wattstopper LMUC-100 User manual

Quick Start Guide
SENSOR PLACEMENT 10’ MAX. HEIGHT
CONNECTIVITY
The illustrations below show examples of free-topology wiring. The LMDC-100 communicates to all other Digital Lighting
Management devices connected to the low voltage DLM Local Network, regardless of their position on the DLM Local Network.
LMUC-100
Digital Lighting Management
Ultrasonic Ceiling Mount
Occupancy Sensor
31.6’
9.63m
max.
31.6’
9.63m
max.
Sensor Sensor
30’
9.14m
50’
15.24m
Strong air
supply
6’
Sensor
Mount sensor at least 6’ away
from strong air supply
Line
Voltage
Room
Controller
J-Boxes
Daylight Sensor
SwitchSwitch
Corner Mount
Sensor
Ceiling Mount
Sensor
DLM Local Network
Low Voltage
LMRJ Cables
Loads
2
1
Line/Hot
Black wire
Neutral
White wire
Red wire
to Load A (1)
Yellow wire
to Load B (2)
LMRC
102
Room
Controller
J Box
Ceiling Mount
Occupancy
Sensor
Switch
To
Load
Voltage: .....................................................................................24VDC
Current Consumption:...............................................................20mA
Power Supply:...................Watt Stopper/Legrand Room Controllers
Connection to the DLM Local Network........................ 2 RJ-45 ports
DLM Local Network Characteristics:
Provides low voltage power over Cat 5e cable (LMRJ).
Supports up to 24 communicating devices, including 4
LMRC-10x or LMPL-101 max per each DLM Local Network
Free topology up to 1,000ft of low voltage cable.
Environment .......................................................For Indoor Use Only
Operating Temperature ................. 32° to 131°F (0° to 55°C)
Storage Temperature....................23° to 176°F (-5° to 80°C)
Relative Humidity........................ 5 to 95% (non condensing)
Patent Pending
THIS UNIT IS PRESET FOR PLUG N’ GO™
OPERATION, ADJUSTMENT IS OPTIONAL.
For full operational details, adjustment and more
features of the product, see the DLM System Installation
Guide supplied with the LMRC-102 and also available at
www.wattstopper.com
INSTALLATION SHALL BE
IN ACCORDANCE WITH ALL
APPLICABLE REGULATIONS,
LOCAL AND NEC CODES.
Intended for Listed Class 2 DLM
Devices.
For Class 2 DLM devices -
To be connected to a Class 2
power source only.
For Class 2 Device Wiring Only –
Do Not Reclassify and Install as
Class 1, or Power and Lighting
Wiring.
Wire connections shall be rated
suitable for the wire size (lead
and building wiring) employed.
31.6 ft
9.63m
22.3 ft
6.79m
Minor Motion
Major Motion
COVERAGE PATTERN
The LMUC-100 provides a 360° coverage pattern.The
coverage shown represents maximum coverage for
walking motion at a mounting height of 8 to 10 feet.
TROUBLESHOOTING
Loads do not operate as expected.
LEDs don’t light, display
is off
1. Check to see that the the sensor is connected to the DLM local Network.
2. Check for 24VDC input to the sensor: Plug in a different DLM device at the sensor location.
If the device does not power up, 24VDC is not present.
• Check the high voltage connections to the room controller.
• If high voltage connections are good and high voltage is present, recheck DLM local
Network connections between the sensor and the room controller.
The wrong lights are
controlled
1. Configure the sensor to control the desired lights using the Push n’ Learn adjustment
procedure.
LEDs turn ON and OFF but
load doesn’t switch
1. Make sure device is not in PnL.
2. Check load connections to room controller.
10/2014
11438r2
Please
Recycle
2800 De La Cruz Blvd.
Santa Clara, CA 95050
Phone: 800.879.8585
www.wattstopper.com
MOUNTING
Rear
housing
4" Octagonal J-Box
(at least 1.5" deep)
Front cover
Ceiling
Rear
housing
Front cover
Ceiling hole
LMRJ cable
LMRJ cable
Spring clips (2)
Screws
For applications requiring plenum rating No box required in non-plenum rated applications
To octagon box: Through ceiling tile:
WARNING: TO CONNECT A COMPUTER TO THE DLM LOCAL
NETWORK USE THE LMCI100. NEVER CONNECT THE DLM LOCAL
NETWORK TO AN ETHERNET PORT  DOING SO MAY DAMAGE
COMPUTERS AND OTHER CONNECTED EQUIPMENT.
WARNING: A junction box used for sensor installation must not contain any Class 1, Class 3, or other power or
lighting line voltage circuits
Load Parameters
Load 1 Loads 2-8
or more**
Plug Load
ON Mode
Operation* AUTO-ON
MANUAL-ON
if switch is
connected.
AUTO-ON
if no switch.
AUTO-ON
Blink Warning OFF OFF OFF
Daylighting ON OFF OFF
* Auto-OFF is enabled according to the sensor Time
Delay when a sensor is bound to the load, regardless
of whether the load was turned on automatically with
occupancy or manually using a switch.
** Max 8 loads using LMRC-100 series room controllers.
FACTORY PRESET OPERATION
Sensor Parameters
T-DELAY Time Delay 20 minutes
Ultrasonic Sensitivity 70%
W-T Walk Through OFF

