Weber captor PAX Series User manual

w
eber
P
AX-Panel Meters
MODEL PAX – 1/8 DIN ANALOG INPUT PANEL METERS
•
PROCESS, VOLTAGE, CURRENT, TEMPERATURE, AND STRAIN
GAGE INPUTS
• 5-DIGIT 0.56" RED SUNLIGHT READABLE DISPLAY
• VARIABLE INTENSITY DISPLAY
• 16 POINT SCALING FOR NON-LINEAR PROCESSES
• PROGRAMMABLE FUNCTION KEYS/USER INPUTS
• 9 DIGIT TOTALIZER (INTEGRATOR) WITH BATCHING
• OPTIONAL CUSTOM UNITS OVERLAY W/BACKLIGHT
• FOUR SETPOINT ALARM OUTPUTS (W/OPTION CARD)
• COMMUNICATION AND BUS CAPABILITIES (W/OPTION CARD)
• RETRANSMITTED ANALOG OUTPUT (W/OPTION CARD)
• PC SOFTWARE AVAILABLE FOR METER CONFIGURATION
• NEMA 4X/IP65 SEALED FRONT BEZEL
GENERAL DESCRIPTION
The PAX Analog Panel Meters offer many features and performance
capabilities to suit a wide range of industrial applications. Available in five
different models to handle various analog inputs, including DC Voltage/Current,
AC Voltage/Current, Process, Temperature, and Strain Gage Inputs. Refer to
p
ages 4 through 6 fo
r
the details on the specific models. The optional plug-in
output cards allow the opportunity to configure the meter for present
applications, while providing easy upgrades for future needs.
The meters employ a bright 0.56" LED display. The unit is available with a
red sunlight readable or a standard green LED. The intensity of display can be
adjusted from dark room applications up to sunlight readable, making it ideal
for viewing in bright light applications.
The meters provide a MAX and MIN reading memory with programmable
capture time. The capture time is used to prevent detection of false max or min
readings which may occur during start-up or unusual process events.
The signal totalizer (integrator) can be used to compute a time-input product.
This can be used to provide a readout of totalized flow, calculate service
intervals of motors or pumps, etc. The totalizer can also accumulate batch
weighing operations.
The meters have four setpoint outputs, implemented on Plug-in option cards.
The Plug-in cards provide dual FORM-C relays (5A), quad FORM-A (3A), o
r
either quad sinking or quad sourcing open collector logic outputs. The setpoin
t
alarms can be configured to suit a variety of control and alarm requirements.
Communication and Bus Capabilities are also available as option cards.
These include RS232, RS485, Modbus, DeviceNet, and Profibus-DP. Readou
t
values and setpoint alarm values can be controlled through the bus.
Additionally, the meters have a feature that allows a remote computer to directl
y
control the outputs of the meter. With an RS232 or RS485 card installed, it is
p
ossible to configure the meter using a Windows®based program.
The configuration data can be saved to a file for later recall.
DIMENSIONS In inches (mm) Note: Recommended minimum clearance (behind the panel) for mounting clip installation
is 2.1" (53.4) H x 5.0" (127) W.
A linear DC output signal is available as an optional Plug-in card. The card
p
rovides either 20 mA or 10 V signals. The output can be scaled independent o
f
the input range and can track either the input, totalizer, max or min readings.
Once the meters have been initially configured, the parameter list may be
locked out from further modification in its entirety or only the setpoint values
can be made accessible.
The meters have been specifically designed for harsh industrial environments.
With NEMA 4X/IP65 sealed bezel and extensive testing of noise effects to CE
requirements, the meter provides a tough yet reliable application solution.
SAFETY SUMMARY
All safety related regulations, local codes and instructions that appear in this
literature or on equipment must be observed to ensure personal safety and to
p
revent damage to either the instrument or equipment connected to it. I
f
equipment is used in a manner not specified by the manufacturer, the protection
p
rovided by the equipment may be impaired.
Do not use this unit to directly command motors, valves, or other actuators
not equipped with safeguards. To do so can be potentially harmful to persons o
r
equipment in the event of a fault to the unit.
weber
S e n s o r sG m b H
•Strohde ich 32 • D-2 5377 • Ko llmar • Te l.: +49 4128-591 • [email protected]
1

2
Ordering Information . . . . . . . . . . . . . . . . . . 2
General Meter Specifications . . . . . . . . . . . . 3
Universal DC Input Panel Meter . . . . . . . . . . 4
Process Input Panel Meter . . . . . . . . . . . . . . 4
AC True RMS Voltage and Current Meter . . . 5
Strain Gage Input Panel Meter . . . . . . . . . . . 5
Thermocouple and RTD Input Meter . . . . . . 6
Optional Plug-In Cards . . . . . . . . . . . . . . . . . 7
Installing the Meter . . . . . . . . . . . . . . . . . . . . 8
Setting the Jumpers . . . . . . . . . . . . . . . . . . . 8
Wiring the Meter . . . . . . . . . . . . . . . . . . . . . 10
Reviewing the Front Buttons and Display . . 13
Programming the Meter . . . . . . . . . . . . . . . 14
Factory Service Operations . . . . . . . . . . . . 23
Parameter Value Chart . . . . . . . . . . . . . . . . 25
Programming Overview . . . . . . . . . . . . . . . 27
TABLE OFCONTENTS
ORDERING INFORMATION
PAX 0 0
D - DC Volt/ Current Input
P - Process Input
H - AC True RMS Volt/Current Input
S - Strain Gage/Bridge Input
T - Thermocouple and RTD Input
0 - Red, Sunlight Readable Display
1 - Green Display
0 - 85 to 250 VAC
1 - 11 to 36 VDC, 24 VAC
Meter Part Numbers
Option Card and Accessories Part Numbers
SFPAXPC Configuration Software for Windows 3.x and 95 (3.5" disk)SFPAX*
Accessories PAXLBK10Units Label Kit Accessory (Not required for PAXT)PAXLBK
PAXCDC4C
PAXCDC40
PAXCDC30
Extended Modbus Communications Card with Dual RJ11 Connector
Modbus Communications Card
DeviceNet Communications Card
Optional
Plug-In
Cards
PAXCDC50
PAXCDL10
Profibus-DP Communications Card
Analog Output CardPAXCDL
PAXCDC2C
PAXCDC20
Extended RS232 Serial Communications Output Card with 9 Pin D Connector
RS232 Serial Communications Output Card with Terminal Block
PAXCDC1C
PAXCDC10
PAXCDC
PAXCDS40Quad Setpoint Sourcing Open Collector Output Card
PAXCDS30Quad Setpoint Sinking Open Collector Output Card
PAXCDS20Quad Setpoint Relay Output Card
TYPE
PAXCDS10Dual Setpoint Relay Output Card
PAXCDS
PART NUMBERSDESCRIPTIONMODEL NO.
*Software can be downloaded from www.redlion.net
RS485 Serial Communications Output Card with Terminal Block
Extended RS485 Serial Communications Output Card with Dual RJ11 Connector
PAX-D.QXD 10/11/04 11:38 AM Page 2

