manuals.online logo
Brands
  1. Home
  2. •
  3. Brands
  4. •
  5. Watts
  6. •
  7. Control Unit
  8. •
  9. Watts CIVIC1 User manual

Watts CIVIC1 User manual

Other manuals for CIVIC1

1

Other Watts Control Unit manuals

Watts WFC-03 HCM RF 230 User manual

Watts

Watts WFC-03 HCM RF 230 User manual

Watts AMES Deringer 20 User manual

Watts

Watts AMES Deringer 20 User manual

Watts LFM113-19 User manual

Watts

Watts LFM113-19 User manual

Watts AMES 960GD-17 Installation and operating instructions

Watts

Watts AMES 960GD-17 Installation and operating instructions

Watts LFUSG-B-M1 User manual

Watts

Watts LFUSG-B-M1 User manual

Watts 007 Series Operating instructions

Watts

Watts 007 Series Operating instructions

Watts FRG3015-F RV User manual

Watts

Watts FRG3015-F RV User manual

Watts MINIMIXing User manual

Watts

Watts MINIMIXing User manual

Watts Ames 912GD-01 Owner's manual

Watts

Watts Ames 912GD-01 Owner's manual

Watts AMES LF960GD-15 Series User manual

Watts

Watts AMES LF960GD-15 Series User manual

Watts AMES 910GD-11 Installation and operating instructions

Watts

Watts AMES 910GD-11 Installation and operating instructions

Watts AMES 981GD User manual

Watts

Watts AMES 981GD User manual

Watts LFM127-32 Installation and operating instructions

Watts

Watts LFM127-32 Installation and operating instructions

Watts Ames 920GD-15 Owner's manual

Watts

Watts Ames 920GD-15 Owner's manual

Watts LFM113-21 Guide

Watts

Watts LFM113-21 Guide

Watts AMES Deringer 50 User manual

Watts

Watts AMES Deringer 50 User manual

Watts LF70A Series User manual

Watts

Watts LF70A Series User manual

Watts FEBCO 860 Small Series Operating instructions

Watts

Watts FEBCO 860 Small Series Operating instructions

Watts AMES 930GD User manual

Watts

Watts AMES 930GD User manual

Watts LFM116-31 Owner's manual

Watts

Watts LFM116-31 Owner's manual

Watts LFM127-2 Series Installation and operating instructions

Watts

Watts LFM127-2 Series Installation and operating instructions

Watts iDROSET CSD Series User manual

Watts

Watts iDROSET CSD Series User manual

Watts SENTINEL Hudrosolutions LEAK DEFENSE User manual

Watts

Watts SENTINEL Hudrosolutions LEAK DEFENSE User manual

Watts AMES LF981GD Series User manual

Watts

Watts AMES LF981GD Series User manual

Popular Control Unit manuals by other brands

Seitz 14A80 user manual

Seitz

Seitz 14A80 user manual

Wilo RS485 Installation and operating instructions

Wilo

Wilo RS485 Installation and operating instructions

Becker CentralControl CC41 Commissioning Instruction

Becker

Becker CentralControl CC41 Commissioning Instruction

SICK CDB650 operating instructions

SICK

SICK CDB650 operating instructions

Panduit NetKey NKP5E88M Series installation instructions

Panduit

Panduit NetKey NKP5E88M Series installation instructions

MX Options Concentric Petite Fitting instructions

MX

MX Options Concentric Petite Fitting instructions

Clean Water Systems Fleck 2510 Installation & start?up guide

Clean Water Systems

Clean Water Systems Fleck 2510 Installation & start?up guide

Fairchild FSB44104A user guide

Fairchild

Fairchild FSB44104A user guide

LEGRAND Wattstopper LMIN-104 installation instructions

LEGRAND

LEGRAND Wattstopper LMIN-104 installation instructions

PMK ATT10BNCS instruction manual

PMK

PMK ATT10BNCS instruction manual

Tektronix TDS3FFT user manual

Tektronix

Tektronix TDS3FFT user manual

Woodward easYgen Technical manual

Woodward

Woodward easYgen Technical manual

Balluff BNI EIP-502-105-R015 user guide

Balluff

Balluff BNI EIP-502-105-R015 user guide

NXP Semiconductors TWR-LS1021A Getting started

NXP Semiconductors

NXP Semiconductors TWR-LS1021A Getting started

Advantech PCM-3117 Startup manual

Advantech

Advantech PCM-3117 Startup manual

Danfoss MCO 101 manual

Danfoss

Danfoss MCO 101 manual

Moons' Lin Engineering R701P user manual

Moons'

Moons' Lin Engineering R701P user manual

Aventics RV1 operating instructions

Aventics

Aventics RV1 operating instructions

manuals.online logo
manuals.online logoBrands
  • About & Mission
  • Contact us
  • Privacy Policy
  • Terms and Conditions

Copyright 2025 Manuals.Online. All Rights Reserved.