Other wattstopper Security Sensor manuals

wattstopper Legrand LMPX-100 User manual

wattstopper

wattstopper Legrand LMPX-100 User manual

wattstopper CI-300 User manual

wattstopper

wattstopper CI-300 User manual

wattstopper EW-105-24 User manual

wattstopper

wattstopper EW-105-24 User manual

wattstopper WS-250 User manual

wattstopper

wattstopper WS-250 User manual

wattstopper CX-105 User manual

wattstopper

wattstopper CX-105 User manual

wattstopper LMDW-101 User manual

wattstopper

wattstopper LMDW-101 User manual

wattstopper Legrand LMPX-100-1 User manual

wattstopper

wattstopper Legrand LMPX-100-1 User manual

wattstopper LMDC-100 User manual

wattstopper

wattstopper LMDC-100 User manual

Popular Security Sensor manuals by other brands

koban KCL-01 manual

koban

koban KCL-01 manual

Trotec BE15 operating manual

Trotec

Trotec BE15 operating manual

Cliplight 580952 user manual

Cliplight

Cliplight 580952 user manual

ITALIANA SENSORI 8086-ISR057 quick start guide

ITALIANA SENSORI

ITALIANA SENSORI 8086-ISR057 quick start guide

Edimax AI-2003W Quick installation guide

Edimax

Edimax AI-2003W Quick installation guide

B.E.G. LUXOMAT PD9-S manual

B.E.G.

B.E.G. LUXOMAT PD9-S manual

Niko Nikobus 430-00502 manual

Niko

Niko Nikobus 430-00502 manual

Optex SL-100 TNR installation instructions

Optex

Optex SL-100 TNR installation instructions

Pima DPC Series installation instructions

Pima

Pima DPC Series installation instructions

teko Astra-5131 quick start guide

teko

teko Astra-5131 quick start guide

Rielta PYRONE-5 installation guide

Rielta

Rielta PYRONE-5 installation guide

Optex RLS-3060 installation instructions

Optex

Optex RLS-3060 installation instructions

Omron Z4D-F manual

Omron

Omron Z4D-F manual

olympia electronics tuv BS-360 Installation

olympia electronics

olympia electronics tuv BS-360 Installation

Monacor MOUSE-09 manual

Monacor

Monacor MOUSE-09 manual

SICK ELS35 operating instructions

SICK

SICK ELS35 operating instructions

Rosslare SA-20 installation manual

Rosslare

Rosslare SA-20 installation manual