3
GENERAL METER SPECIFICATIONS
1. DISPLAY: 5 digit, 0.56" (14.2 mm) red sunlight readable or standard green
LEDs, (-19999 to 99999)
2. POWER:
AC ersions:
AC Power: 85 to 250 AC, 50/60 Hz, 15 A
Isolation: 2300 rms for 1 min. to all inputs and outputs.
DC ersions (Not available on PAXH):
DC Power: 11 to 36 DC, 11 W
(derate operating temperature to 40° C if operating <15 DC and three
plug-in option cards are installed)
AC Power: 24 AC, ± 10%, 50/60 Hz, 15 A
Isolation: 500 rms for 1 min. to all inputs and outputs (50 working).
3. ANNUNCIATORS:
MAX - maximum readout selected
MIN - minimum readout selected
TOT - totalizer readout selected, flashes when total overflows
SP1 - setpoint alarm 1 is active
SP2 - setpoint alarm 2 is active
SP3 - setpoint alarm 3 is active
SP4 - setpoint alarm 4 is active
Units Label - optional units label backlight
4. KEYPAD: 3 programmable function keys, 5 keys total
5. A/D CONVERTER: 16 bit resolution
6. UPDATE RATES:
A/D conversion rate: 20 readings/sec.
Step response: 200 msec. max. to within 99% of final readout value
(digital filter and internal zero correction disabled)
700 msec. max. (digital filter disabled, internal zero correction enabled)
PAXH Only: 1 sec max. to within 99% of final readout value (digital filter
disabled)
Display update rate: 1 to 20 updates/sec.
Setpoint output on/off delay time: 0 to 3275 sec.
Analog output update rate: 0 to 10 sec
Max./Min. capture delay time: 0 to 3275 sec.
7. DISPLAY MESSAGES:
“OLOL” - Appears when measurement exceeds + signal range.
“ULUL” - Appears when measurement exceeds - signal range
PAXT: “SHrt” - Appears when shorted sensor is detected. (RTD only)
PAXT: “OPEN” - Appears when open sensor is detected.
“. . . .” - Appears when display values exceed + display range.
“- . . .” - Appears when display values exceed - display range.
8. INPUT CAPABILITIES: See specific product specifications, pages 4-6
9. EXCITATION POWER: See specific product specifications, pages 4-6
10. LOW FREQUENCY NOISE REJECTION: (Does not apply to PAXH)
Normal Mode: > 60 dB @ 50 or 60 Hz ±1%, digital filter off
Common Mode: >100 dB, DC to 120 Hz
11. USER INPUTS: Three programmable user inputs
Max. Continuous Input: 30 DC
Isolation To Sensor Input Common: Not isolated. (Not PAXH)
PAXH: Isolation to Sensor Input Common: 1400 rms for 1 min.
Working oltage: 125
Response Time: 50 msec. max.
Logic State: Jumper selectable for sink/source logic
12. TOTALIZER:
Function:
Time Base: second, minute, hour, or day
Batch: Can accumulate (gate) input display from a user input
Time Accuracy: 0.01% typical
Decimal Point: 0 to 0.0000
Scale Factor: 0.001 to 65.000
Low Signal Cut-out: -19,999 to 99,999
Total: 9 digits, display alternates between high order and low order readouts
13. CUSTOM LINEARIZATION:
Data Point Pairs: Selectable from 2 to 16
Display Range: -19,999 to 99,999
Decimal Point: 0 to 0.0000
PAXT: Ice Point Compensation: user value (0.00 to 650.00 µ /°C)
14. MEMORY: Nonvolatile E2PROM retains all programmable parameters
and display values.
15. ENVIRONMENTAL CONDITIONS:
Operating Temperature Range: 0 to 50°C (0 to 45°C with all three plug-in
cards installed)
Storage Temperature Range: -40 to 60°C
Operating and Storage Humidity: 0 to 85% max. RH non-condensing
Altitude: Up to 2000 meters
16. CERTIFICATIONS AND COMPLIANCES:
SAFETY
UL Recognized Component, File #E179259, UL3101-1, CSA C22.2 No.
1010-1
PAXT Only: File # E156876, UL873, CSA C22.2 No. 24
Recognized to U.S. and Canadian requirements under the Component
Recognition Program of Underwriters Laboratories, Inc.
UL Listed, File # E137808, UL508, CSA C22.2 No. 14-M95
LISTED by Und. Lab. Inc. to U.S. and Canadian safety standards
Type 4X Enclosure rating (Face only), UL50
IECEE CB Scheme Test Certificate #US/7470A/UL
CB Scheme Test Report #03ME09282-08292003
Issued by Underwriters Laboratories, Inc.
IEC 1010-1, EN 61010-1: Safety requirements for electrical equipment
for measurement, control, and laboratory use, Part I
IP65 Enclosure rating (Face only), IEC 529
IP20 Enclosure rating (Rear of unit), IEC 529
ELECTROMAGNETIC COMPATIBILITY
Notes:
1. Self-recoverable loss of performance during EMI disturbance at 10 V/m:
Measurement input and/or analog output signal ma deviate during
EMI disturbance.
For operation without loss of performance:
Unit is mounted in a metal enclosure (Bucke e SM7013-0 or equivalent)
I/O and power cables are routed in metal conduit connected to earth
ground.
Refer to EMC Installation Guidelines section of the bulletin for additional
information.
17. CONNECTIONS: High compression cage-clamp terminal block
Wire Strip Length: 0.3" (7.5 mm)
Wire Gage: 30-14 AWG copper wire
Torque: 4.5 inch-lbs (0.51 N-m) max.
18. CONSTRUCTION: This unit is rated for NEMA 4X/IP65 outdoor use.
IP20 Touch safe. Installation Category II, Pollution Degree 2. One piece
bezel/case. Flame resistant. Synthetic rubber keypad. Panel gasket and
mounting clip included.
19. WEIGHT: 10.4 oz. (295 g)
VIN > 3.6 VDC VIN < 0.9 VDC
Inactive
VIN < 0.9 VDC VIN > 3.6 VDC
Active
SINKING INPUTS
22 KΩΩpull-up to +5 V
SOURCING INPUTS
22 KΩΩpull-down
INPUT STATE
Power mains class A
Enclosure class AEN 55011RF interference
Emissi ns t EN 50081-2
150 KHz - 80 MHz
Level 3; 10 /rms EN 61000-4-6RF conducted interference
Level 3; 2 Kv power
Level 4; 2 Kv I/OEN 61000-4-4Fast transients (burst)
80 MHz - 1 GHz
Level 3; 10 /m 1
EN 61000-4-3Electromagnetic RF fields
Level 3; 8 Kv air
Level 2; 4 Kv contactEN 61000-4-2Electrostatic discharge
200 Hz, 50% duty cycle
900 MHz ±5 MHz
Immunity t EN 50082-2
Level 3; 10 /mEN 50204Simulation of cordless telephones
PAX-D.QXD 10/11/04 11:38 AM Page 3