Watts Industries Italia Srl Watts EW089.308_en – rev.1 Gas detection Control Unit – CIVIC1
28/03/2011 Gas detection systems for industrial environments 1 of 4
Watts Industries Italia S.r.l.
Via Brenno, 21
20853 Biassono (MB) - Italy
Phone +39 039 4986.1
Fax. +39 039 4986.222
e-mail: info@wattsindustries.it
Installation instructions Gas detection control unit CIVIC1
GENERAL
The CIVIC1 control unit can be used to connect one detector
(model UR13 or UR20S) to create gas detection systems in
environments such as boiler rooms, workshops, warehouses,
laboratories etc.; the incorporated alarm relay can be used to
control a solenoid valve or an accessory device (siren, flashing
light, extractor, etc.). The installation of a gas or carbon monoxide
detection system does not constitute a release from compliance
with all regulations for the installation and use of gas devices and
with the relative safety standards and legal provisions in force for
this kind of system. Installation, periodic inspections and
maintenance of devices and systems must be carried out by
qualified service technicians.
TECHNICAL SPECIFICATIONS
CIVIC1 control unit (data with UR20S detectors in
brackets)
Power supply: 12 Vac/dc 10%
Consumption: about 160mA (320mA) with the detector only
460mA (620mA) with detector and failure
output
Connections: two terminals of 2.5 mm2
Protection: Power input fuse 1A 5x20mm
Inputs: one, for UR13, or UR20Sdetectors (different
types of gas)
Detector connection: three terminals of 2.5 mm2:
C (-12...24V); S (+4…20mA); A (+12...24V)
Max cable run length: 50 m
Diameter of the 3 wires: 1.5 mm2
Alarm output: 1 relay with one contact SPDT 8A 250Vac
Failure output: one open collector 12Vdc / 300mA max
Output connections: three terminals of 2.5 mm2for C-NC-NO relay
two terminals of 2.5 mm2for open collector
Visual alarms: 1 green LED: power on
1 yellow LED: failure
1 red LED: gas alarm
Audible alarms: 1 buzzer noise level > 60db at 1m
“Reset/Test” button: 1 for alarm Reset and detector Test
Enclosure: RAL7035 grey, self-extinguishing plastic house
Dimensions and weight: 105x90x58 mm (6 modules to standard DIN
43880), 185 g
Mounting: Back panel Omega DIN rail (EN50022)
Protection rating: IP20; IP40 when correctly installed in
electric panel
Room temperature: 0 50 °C
Humidity 90% RH (non condensing)
EC Conformity
Product standards: Standards EN 60079-29-1; CEI 216-5/1
LV Directives/Standards LV 2006/95/EC, Standard EN 60730-1
EMC Directives/Standards EMC 2004/108/EC, Standard EN 50270
URx13 (URx20..) detectors
Power supply: from the UCE1 control unit
Consumption: 40 mA (200mA)
Connections: three terminals of 2.5 mm2:
C (-12...24V); S (+4…20mA); A (+12...24V)
URx13 models: Methane Gas Cod. 0940561
LPG Cod. 0940562
Carbon monoxide Cod. 0940563
UR20S models: Various gases, see dedicated data sheet
Calibration UR13: 10% LEL of Methane
12% LEL of Isobutane
200ppm of CO
(UR20S 20% LEL combustibles, 100ppm CO)
Enclosure: self-extinguishing plastic
Dimensions and weight: 66x90x45 mm (depending on model), 65 g
Mounting: wall-mounted using plastic screws and anchors
Protection: IP44 (IP44, IP55 or IP65 depending on model)
Room temperature: 0 50 °C (-20 +50°C)
Humidity: 90% RH (non condensing)
LVD Directives/Standards Not applicable
EMC Directives/Standards EMC 2004/108/EC, Standard EN 50270
Other features of UR20S detectors
See technical features on dedicated data sheet.
INSTALLATION
MOUNTING
Ensure correct environmental conditions (See Technical
Specifications).
CIVIC1 control unit
To guarantee the correct protection rating for the device it must
be installed in an electric panel manufactured according to the
