

WAGO

WAGO WAGO-I/O-SYSTEM 750 750-481/003-000 User manual

WAGO 753-668/000-004 User manual

WAGO

WAGO 753-668/000-004 User manual

WAGO 750-654 User manual

WAGO

WAGO 750-654 User manual

WAGO 767-5201 User manual

WAGO

WAGO 767-5201 User manual

WAGO 751-5701 User manual

WAGO

WAGO 751-5701 User manual

WAGO 750-535 User manual

WAGO

WAGO 750-535 User manual

WAGO 750-483/040-000 User manual

WAGO

WAGO 750-483/040-000 User manual

Popular Control Unit manuals by other brands

Seitz 14A80 user manual

Seitz

Seitz 14A80 user manual

Wilo RS485 Installation and operating instructions

Wilo

Wilo RS485 Installation and operating instructions

Becker CentralControl CC41 Commissioning Instruction

Becker

Becker CentralControl CC41 Commissioning Instruction

SICK CDB650 operating instructions

SICK

SICK CDB650 operating instructions

Panduit NetKey NKP5E88M Series installation instructions

Panduit

Panduit NetKey NKP5E88M Series installation instructions

MX Options Concentric Petite Fitting instructions

MX

MX Options Concentric Petite Fitting instructions

Clean Water Systems Fleck 2510 Installation & start?up guide

Clean Water Systems

Clean Water Systems Fleck 2510 Installation & start?up guide

Fairchild FSB44104A user guide

Fairchild

Fairchild FSB44104A user guide

LEGRAND Wattstopper LMIN-104 installation instructions

LEGRAND

LEGRAND Wattstopper LMIN-104 installation instructions

PMK ATT10BNCS instruction manual

PMK

PMK ATT10BNCS instruction manual

Tektronix TDS3FFT user manual

Tektronix

Tektronix TDS3FFT user manual

Woodward easYgen Technical manual

Woodward

Woodward easYgen Technical manual

Balluff BNI EIP-502-105-R015 user guide

Balluff

Balluff BNI EIP-502-105-R015 user guide

NXP Semiconductors TWR-LS1021A Getting started

NXP Semiconductors

NXP Semiconductors TWR-LS1021A Getting started

Advantech PCM-3117 Startup manual

Advantech

Advantech PCM-3117 Startup manual

Danfoss MCO 101 manual

Danfoss

Danfoss MCO 101 manual

Moons' Lin Engineering R701P user manual

Moons'

Moons' Lin Engineering R701P user manual

Aventics RV1 operating instructions

Aventics

Aventics RV1 operating instructions

manuals.online logo
manuals.online logoBrands
  • About & Mission
  • Contact us
  • Privacy Policy
  • Terms and Conditions

Copyright 2025 Manuals.Online. All Rights Reserved.

9/13/2007 Using the WAGO 750-655 AS-i Module with the SMLC 1
Using the WAGO 750-655 AS-i Module with the SMLC
9/13/2007 Using the WAGO 750-655 AS-i Module with the SMLC 2
Introduction
The AS-interface master module 750-655 is
used to integrate the AS-interface network into
the WAGO-I/O-SYSTEM 750.
The AS-interface master module 750-655
behaves as a master for the AS-interface and as
a slave for the field bus. It complies with the
new AS-interface specification 2.1. This means
that:
• up to 62 AS-interface slaves can be connected
to the master
• the transmission of analog values is integrated
within the masters
• all other functions of the new specification,
such as the evaluation of peripheral errors, are
also implemented
The SMLC’s PLC Configuration supports using
the 750-655 with any of the 750 Series Ethernet
bus couplers.
9/13/2007 Using the WAGO 750-655 AS-i Module with the SMLC 3
From the WAGO manual
for the 750-655.
Up to three 750-655
modules can be
connected to one bus
coupler.
IMPORTANT: You
must have SMLC
firmware version 2.4.2
or later to use the 750-
655 module!
9/13/2007 Using the WAGO 750-655 AS-i Module with the SMLC 4
The 750-655 can be
configured in several
different operating modes.
In each of these modes
various process image
sizes can be selected,
allowing access to
increasing numbers of
AS-i slaves.
The SMLC requires that
the 750-655 be configured
in operating Mode 1 -
permanently configured
mailbox.
The SMLC requires the use of Mode 1
9/13/2007 Using the WAGO 750-655 AS-i Module with the SMLC 5
While the 750-655 can be configured for
many different process image sizes the
SMLC supports a limited number of these.
In the SMLC’s PLC Configuration you can
select from the following Mode 1 possible
configurations:
24 byte process image, 6 byte mailbox
12 byte process image, 6 byte mailbox
12 byte process image, 0 byte mailbox
40 byte process image, 0 byte mailbox
48 byte process image, 12 byte mailbox
The 0 byte mailbox configurations only
support digital slaves. If you intend to use
analog slaves you need to select a
configuration with a non-zero length
mailbox.
The table at the right shows all of the
possible Mode 1 configurations. The SMLC
only supports those listed above!
9/13/2007 Using the WAGO 750-655 AS-i Module with the SMLC 6
In order to decide which configuration you should insert into the SMLC’s PLC Configuration consider how many
slave devices you intend to use and whether they are all digital or if you will have some analog devices.
If you are going to use analog device you must use one of the configuration that supports the mailbox.
If you are going to use all digital devices you can pick one of the configurations with a 0 byte mailbox. The
advantage of the 0 byte mailbox is that the AS-i module will take up less memory in the bus coupler’s process
image, allowing you to install more I/O modules. Remember that the bus coupler is limited to 255 bytes of
inputs and 255 bytes of outputs and a maximum of 64 modules.
For example: if you know that you will have less then 20 digital AS-i devices and no analog devices then
selecting the 12 byte process image with a 0 byte mailbox is sufficient.
The table below shows how many slave devices can be supported for a given configuration. 7A indicates 7 slaves
on the A bus. 31A/31B indicates 31 slaves on the A bus and 31 slaves on the B bus, etc.
9/13/2007 Using the WAGO 750-655 AS-i Module with the SMLC 7
In order to configure the 750-655 AS-i module and to assign the slave device IDs you need to use
the WAGO I/O Check software (759-302). Connect the WAGO programming cable (750-920) to the
bus coupler and to a free serial port on your computer.
NOTE: If the Ethernet cable is plugged into the bus coupler, unplug it. WAGO I/O Check will not allow
you to configure the bus coupler while the fieldbus is active!
9/13/2007 Using the WAGO 750-655 AS-i Module with the SMLC 8
Start WAGO-I/O-Check configure the I/O Check COM port using the Settings menu.
In this example the cable is connected to COM2.
9/13/2007 Using the WAGO 750-655 AS-i Module with the SMLC 9
Start WAGO-I/O-Check and click on the Node Configuration icon to read the current configuration. In
this example we only have the 750-655 AS-i module and a 750-600 end module connected to a 750-342.
9/13/2007 Using the WAGO 750-655 AS-i Module with the SMLC 10
Click on the Settings button to configure the process image and mailbox size. The default settings are
24 byte process image and 6 byte fixed mailbox. The SMLC supports this configuration and this selection
allows you to access up to 31 AS-i slaves.
The SMLC does not support the Overlapped Mailbox so do not check this.
If you change any of the settings click the Apply button to send the new configuration to the bus coupler.