4
MODEL PAXD - UNIVERSAL DC INPUT
MODEL PAXP - PROCESS INPUT
* After 20 minute warm-up. Accuracy is specified in two ways:
Accuracy over an 18 to 28°C and 10 to 75% RH environment; and
accuracy over a 0 to 50°C and 0 to 85%RH (non-condensing
environment). Accuracy over the 0 to 50°C range includes the
temperature coefficient effect of the meter.
EXCITATION POWER:
Transmitter Power: 24 DC, ±5%, regulated, 50 mA max.
Reference oltage: 2 DC, ±2%
Compliance: 1 kohm load min. (2 mA max.)
Temperature coefficient: 40 ppm/°C max.
Reference Current: 1.75 mADC, ±2%
Compliance: 10 kohm load max.
Temperature coefficient: 40 ppm/°C max.
GFOUR VOLTAGE RANGES (300 VDC Max)
GFIVE CURRENT RANGES (2A DC Max)
GTHREE RESISTANCE RANGES (10K Ohm Max)
GSELECTABLE 24 V, 2 V, 1.75 mA EXCITATION
GDUAL RANGE INPUT (20 mA or 10 VDC)
G24 VDC TRANSMITTER POWER
PAXD SPECIFICATIONS
INPUT RANGES:
PAXP SPECIFICATIONS
SENSOR INPUTS:
INPUT
RANGE
ACCURACY*
(18 to 28°C
ACCURACY*
(0 to 50°C
IMPEDANCE/
COMPLIANCE
MAX
CONTINUOUS
OVERLOAD
RESOLUTION
±200 mVDC 0.03% of reading
+30 µV
0.12% of reading
+40 µV1.066 Mohm 100 V 10 µV
±2 VDC 0.03% of reading
+0.3 mV
0.12% of reading
+0.4 mV 1.066 Mohm 300 V 0.1 mV
±20 VDC 0.03% of reading
+3 mV
0.12% of reading
+4 mV 1.066 Mohm 300 V 1 mV
±300 VDC 0.05% of reading
+30 mV
0.15% of reading
+40 mV 1.066 Mohm 300 V 10 mV
±200 µADC 0.03% of reading
+0.03 µA
0.12% of reading
+0.04µA1.11 Kohm 15 mA 10 nA
±2 mADC 0.03% of reading
+0.3 µA
0.12% of reading
+0.4 µA111 ohm 50 mA 0.1 µA
±20 mADC 0.03% of reading
+3µA
0.12% of reading
+4 µA11.1 ohm 150 mA 1 µA
±200 mADC 0.05% of reading
+30 µA
0.15% of reading
+40 µA1.1 ohm 500 mA 10 µA
±2 ADC 0.5% of reading
+0.3 mA
0.7% of reading
+0.4 mA 0.1 ohm 3 A 0.1 mA
100 ohm 0.05% of reading
+30 Mohm
0.2% of reading
+40 Mohm 0.175 V 30 V 0.01 ohm
1000 ohm 0.05% of reading
+0.3 ohm
0.2% of reading
+0.4 ohm 1.75 V 30 V 0.1 ohm
10 Kohm 0.05% of reading
+1 ohm
0.2% of reading
+1.5 ohm 17.5 V 30 V 1 ohm
* After 20 minute warm-up. Accuracy is specified in two ways: Accuracy over an
18 to 28°C and 10 to 75% RH environment; and accuracy over a 0 to 50°C and 0
to 85%RH (non-condensing environment). Accuracy over the 0 to 50°C range
includes the temperature coefficient effect of the meter.
EXCITATION POWER:
Transmitter Power: 24 DC, ±5%, regulated, 50 mA max.
INPUT
(RANGE
ACCURACY*
(18 to 28°C
ACCURACY*
(0 to 50°C
IMPEDANCE/
COMPLIANCE
MAX
CONTINUOUS
OVERLOAD
DISPLAY
RESOLUTION
20 mA
(-2 to 26 mA)
0.03% of
reading +2 µA
0.12% of
reading +3 µA20 ohm 150 mA 1 µA
10 VDC
(-1 to 13 VDC)
0.03% of
reading +2 mV
0.12% of
reading +3 mV 500 Kohm 300 V 1 mV
PAX-D.QXD 10/11/04 11:38 AM Page 4

5
MODEL PAXH - AC TRUE RMS VOLT AND CURRENT
GFOUR VOLTAGE RANGES (300 VAC Max)
GFIVE CURRENT RANGES (5 A Max)
GACCEPTS AC OR DC COUPLED INPUTS
GTHREE WAY ISOLATION: POWER, INPUT AND OUTPUTS
MODEL PAXS - STRAIN GAGE INPUT
GLOAD CELL, PRESSURE AND TORQUE BRIDGE INPUTS
GDUAL RANGE INPUT:
±
24 mV OR
±
240 mV
GSELECTABLE 5 VDC OR 10 VDC BRIDGE EXCITATION
GPROGRAMMABLE AUTO-ZERO TRACKING
PAXS SPECIFICATIONS
SENSOR INPUTS:
PAXH SPECIFICATIONS
INPUT RANGES:
Isolation To Option Card Commons and User Input Commons: 125 rms
Isolation To AC Power Terminals: 250 rms
*Conditions for accuracy specification:
- 20 minutes warmup
- 18-28°C temperature range, 10-75% RH non-condensing
- 50 Hz - 400 Hz sine wave input
- 1% to 100% of range
- Add 0.1% reading + 20 counts error over 0-50°C range
- Add 0.2% reading + 10 counts error for crest factors up to 3, add 1% reading up to 5
- Add 0.5% reading + 10 counts of DC component
- Add 1% reading + 20 counts error over 20 Hz to 10 KHz range
** Non-repetitive surge rating: 15 A for 5 seconds
*** Inputs are direct coupled to the input divider and shunts. Input signals with
high DC component levels may reduce the usable range.
MAX CREST FACTOR (Vp/VRMS): 5 @ Full Scale Input
INPUT COUPLING: AC or AC and DC
INPUT CAPACITANCE: 10 pF
COMMON MODE VOLTAGE: 125 AC working
COMMON MODE REJECTION: (DC to 60 Hz) 100 dB
INPUT
RANGE ACCURACY* MAX DC
BLOCKING
IMPEDANCE
(60 Hz
MAX
CONTINUOUS
OVERLOAD
RESOLUTION
2 mA 0.1% of reading
+2 µA ±50 mA
111 ohm 50 mA 0.1 µA
20 mA 0.1% of reading
+20 µA±150 mA
11.1 ohm 150 mA 1 µA
200 mA 0.1% of reading
+0.2 mA ±500 mA
1.1 ohm 500 mA 10 µA
5 A 0.5% of reading
+5 mA ±7 A***
0.02 ohm 7 A** 1 mA
200 mV 0.1% of reading
+0.4 mV ±10 V
686 Kohm 30 V 0.01 mV
2 V 0.1% of reading
+2 mV ±50 V
686 Kohm 30 V 0.1 mV
20 V 0.1% of reading
+20 mV ±300 V
686 Kohm 300 V 1 mV
300 V 0.2% of reading
+0.3 V ±300 V***
686 Kohm 300 V 0.1 V
200 µA0.1% of reading
+0.4 µA±15 mA
1.11 Kohm 15 mA 0.01 µA
CONNECTION TYPE: 4-wire bridge (differential)
2-wire (single-ended)
COMMON MODE RANGE (w.r.t. input common): 0 to +5 DC
Rejection: 80 dB (DC to 120 Hz)
BRIDGE EXCITATION :
Jumper Selectable: 5 DC @ 65 mA max., ±2%
10 DC @ 125 mA max., ±2%
Temperature coefficient (ratio metric): 20 ppm/°C max.
INPUT RANGE ACCURACY*
(18 to 28°C
ACCURACY*
(0 to 50°C IMPEDANCE
MAX
CONTINUOUS
OVERLOAD
RESOLUTION
±24 mVDC 0.02% of
reading +3 µV
0.07% of
reading +4 µV100 Mohm 30 V 1 µV
±240 mVDC 0.02% of
reading +30 µV
0.07% of
reading +40 µV100 Mohm 30 V 10 µV
* After 20 minute warm-up. Accuracy is specified in two ways: Accuracy over an 18
to 28°C and 10 to 75% RH environment; and accuracy over a 0 to 50°C and 0 to
85% RH (non-condensing environment). Accuracy over the 0 to 50°C range
includes the temperature coefficient effect of the meter.
PAX-D.QXD 10/11/04 11:38 AM Page 5