laws in force for workplaces and that can also house the power
supply system. Mount the control unit on a rail (to DIN EN
50022), using accessories for standard electric panels. It can be
installed on a mounting plate or in DIN rail modules.
UR13 (UR20S) detectors
To be used for wall-mounting (vertical), attached by plastic
screws and anchors. To install, insert a screwdriver in the recess
at the bottom of the enclosure to open it; avoid damage to the
sensor and do not touch the calibration devices. The detectors
must be correctly positioned for the system to operate properly.
For this purpose, the control units must be installed:
-in zones with constant natural air circulation
-in zones free of dust and dirt that could clog up the sensor and
make it ineffective
-never near running water, exhaust vents, windows, openings
etc.
-at a suitable distance from the gas-fuelled equipment to avoid
the system taking inappropriate action due to possible
functional loss.
The positioning also depends on the type of gas that is to be
detected, in particular:
-UR13: Methane gas - high, about 20-30 cm from ceiling
-UR13: LPG - low, about 20-30 cm from floor
-UR13: CO - about 1.5 m from floor
For new plants, the detector must be installed at the last possible
moment so that typical worksite activities (particularly welding,
painting, sealing etc.), do not damage the actual detector
(particularly the sensing element).
UR20S detectors
See installation instructions on dedicated data sheet.
ELECTRICAL CONNECTIONS
Normal electric cables can be used. Still, if detectors are to be
installed in environments with high exposure to EMI, it is
advisable to use shielded cables. The detection system must
always be operating, so power switches or other devices that
could inadvertently make the detector inoperative must not be
used. Do not touch the sensing element and the electronic circuits
for any reason whatsoever. Tampering of any kind may cause the
system to operate incorrectly.
Ensure compliance with all current electric standards.
Watts Industries Italia Srl Watts EW089.308_en – rev.1 Gas detection Control Unit – CIVIC1
28/03/2011 Gas detection systems for industrial environments 2 of 4
CIVIC1 control unit
The control unit must be powered at 12 Vac/dc; use transformers
with double insulation, sized for uninterrupted use for the power
utilised (See Technical specifications).
For connecting the relay output use wires with a minimum
diameter of 1.5 mm2.
Prepare wiring connections according to the electrical diagrams
contained in these instructions.
UR13 or UR20S detector
Prepare wiring connections according to the electrical diagrams
contained in these instructions, using wires with a minimum
diameter of 1.5 mm2for a maximum length of 50 m.
COMMISSIONING
The CIVIC1 control unit and the UR13 or UR2S detectors are
safety control devices, therefore they must not be tampered with;
do not touch the sensor or the electronics for any reason
whatsoever. Carry out the following controls:
-the power supply for the control unit must comply with the
values provided (12 Vac/dc 10%)
-make sure the power consumed by any device connected to the
relay terminals is below or the same as the maximum capacity
of the contacts (See Technical specifications)
-make sure the consumption of any device connected to the
open collector output terminals is below what is declared in the
technical data
-the detector must be compatible with the type of gas to
monitor and correctly connected to the control unit.
Depending on the type of detector to connect it is necessary to
position jumpers E5 and E6 as follows:
-the operating mode (positive or negative logic) selected must