6
MODEL PAXT - THERMOCOUPLE AND RTD INPUT
GTHERMOCOUPLE AND RTD INPUTS
GCONFORMS TO ITS- 0 STANDARDS
GCUSTOM SCALING FOR NON-STANDARD PROBES
GTIME-TEMPERATURE INTEGRATOR
PAXT SPECIFICATIONS
READOUT:
Resolution: ariable: 0.1, 0.2, 0.5, or 1, 2, or 5 degrees
Scale: F or C
Offset Range: -19,999 to 99,999 display units
THERMOCOUPLE INPUTS:
Input Impedance: 20 MΩ
Lead Resistance Effect: 0.03µ/ohm
Max. Continuous Overvoltage: 30
RTD INPUTS:
Type: 3 or 4 wire, 2 wire can be compensated for lead wire resistance
Excitation current: 100 ohm range: 165 µA
10 ohm range: 2.6 mA
Lead resistance: 100 ohm range: 10 ohm/lead max.
10 ohm range: 3 ohms/lead max.
Max. continuous overload: 30
CUSTOM RANGE: Up to 16 data point pairs
Input range: -10 to 65 m
0 to 400 ohms, high range
0 to 25 ohms, low range
Display range: -19999 to 99999
STANDARD
***
ACCURACY*
(0 to 50°C
ACCURACY*
(18 to 28°C
RANGE
no official
standard
0.9°C0.4°C-100 to 260°C
10 ohm Copper
alpha = .00427
INPUT TYPE
no official
standard
0.5°C0.2°C-80 to 260°C
120 ohm Nickel
alpha = .00672
no official
standard
1.6°C0.4°C-200 to 850°C
100 ohm Pt
alpha = .003919
IEC 7511.6°C0.4°C-200 to 850°C
100 ohm Pt
alpha = .00385
0.20% of reading
+ 0.007 Ω
0.04% of reading
+ 0.005 Ω
0 to 25 Ω
(1 MΩres.)
Custom
10 ohm range
0.12% of reading
+ 0.05 Ω
0.02% of reading
+ 0.04 Ω
0 to 400 Ω
(10 MΩres.)
Custom
100 ohm range
ACCURACY*
(0 to 50°°C
0.12% of reading
+ 5µV
0.02% of reading
+ 4µV
-10 to 65mV
(1 µV res.)
Custom
mV range
ACCURACY*
(18 to 28°°C
RANGEINPUT TYPE
WIRE COLOR
INPUT
TYPE RANGE ACCURACY*
(0 to 50°C STANDARD
ANSI BS 1843
T-200 to 400°C
-270 to -200°C
1.2°C
**
2.1°C ITS-90 (+) blue
(-) red
(+) white
(-) blue
E-200 to 871°C
-270 to -200°C
1.0°C
**
2.4°C ITS-90 (+) purple
(-) red
(+) brown
(-) blue
J-200 to 760°C 1.1°C 2.3°C ITS-90 (+) white
(-) red
(+) yellow
(-) blue
K-200 to 1372°C
-270 to -200°C
1.3°C
**
3.4°C ITS-90 (+) yellow
(-) red
(+) brown
(-) blue
R-50 to 1768°C 1.9°C 4.0°C ITS-90 no
standard
(+) white
(-) blue
S-50 to 1768°C 1.9°C 4.0°C ITS-90 no
standard
(+) white
(-) blue
B100 to 300°C
300 to 1820°C
3.9°C
2.8°C
5.7°C
4.4°C ITS-90 no
standard
no
standard
N1.3°C
**
3.1°C ITS-90 (+) orange
(-) red
(+) orange
(-) blue
C
(W5/W26) 0 to 2315°C 1.9°C 6.1°C ASTM
E988-90***
no
standard
no
standard
*After 20 min. warm-up. Accuracy is specified in two ways: Accuracy over an
18 to 28°C and 15 to 75% RH environment; and Accuracy over a 0 to 50°C and 0
to 85% RH (non condensing) environment. Accuracy specified over the 0 to 50°C
operating range includes meter tempco and ice point tracking effects. The
specification includes the A/D conversion errors, linearization conformity, and
thermocouple ice point compensation. Total system accuracy is the sum of meter
and probe errors. Accuracy may be improved by field calibrating the meter readout
at the temperature of interest.
** The accuracy over the interval -270 to -200°C is a function of temperature,
ranging from 1°C at -200°C and degrading to 7°C at -270°C. Accuracy may be
improved by field calibrating the meter readout at the temperature of interest.
*** These curves have been corrected to ITS-90.
ACCURACY*
(18 to 28°C
-200 to 1300°C
-270 to -200°C
ACCESSORIES
UNITS LABEL KIT (PAXLBK - Not required for PAXT
Each meter has a units indicator with backlighting that can be customized
using the Units Label Kit. The backlight is controlled in the programming.
Each PAXT meter is shipped with °F and °C overlay labels which can be
installed into the meter’s bezel display assembly.
EXTERNAL CURRENT SHUNTS (APSCM
To measure DC current signals greater than 2 ADC, a shunt must be used. The
APSCM010 current shunt converts a maximum 10 ADC signal into 10.0 m .
The APSCM100 current shunt converts a maximum 100 ADC signal into 100.0
m . The continuous current through the shunt is limited to 115% of the rating.
PAX-D.QXD 10/11/04 11:38 AM Page 6

7
WARNING: Disconnect all power to the unit before
installing Plug-in cards.
Adding Option Cards
The PAX and MPAX series meters can be fitted with up to three optional plug-
in cards. The details for each plug-in card can be reviewed in the specification
section below. Only one card from each function type can be installed at one time.
The function types include Setpoint Alarms (PAXCDS), Communications
(PAXCDC), and Analog Output (PAXCDL). The plug-in cards can be installed
initially or at a later date.
PAXH Isolation Specifications For All Option Cards
Is lati n T Sens r C mm ns: 1400 rms for 1 min.
Working oltage: 125
Is lati n t User Input C mm ns: 500 rms for 1 min.
Working oltage 50
COMMUNICATION CARDS (PAXCDC
A variety of communication protocols are available for the PAX and MPAX
series. Only one of these cards can be installed at a time. When programming
the unit via RLCPro, a Windows®based program, the RS232 or RS485 Cards
must be used.
SERIAL COMMUNICATIONS CARD
Type: RS485 or RS232
Is lati n T Sens r & User Input C mm ns: 500 rms for 1 min.
Working oltage: 50 . Not Isolated from all other commons.
Data: 7/8 bits
Baud: 300 to 19,200
Parity: no, odd or even
Bus Address: Selectable 0 to 99, Max. 32 meters per line (RS485)
Transmit Delay: Selectable for 2 to 50 msec or 50 to 100 msec (RS485)
DEVICENET™ CARD
C mpatibility: Group 2 Server Only, not UCMM capable
Baud Rates: 125 Kbaud, 250 Kbaud, and 500 Kbaud
Bus Interface: Phillips 82C250 or equivalent with MIS wiring protection per
DeviceNet™ olume I Section 10.2.2.
N de Is lati n: Bus powered, isolated node
H st Is lati n: 500 rms for 1 minute (50 working) between DeviceNet™
and meter input common.
MODBUS CARD
Type: RS485; RTU and ASCII MODBUS modes
Is lati n T Sens r & User Input C mm ns: 500 rms for 1 minute.
Working oltage: 50 . Not isolated from all other commons.
Baud Rates: 300 to 38400.
Data: 7/8 bits
Parity: No, Odd, or Even
Addresses: 1 to 247.
Transmit Delay: Programmable; See Transmit Delay explanation.
PROFIBUS-DP CARD
Fieldbus Type: Profibus-DP as per EN 50170, implemented with Siemens
SPC3 ASIC
C nf rmance: PNO Certified Profibus-DP Slave Device
Baud Rates: Automatic baud rate detection in the range 9.6 Kbaud to 12 Mbaud
Stati n Address: 0 to 126, set by the master over the network. Address
stored in non-volatile memory.
C nnecti n: 9-pin Female D-Sub connector
Netw rk Is lati n: 500 rms for 1 minute (50 working) between Profibus
network and sensor and user input commons. Not isolated from all other
commons.
PROGRAMMING SOFTWARE
The SFPAX is a Windows®based program that allows configuration of the
PAX meter from a PC. Using the SFPAX makes it easier to program the PAX
meter and allows saving the PAX program in a PC file for future use. On-line
help is available within the software. A PAX serial plug-in card is required to
program the meter using the software.
SETPOINT CARDS (PAXCDS
The PAX and MPAX series has 4 available setpoint alarm output plug-in
cards. Only one of these cards can be installed at a time. (Logic state of the
outputs can be reversed in the programming.) These plug-in cards include:
PAXCDS10 - Dual Relay, FORM-C, Normally open & closed
PAXCDS20 - Quad Relay, FORM-A, Normally open only
PAXCDS30 - Isolated quad sinking NPN open collector
PAXCDS40 - Isolated quad sourcing PNP open collector
DUAL RELAY CARD
Type: Two FORM-C relays
Is lati n T Sens r & User Input C mm ns: 2000 rms for 1 min.
Working oltage: 240 rms
C ntact Rating:
One Relay Energized: 5 amps @ 120/240 AC or 28 DC (resistive load),
1/8 HP @120 AC, inductive load
Total current with both relays energized not to exceed 5 amps
Life Expectancy: 100 K cycles min. at full load rating. External RC snubber
extends relay life for operation with inductive loads
QUAD RELAY CARD
Type: Four FORM-A relays
Is lati n T Sens r & User Input C mm ns: 2300 rms for 1 min.
Working oltage: 250 rms
C ntact Rating:
One Relay Energized: 3 amps @ 240 AC or 30 DC (resistive load), 1/10
HP @120 AC, inductive load
Total current with all four relays energized not to exceed 4 amps
Life Expectancy: 100K cycles min. at full load rating. External RC snubber
extends relay life for operation with inductive loads
QUAD SINKING OPEN COLLECTOR CARD
Type: Four isolated sinking NPN transistors.
Is lati n T Sens r & User Input C mm ns: 500 rms for 1 min.
Working oltage: 50 . Not Isolated from all other commons.
Rating: 100 mA max @ SAT = 0.7 max. MAX = 30
QUAD SOURCING OPEN COLLECTOR CARD
Type: Four isolated sourcing PNP transistors.
Is lati n T Sens r & User Input C mm ns: 500 rms for 1 min.
Working oltage: 50 . Not Isolated from all other commons.
Rating: Internal supply: 24 DC ± 10% , 30 mA max. total
External supply: 30 DC max., 100 mA max. each output
ALL FOUR SETPOINT CARDS
Resp nse Time: 200 msec. max. to within 99% of final readout value (digital
filter and internal zero correction disabled)
700 msec. max. (digital filter disabled, internal zero correction enabled)
LINEAR DC OUTPUT (PAXCDL
Either a 0(4)-20 mA or 0-10 retransmitted linear DC output is available
from the analog output plug-in card. The programmable output low and high
scaling can be based on various display values. Reverse slope output is possible
by reversing the scaling point positions.
PAXCDL10 - Retransmitted Analog Output Card
ANALOG OUTPUT CARD
Types: 0 to 20 mA, 4 to 20 mA or 0 to 10 DC
Is lati n T Sens r & User Input C mm ns: 500 rms for 1 min.
Working oltage: 50 . Not Isolated from all other commons.
Accuracy: 0.17% of FS (18 to 28°C); 0.4% of FS (0 to 50°C)
Res luti n: 1/3500
C mpliance: 10 DC: 10 KΩload min., 20 mA: 500 Ωload max.
Update time: 200 msec. max. to within 99% of final output value (digital
filter and internal zero correction disabled)
700 msec. max. (digital filter disabled, internal zero correction enabled)
OPTIONAL PLUG-IN OUTPUT CARDS
PAXCDC30 - DeviceNet
PAXCDC50 - Profibus-DPPAXCDC20 - RS232 Serial
PAXCDC40 - ModbusPAXCDC10 - RS485 Serial
PAX-D.QXD 10/11/04 11:38 AM Page 7

8
Installation
The PAX meets NEMA 4X/IP65 requirements when properly installed. The
unit is intended to be mounted into an enclosed panel. Prepare the panel cutout
to the dimensions shown. Remove the panel latch from the unit. Slide the panel
gasket over the rear of the unit to the
back of the bezel. The unit should
be installed fully assembled.
Insert the unit into the panel
cutout.
While holding the unit in place, push the panel latch over the rear of the unit
so that the tabs of the panel latch engage in the slots on the case. The panel
latch should be engaged in the farthest forward slot possible. To achieve a
proper seal, tighten the latch screws evenly until the unit is snug in the panel
(Torque to approximately 7 in-lbs [79N-cm]). Do not over-tighten the screws.
Installation Environment
The unit should be installed in a location that does not exceed the maximum
operating temperature and provides good air circulation. Placing the unit near
devices that generate excessive heat should be avoided.
The bezel should be cleaned only with a soft cloth and neutral soap product.
Do NOT use solvents. Continuous exposure to direct sunlight may accelerate
the aging process of the bezel.
Do not use tools of any kind (screwdrivers, pens, pencils, etc.) to operate the
keypad of the unit.
PANEL CUT-OUT
1.0 INSTALLING THE METER
2.0 SETTING THE JUMPERS
The meter can have up to four jumpers that must be checked and / or changed
prior to applying power. The following Jumper Selection Figures show an
enlargement of the jumper area.
To access the jumpers, remove the meter base from the case by firmly
squeezing and pulling back on the side rear finger tabs. This should lower the
latch below the case slot (which is located just in front of the finger tabs). It is
recommended to release the latch on one side, then start the other side latch.
Input Range Jumper
This jumper is used to select the proper input range. The input range selected
in programming must match the jumper setting. Select a range that is high enough
to accommodate the maximum input to avoid overloads. The selection is different
for each meter. See the Jumper Selection Figure for appropriate meter.
Excitation Output Jumper
If your meter has excitation, this jumper is used to select the excitation range
for the application. If excitation is not being used, it is not necessary to check or
move this jumper.
User Input Logic Jumper
This jumper selects the logic state of all the user inputs. If the user inputs are
not used, it is not necessary to check or move this jumper.
PAXH:
Signal Jumper
This jumper is used to select the signal type. For current signals, the jumper
is installed. For voltage signals, remove the jumper from the board. (For 2
inputs, this removed jumper can be used in the “2 only” location.)
Couple Jumper
This jumper is used for AC / DC couple. If AC couple, then the jumper is
removed from the board. If DC couple is used, then the jumper is installed.
PAXD Jumper Selection
Main
Circuit
Board
JUMPER
LOCATION
JUMPER
LOCATION
CURRENT EXCITATION
USER INPUT
VOLT/
O M
JUMPER SELECTIONS
The indicates factory setting.
Input Range Jumper
One jumper is used for voltage/ohms or current input ranges. Select the proper input range high
enough to avoid input signal overload. Only one jumper is allowed in this area. Do not have a jumper
in both the voltage and current ranges at the same time. Avoid placing the jumper across two ranges.
PAX-D.QXD 10/11/04 11:38 AM Page 8