be consistent with the system choices. As regards this, check
the position of Jumper E1 (See Operation)
-the operating mode selected for the relay must be consistent
with the system choices. As regards this, check the position of
Jumper E2 (See Operation)
-test the gas alarm and the detector failure condition events
(See Operation).
OPERATION
The Jumper E1 can be used to select the operating mode (positive
or negative logic).
The control unit signals its operating status through LEDs.
Depending on the operating mode selected through Jumper E1, in
a normal situation (no alarm), the LEDs, the OC output and the
relay are as follows:
positive operating logic: LEDs on; relay energised, OC output =
ON
negative operating logic: LEDs off; relay de-energised, OC
output= OFF
If the negative operating logic is selected, the alarm relay can be
permanently or impulse controlled, depending on the position of
Jumper E2:
Once the correct power is supplied, the control unit carries out the
following phases in sequence:
LED and buzzer tests (about 5 seconds)
Whichever operating mode is selected, the LEDs will switch on in
sequence and the buzzer will sound briefly.
Warm-up of detector (about 1 minute)
During this phase, which brings the detector up to the correct
operating temperature, the gas detection system is not
operational. During this phase, if the wiring connections are
correct, the control unit display shows the following:
Operating test (about 3 minutes)
Once the detector warm-up phase is complete, the device enters
the operating test phase. During this phase, all internal timing is
reset to ease operating verification of the detector (alarm
simulation). In this case, the control unit display shows the
following:
Keep the “Reset/Test” button pressed down for over 1 second to
interrupt the operating test phase. To test the detector correctly,
proceed as follows:
Gas alarm test:
Bring the test cylinder close to the detector grille and release a
small amount of gas (caution: if the gas is aimed directly at the
sensor, this will be permanently damaged). For CO testing of
detector, smoke produced by combustion can be used. The control
unit will signal the alarm as follows:
Keep the “Reset/Test” button pressed down for 1 second to
silence the alarm (if there is no gas remaining) and terminate the
operating test phase. To restart the Test phase, just keep the
relative button pressed down for about 6 seconds.
Caution The repeated use or high concentration of
interfering substances (alcohol, lighter fluid etc.)
can cause permanent damage to the sensor and
put the device out of order.
Interface Positive logic Negative logic
Power supply LED Green Flashing 1 Hz Flashing 1 Hz
Failure LED Yellow On Off
Gas alarm LED Red On Off
Alarm buzzer No sound No sound
Alarm relay Energised De-energised
Failure output On Off
Interface Positive logic Negative logic
Power supply LED Green Flashing 2 Hz Flashing 2 Hz
Failure LED Yellow On Off
Gas alarm LED Red On Off
Alarm buzzer No sound No sound
Alarm relay Energised De-energised
Failure output On Off
E2
A
B
E2
A
B
E2
A
B
Posizione A
Relè di allarme
Comando permanente
Posizione B
Relè di allarme
Comando impulsivo
E1
A
B
E1
A
B
E1
A
B
Posizione A
Logica positiva
Posizione B
Logica negativa
E2
A
B
E2
A
B
E2
A
B
E2
A
B
E2
A
B
E2
A
B
Posizione A
Relè di allarme
Comando permanente
Posizione B
Relè di allarme
Comando impulsivo
E1
A
B
E1
A
B
E1
A
B
E1
A
B
E1
A
B
E1
A
B
Posizione A
Logica positiva
Posizione B
Logica negativa
Interface Positive logic Negative logic
Detector alarm LED Red Off On
Alarm buzzer Continuous sound Continuous sound
Alarm relay De-energised Energised
(permanently or
pulsed depending