PAXP Jumper Selection
PAXS Jumper Selection
JUMPER SELECTIONS
The indicates factory setting.
Main
Circuit
Board
USER INPUT
JUMPER
LOCATION
Main
Circuit
Board
JUMPER
LOCATION
JUMPER
LOCATION
USER INPUT
INPUT RANGE
BRIDGE
JUMPER SELECTIONS
The indicates factory setting.
Bridge Excitation
One jumper is used to select bridge excitation to allow use of the higher sensitivity 24 m input
range. Use the 5 excitation with high output (3 m / ) bridges. The 5 excitation also reduces
bridge power compared to 10 excitation.
A maximum of four 350 ohm load cells can be driven by the internal bridge excitation voltage.
PAXH Jumper Selection
JUMPER SELECTIONS
The indicates factory setting.
Signal Jumper
One jumper is used for the input signal type. For current signals, the jumper
is installed. For voltage signals, remove the jumper from the board. (For 2
inputs, this removed jumper can be used in the “2 only” location.)
Couple Jumper
One jumper is used for AC / DC couple. If AC couple is used, then the jumper
is removed from the board. If DC couple is used, then the jumper is installed.
Input Range Jumper
For most inputs, one jumper is used to select the input range. However, for
the following ranges, set the jumpers as stated:
5 A: Remove all jumpers from the input range.
2 V: Install one jumper in “.2/2 ” position and one jumper in “2 only”.
All Other Ranges: One jumper in the selected range only.
Do not have a jumper in both the voltage and current ranges at the same time.
Avoid placing a jumper across two ranges.
CAUTION: To maintain the electrical safety of the meter, remove
unneeded jumpers completely from the meter. Do not move the
jumpers to positions other than those specified.
Main
Circuit
Board
Jumper
Locations CURR/VOLT
SIGNAL
2 V ONLY
USER INPUT
AC/DC COUPLE
VOLTAGE
CURRENT
RANGES
PAX-D.QXD 10/11/04 11:38 AM Page 9

10
WIRING OVERVIEW
Electrical connections are made via screw-clamp terminals located on the
back of the meter. All conductors should conform to the meter’s voltage and
current ratings. All cabling should conform to appropriate standards of good
installation, local codes and regulations. It is recommended that power supplied
to the meter (DC or AC) be protected by a fuse or circuit breaker.
When wiring the meter, compare the numbers embossed on the back of the
meter case against those shown in wiring drawings for proper wire position.
Strip the wire, leaving approximately 0.3" (7.5 mm) bare lead exposed (stranded
wires should be tinned with solder). Insert the lead under the correct screw-
clamp terminal and tighten until the wire is secure. (Pull wire to verify
tightness.) Each terminal can accept up to one #14 AWG (2.55 mm) wire, two
#18 AWG (1.02 mm), or four #20 AWG (0.61 mm).
EMC INSTALLATION GUIDELINES
Although this meter is designed with a high degree of immunity to Electro-
Magnetic Interference (EMI), proper installation and wiring methods must be
followed to ensure compatibility in each application. The type of the electrical
noise, its source or the method of coupling into the unit may be different for
various installations.Listed below are some EMC guidelines for successful
installation in an industrial environment.
1. The meter should be mounted in a metal enclosure, which is properly
connected to protective earth.
2. With use of the lower input ranges or signal sources with high source
impedance, the use of shielded cable may be necessary. This helps to guard
against stray AC pick-up. Attach the shield to the input common of the meter.
Line voltage monitoring and 5A CT applications do not usually require
shielding.
3. To minimize potential noise problems, power the meter from the same power
branch, or at least the same phase voltage as that of the signal source.
4. Never run Signal or Control cables in the same conduit or raceway with AC
power lines, conductors feeding motors, solenoids, SCR controls, and
heaters, etc. The cables should be run in metal conduit that is properly
grounded. This is especially useful in applications where cable runs are long
and portable two-way radios are used in close proximity or if the installation
is near a commercial radio transmitter.
5. Signal or Control cables within an enclosure should be routed as far away as
possible from contactors, control relays, transformers, and other noisy
components.
6. In extremely high EMI environments, the use of external EMI suppression
devices, such as ferrite suppression cores, is effective. Install them on Signal
and Control cables as close to the unit as possible. Loop the cable through the
core several times or use multiple cores on each cable for additional
protection. Install line filters on the power input cable to the unit to suppress
power line interference. Install them near the power entry point of the
enclosure. The following EMI suppression devices (or equivalent) are
recommended:
Ferrite Suppression Cores for signal and control cables:
Fair-Rite # 0443167251 (RLC #FCOR0000)
TDK # ZCAT3035-1330A
Steward #28B2029-0A0
Line Filters for input power cables:
Schaffner # FN610-1/07 (RLC #LFIL0000)
Schaffner # FN670-1.8/07
Corcom #1 R3
Note: Reference manufacturer’s instructions when installing a line filter.
7. Long cable runs are more susceptible to EMI pickup than short cable runs.
Therefore, keep cable runs as short as possible.
8. Switching of inductive loads produces high EMI. Use of snubbers across
inductive loads suppresses EMI.
Snubber: RLC#SNUB0000.
3.0 WIRING THE METER
3.1 POWER WIRING
AC Power
Terminal 1: AC
Terminal 2: AC
DC Power
Terminal 1: + DC
Terminal 2: - DC
PAXT Jumper Selection
Main
Circuit
Board
JUMPER
LOCATION
JUMPER
LOCATION
USER INPUT
RTD
INPUT
JUMPER SELECTIONS
The indicates factory setting.
RTD Input Jumper
One jumper is used for RTD input ranges. Select the proper range to match
the RTD probe being used. It is not necessary to remove this jumper when
not using RTD probes.
PAX-D.QXD 10/11/04 11:38 AM Page 10

11
Current Signal
(self powered
Terminal 4: +ADC
Terminal 5: -ADC
Voltage Signal
(self powered
Terminal 3: + DC
Terminal 5: - DC
Current Signal (2 wire
requiring excitation
Terminal 4: -ADC
Terminal 6: +ADC
Excitation Jumper: 24
Before connecting signal wires, the Input Range Jumper and Excitation Jumper should be verified for proper position.
3.2 INPUT SIGNAL WIRING
Current Signal (3 wire
requiring excitation
Terminal 4: +ADC (signal)
Terminal 5: -ADC (common)
Terminal 6: + olt supply
Excitation Jumper: 24
Voltage Signal (3 wire
requiring excitation
Terminal 3: + DC (signal)
Terminal 5: - DC (common)
Terminal 6: + olt supply
Excitation Jumper: 24
Resistance Signal
(3 wire requiring
excitation
Terminal 3: Resistance
Terminal 5: Resistance
Terminal 6: Jumper to
terminal 3
Excitation Jumper:
1.75 mA REF.
Potentiometer Signal
(3 wire requiring excitation
Terminal 3: Wiper
Terminal 5: Low end of pot.
Terminal 6: High end of pot.
Excitation Jumper: 2 REF.
Input Range Jumper: 2 olt
Module 1 Input Range: 2 olt
Note: The Appl signal scaling st le
should be used because the signal will
be in volts.
Current Signal
(self powered
Terminal 4: +ADC
Terminal 5: -ADC
Voltage Signal
(self powered
Terminal 3: + DC
Terminal 5: - DC
Current Signal (2 wire
requiring excitation
Terminal 4: -ADC
Terminal 6: +ADC
PAXP INPUT SIGNAL WIRING
PAXD INPUT SIGNAL WIRING
Current Signal (3 wire
requiring excitation
Terminal 4: +ADC (signal)
Terminal 5: -ADC (common)
Terminal 6: + olt supply
Voltage Signal (3 wire
requiring excitation
Terminal 3: + DC (signal)
Terminal 5: - DC (common)
Terminal 6: + olt supply
CAUTION: Sensor input common is NOT isolated from user input common. In order to preserve the safet of the meter application, the sensor input
common must be suitabl isolated from hazardous live earth referenced voltages; or input common must be at protective earth ground potential. If not,
hazardous live voltage ma be present at the User Inputs and User Input Common terminals. Appropriate considerations must then be given to the
potential of the user input common with respect to earth common; and the common of the isolated plug-in cards with respect to input common.
CAUTION: Sensor input common is NOT isolated from user input common. In order to preserve the safet of the meter application, the sensor input
common must be suitabl isolated from hazardous live earth referenced voltages; or input common must be at protective earth ground potential. If not,
hazardous live voltage ma be present at the User Inputs and User Input Common terminals. Appropriate considerations must then be given to the
potential of the user input common with respect to earth common; and the common of the isolated plug-in cards with respect to input common.
PAX-D.QXD 10/11/04 11:38 AM Page 11

12
4-Wire Bridge Input
2-Wire Single
Ended Input
6-Wire Bridge Input
DEADLOAD COMPENSATION
In some cases, the combined deadload and liveload output may exceed the
range of the 24 m input. To use this range, the output of the bridge can be
offset a small amount by applying a fixed resistor across one arm of the bridge.
This shifts the electrical output of the bridge downward to within the operating
range of the meter. A 100 K ohm fixed resistor shifts the bridge output
approximately -10 m (350 ohm bridge, 10 excitation).
Connect the resistor between +SIG and -SIG. Use a metal film resistor with
a low temperature coefficient of resistance.
BRIDGE COMPLETION RESISTORS
For single strain gage applications, bridge completion resistors must be
employed externally to the meter. Only use metal film resistors with a low
temperature coefficient of resistance.
Load cells and pressure transducers are normally implemented as full
resistance bridges and do not require bridge completion resistors.
Before connecting signal wires, the Input Range Jumper should be verified for proper position.
PAXT INPUT SIGNAL WIRING
3-Wire RTD
Thermocouple 2-Wire RTD CAUTION: Sensor input common is NOT isolated
from user input common. In order to preserve the
safet of the meter application, the sensor input
common must be suitabl isolated from hazardous
live earth referenced voltages; or input common
must be at protective earth ground potential. If not,
hazardous live voltage ma be present at the User
Inputs and User Input Common terminals.
Appropriate considerations must then be given to the
potential of the user input common with respect to
earth common; and the common of the isolated plug-
in cards with respect to input common.
CAUTION:
1. Where possible, connect the neutral side of the signal (including current shunts) to the input common of the meter. If the input signal is sourced from
an active circuit, connect the lower impedance (usuall circuit common) to the input signal common of the meter.
2. For phase-to-phase line monitoring where a neutral does not exist, or for an other signal input in which the isolation voltage rating is exceeded, an isolating potential
transformer must be used to isolate the input voltage from earth. With the transformer, the input common of the meter can then be earth referenced for safet .
3. When measuring line currents, the use of a current transformer is recommended. If using external current shunts, insert the shunt in the neutral return line. If the
isolation voltage rating is exceeded, the use of an isolating current transformer is necessar .
Current Signal (AmpsVoltage Signal Current Signal (Milliamps
Before connecting signal wires, the Signal, Input Range and Couple Jumpers
should be verified for proper position.
CAUTION: Connect onl one input signal range to the
meter. Hazardous signal levels ma be present on
unused inputs.
CAUTION: The isolation rating of the input common of the
meter with respect to the option card commons and the
user input common Terminal 8 (If used) is 125 Vrms; and
250 Vrms with respect to AC Power (meter Terminals 1 &
2). To be certain that the ratings are not exceeded, these
voltages should be verified b a high-voltage meter before
wiring the meter.
PAXS INPUT SIGNAL WIRING
PAXH INPUT SIGNAL WIRING
PAX-D.QXD 10/11/04 11:38 AM Page 12

13
Sinking Logic
Terminal 8-10:
Terminal 7: }
In this logic, the user inputs of the
meter are internally pulled up to +5
with 22 K resistance. The input is active
when it is pulled low (<0 .9 ).
3.3 USER INPUT WIRING
Before connecting the wires, the User Input Logic Jumper should be verified for proper position. If not using User
Inputs, then skip this section. Only the appropriate User Input terminal has to be wired.
Sourcing Logic
Terminal 8-10: + DC thru external switching device
Terminal 7: - DC thru external switching device
In this logic, the user inputs of the meter are
internally pulled down to 0 with 22 K
resistance. The input is active when a voltage
greater than 3.6 DC is applied.
Connect external switching device between
appropriate User Input terminal and User Comm.
Sourcing Logic
Terminals 9-11:
+ DC through external switching device
Terminal 8:
- DC through external switching device
In this logic, the user inputs of the meter are
internally pulled down with 22 K resistance.
The input is active when a voltage greater
than 3.6 DC is applied.
Sinking Logic
Terminals 9-11
Terminal 8
In this logic, the user inputs of the
meter are internally pulled up to +5
with 22 K resistance. The input is
active when it is pulled low (<0 .9 ).
Connect external
switching device between
appropriate User Input
terminal and User Comm.
}
PAXH ONLY
*Display Readout Legends may be locked out in Factory Settings.
** Factory setting for the F1, F2, and RST keys is NO mode.
RST
F2MM
F1LL
PAR
DSP
KEY
old with F1L, F2Mto scroll value by x1000
Reset (Function key)**
Decrement selected parameter value
Function key 2; hold for 3 seconds for Second Function 2**
Increment selected parameter value
Function key 1; hold for 3 seconds for Second Function 1**
Store selected parameter and index to next parameterAccess parameter list
Quit programming and return to display modeIndex display through max/min/total/input readouts
PROGRAMMING MODE OPERATIONDISPLAY MODE OPERATION
4.0 REVIEWING THE FRONT BUTTONS AND DISPLAY
3.4 SETPOINT (ALARMS WIRING
3.5 SERIAL COMMUNICATION WIRING
3.6 ANALOG OUTPUT WIRING
See appropriate plug-in card bulletin for details.
PAX-D.QXD 10/11/04 11:38 AM Page 13