on E2)
Failure output Off On
E3
A
B
E6
Posizione (default)
per Sonda URx13
E5
E5
Posizione per
Sonda URx20..
E6
E3
A
B
E3
A
B
E6
Posizione (default)
per Sonda URx13
E5
E3
A
B
E3
A
B
E6
Posizione (default)
per Sonda URx13
E5
E5
Posizione per
Sonda URx20..
E6
E3
A
B
E5
Posizione per
Sonda URx20..
E6
E3
A
B
E3
A
B
(default) position of
detector UR
13
position of detector
UR
20
S
Position A
Positive logic
Position B
Negative logic
Position A
A
larm relay
Permanent control
Position B
A
larm relay
Pulse control
Watts Industries Italia Srl Watts EW089.308_en – rev.1 Gas detection Control Unit – CIVIC1
28/03/2011 Gas detection systems for industrial environments 3 of 4
Detector failure test
Simulate a failure in the detector as follows:
-disconnect the cable of the detector and verify the following
alerts:
-reconnect the detector and press the “Reset/Test” to return the
control unit to normal operating mode, making the sure the
conditions of the various interfaces are reset
Normal operation
This is the normal operating phase of the control unit during which
both gas alarm monitoring and self-testing of the instrument
(detector) and the system (control unit) are active. During this
phase, where there are no alarms and/or abnormalities, the
control unit display shows the following:
When dangerous concentrations of gas are detected, the control
unit enters the gas alarm phase and carries out the following
operations:
Once the gas alarm condition is normalised, the control unit needs
to be reset to its normal operating status. Press the “Reset/Test
button on the front of the control unit to reset it.
If there are abnormalities (detector and/or control unit), the
control unit will show the following display:
Once the failure is fixed, the control unit needs to be reset to its
normal operating status. Press the “Reset/Test button on the front
of the control unit to reset it.
Caution: it is advisable to repeat the operating test at least
once a year, or after a prolonged period of
stoppage and in any case, every time the detector
is replaced.
Caution The average lifetime of the UR13 and UR20S
detectors is 5 years from installation date. They
must be replaced before the end of the 5th year
of use. The average lifetime of detectors is
calculated for use in a typical environment,
normally free from polluting agents (gases,
solvents etc.). More frequent and higher
concentrations of these substances can
accelerate the normal oxidisation process of the
sensing element, subsequently shortening its
lifetime.
GAS ALARM
If an alarm signals a gas leak or the presence of carbon
monoxide, proceed as follows:
-put out flames and switch off all gas equipment
-do not for any reason switch on or off lights or any electrical
equipment
-open doors and windows to air the environment
-look for and eliminate the cause of the alarm. If this is not
possible, leave the building and contact emergency services
from outside.
ENVIRONMENTAL COMPATIBILITY AND DISPOSAL
This product has been designed and constructed
using materials and processes that take into account
the environmental issue. Refer to the following notes for disposal
of the product at the end of its working life, or when it is replaced:
-for disposal purposes, this product is classified as an electric
and electronic device: do not dispose of it with normal
household waste, in particular as regards the printed circuit
-comply with all local laws in force
-as far as possible reuse basic materials to keep environmental
impact to a minimum
-use local depots and waste recycling companies, or contact the
supplier or manufacturer to return used products or to ask for
information on environmental compatibility and waste disposal
-the product packaging can be reused. Keep it for future use or
to return the product to the supplier.
TROUBLESHOOTING
Problem Possible cause
NC valve does not open
-Valve not connected
-Alarm in progress
-Detector warm-up phase in
progress
-Defective detector
-Presence of failure
NO valve does not close
-Valve not connected
-Connection cables cut
-No alarm active
“Reset/Test” button does not
reset to initial conditions
-Alarm in progress
-Failure occurring in control
unit
Interface Positive logic Negative logic
Detector Failure LED Yellow Off On
Alarm buzzer Intermittent
sound
Intermittent sound
Failure output Off On
Interface Positive logic Negative logic
Power supply LED Green On On
Failure LED Yellow On Off
Gas alarm LED Red On Off
Alarm buzzer No sound No sound
Alarm relay Energised De-energised
Failure output On Off
Interface Positive logic Negative logic
Detector alarm LED Red Off On
Alarm buzzer Continuous
sound
Continuous sound
Alarm relay De-energised Energised
(permanently or
pulsed depending
on E2)
Failure output On Off
Interface Positive logic Negative logic
Failure LED Yellow Off On
Alarm buzzer Intermittent
sound Intermittent
sound
Failure output On Off
Watts Industries Italia Srl Watts EW089.308_en – rev.1 Gas detection Control Unit – CIVIC1
28/03/2011 Gas detection systems for industrial environments 4 of 4
TERMINAL MODULE
+(TB1) Power supply 12 Vac/dc (positive)
-(TB1) Power supply 12 Vac/dc (negative)
+(TB3) OC output 12 Vac/dc (positive)
-(TB3) OC output 12 Vac/dc (negative)
CAlarm Alarm relay output (common)
NC Alarm Alarm relay output (Normally Closed contact)
NO Alarm Alarm relay output (Normally Open contact)
UR13 detector connections
CDetector input (C, common)
S Detector input (S, signal)
A Detector input (A, power supply 6.5V)
UR20S detector connections
CDetector input (+12...…24V, negative power supply/signal)
SDetector input (+4...…20mA, positive signal)
ADetector input (+12…...24V, positive power supply/signal)
DESCRIPTION GAS DETECTION CONTROL UNIT
1 TB1 - Power supply terminals 12 Vac/dc
2Protection fuse 1A
3TB3 - “Failure” open collector terminals
4TB2 - “Alarm” relay terminal block
5LED signalling presence of current
6LED failure alert
7Gas alarm LED alert
8Reset/Test button
9TB4 - Gas detector connection terminals
10 Jumper E5E6 for configuration of detector inputs:
E5 - Sel. power supply: A=6.5V (UR13), B=12V (UR20)
E6 - Sel. input A=threshold (UR13), B=4...20mA (UR20S)
11 Set-up jumper:
E1 – operating mode
E2 – Alarm relay operating mode
E3 – selection detector type: omitted=UR13, A=UR20S
E4 – available
12 Connector P1 (communication – not used)
13 CN1 connector and service Jumper J1
CONNECTION DIAGRAMS
Control unit with NA solenoid valve, negative mode.
N1 CIVIC1 control unit
B1 UR13 or UR20S detector
Y1 NA gas solenoid valve (Vaux: 24230Vac)
L1 Failure alert device (12 V/300 mA max)
DIMENSIONS
CIVIC1 control unit 58
48
33
105
90
62
45
TB1
TB2
TB3
CIVIC1
58
48
33
105
90
62
45
TB1
TB2
TB3
58
48
33
105
90
62
45
TB1
TB2
TB3
CIVIC1
UR13 (or UR20S) detectors
UR20S. detectors
Depending on model (see dedicated technical data sheet).
Installation data Installer's stamp
Control unit installation date:
Detector replacement date:
+
-
NO
C
S
A
C
NC
TB2
TB1
TB4
Allarme
+
-
TB3
+
-
NO
C
NO
C
S
A
C
NC
TB2
TB1
TB4
Allarme
+
-
TB3
Alarm
+S A
C
-NO
C
NC
S A
C
B1
12 Vac/dc
12 Vac/dc
N1
Y1
Vaux
Vaux
Allarme
+-
L1
-12…24V
+4…20mA
+12…24V
URx20..
URx13
+S A
C
-NO
C
NC
S A
C
B1
12 Vac/dc
12 Vac/dc
N1
Y1
Vaux
Vaux
Allarme
+-
L1
-12…24V
+4…20mA
+12…24V
URx20..
URx13
Alarm
12 3
11 910
12
8
567
13
4
CIVIC1
11 22 33
11 9910
12
88
55 66 77
13
44
CIVIC1