14
OVERVIEW
PROGRAMMING MENU
.0 PROGRAMMING THE METER
DISPLAY MODE
The meter normally operates in the Display Mode. In this mode, the meter
displays can be viewed consecutively by pressing the DSP key. The
annunciators to the left of the display indicate which display is currently shown;
Max alue (MAX), Min alue (MIN), or Totalizer alue (TOT). Each of these
displays can be locked from view through programming. (See Module 3) The
Input Display alue is shown with no annunciator.
PROGRAMMING MODE
Two programming modes are available.
Full Pr gramming M de permits all parameters to be viewed and modified.
Upon entering this mode, the front panel keys change to Programming Mode
operations. This mode should not be entered while a process is running, since
the meter functions and User Input response may not operate properly while
in Full Programming Mode.
Quick Pr gramming M de permits only certain parameters to be viewed
and/or modified. When entering this mode, the front panel keys change to
Programming Mode operations, and all meter functions continue to operate
properly. Quick Programming Mode is configured in Module 3. The Display
Intensity Level “” parameter is available in the Quick Programming
Mode only when the security code is non-zero. For a description, see Module
9—Factory Service Operations. Throughout this document, Programming
Mode (without Quick in front) always refers to “Full” Programming Mode.
PROGRAMMING TIPS
The Programming Menu is organized into nine modules (See above). These
modules group together parameters that are related in function. It is
recommended to begin programming with Module 1 and proceed through each
module in sequence. Note that Modules 6 through 8 are only accessible when
the appropriate plug-in option card is installed. If lost or confused while
programming, press the DSP key to exit programming mode and start over.
When programming is complete, it is recommended to record the meter settings
on the Parameter alue Chart and lock-out parameter programming with a User
Input or lock-out code. (See Modules 2 and 3 for lock-out details.)
FACTORY SETTINGS
Factory Settings may be completely restored in Module 9. This is a good
starting point if encountering programming problems. Throughout the module
description sections which follow, the factory setting for each parameter is
shown below the parameter display. In addition, all factory settings are listed on
the Parameter alue Chart following the programming section.
ALTERNATING SELECTION DISPLAY
In the module description sections which follow, the dual display with
arrows appears for each programming parameter. This is used to illustrate the
display alternating between the parameter (top display) and the parameter's
Factory Setting (bottom display). In most cases, selections or value ranges for
the parameter will be listed on the right.
Indicates Program Mode Alternating Display
Parameter
Selection/Value
STEP B STEP PROGRAMMING INSTRUCTIONS:
PROGRAMMING MODE ENTRY (PAR KEY
The Programming Mode is entered by pressing the PAR key. If this mode is
not accessible, then meter programming is locked by either a security code or a
hardware lock. (See Modules 2 and 3 for programming lock-out details.)
MODULE ENTRY (ARROW & PAR KEYS
Upon entering the Programming Mode, the display alternates between
and the present module (initially ). The arrow keys (F1and F2) are used
to select the desired module, which is then entered by pressing the PAR key.
PARAMETER (MODULE MENU (PAR KEY
Each module has a separate parameter menu. These menus are shown at the
start of each module description section which follows. The PAR key is pressed
to advance to a particular parameter to be changed, without changing the
programming of preceding parameters. After completing a module, the display
will return to . From this point, programming may continue by selecting
and entering additional modules. (See MODULE ENTRY above.)
PARAMETER SELECTION ENTRY (ARROW & PAR KEYS
For each parameter, the display alternates between the parameter and the
present selection or value for that parameter. For parameters which have a list
of selections, the arrow keys (F1and F2) are used to sequence through the
list until the desired selection is displayed. Pressing the PAR key stores and
activates the displayed selection, and also advances the meter to the next
parameter.
NUMERICAL VALUE ENTRY (ARROW, RST & PAR KEYS
For parameters which require a numerical value entry, the arrow keys can be
used to increment or decrement the display to the desired value. When an arrow
key is pressed and held, the display automatically scrolls up or scrolls down.
The longer the key is held, the faster the display scrolls.
The RST key can be used in combination with the arrow keys to enter large
numerical values. When the RST key is pressed along with an arrow key, the
display scrolls by 1000’s. Pressing the PAR key stores and activates the
displayed value, and also advances the meter to the next parameter.
PROGRAMMING MODE EXIT (DSP KEY or PAR KEY at
The Programming Mode is exited by pressing the DSP key (from anywhere
in the Programming Mode) or the PAR key (with displayed). This will
commit any stored parameter changes to memory and return the meter to the
Display Mode. If a parameter was just changed, the PAR key should be pressed
to store the change before pressing the DSP key. (If power loss occurs before
returning to the Display Mode, verify recent parameter changes.)
PAX-D.QXD 10/11/04 11:38 AM Page 14

15
.1 MODULE 1 - SIGNAL INPUT PARAMETERS ()
PAXH INPUT RANGE
PAXH INPUT COUPLE
Select the input range that corresponds to the external signal. This selection
should be high enough to avoid input signal overload but low enough for the
desired input resolution. This selection and the position of the Input Range
Jumper must match.
The input signal can be either AC coupled (rejecting the DC components of
the signal) or DC coupled (measures both the AC and DC components of the
signal). The coupling jumper and the setting of this parameter must match.
dC
or
AC
SELECTION
RANGE
RESOLUTION
5.000 A
200.00 mA
20.000 mA
2.0000 mA
200.00 µA
200uA
RANGE
RESOLUTION
SELECTION
300.0 V
20.000 V
2.0000 V
200.00 mV
0.2u
PAX PARAMETER MENU
PAXT PARAMETER MENU
PAXD INPUT RANGE
Select the input range that corresponds to the external signal. This selection
should be high enough to avoid input signal overload but low enough for the
desired input resolution. This selection and the position of the Input Range
Jumper must match.
1000o
10000 ohm
1000.0 ohm
±200.00 mV
±2.0000 A
2A
SELECTION RANGE
RESOLUTION
RANGE
RESOLUTION
SELECTION
100o
300u
100.00 ohm
±300.00 V
±200.00 mA
20u
2u
±20.000 V
±2.0000 V
±20.000 mA
±2.0000 mA
±200.00 µA
200uA
Refer to the appropriate Input Range for the selected
meter. Use only one Input Range, then proceed to Display
Decimal Point.
PAXP INPUT RANGE
Select the input range that corresponds to the external signal.
10.000 V
20.000 mA
RANGE
RESOLUTION
SELECTION
PAXS INPUT RANGE
Select the input range that corresponds to the external signal. This selection
should be high enough to avoid input signal overload but low enough for the
desired input resolution. This selection and the position of the Input Range
Jumper must match.
RANGE
RESOLUTION
0.02u
SELECTION
±24 mV
±240 mV
PAXT INPUT TYPE
Select the input type that corresponds to the input sensor. For RTD types,
check the RTD Input Jumper for matching selection. For custom types, the
Temperature Scale parameter is not available, the Display Decimal Point is
expanded, and Custom Sensor Scaling must be completed.
CS-rH
Custom RTD Low
Custom RTD igh
N TC
B TC
Cu427
Custom TC
RTD copper 10 Ω
S TC
R TC
SELECTION TYPETYPESELECTION
Ni672
Pt392
RTD nickel 672
RTD platinum 392
K TC
Pt385
RTD platinum 385
C TC
J TC
E TC
T TC
tc-t
PAXT TEMPERATURE SCALE
Select the temperature scale. This selection applies for Input, MAX, MIN,
and TOT displays. This does not change the user installed Custom Units
Overlay display. If changed, those parameters that relate to the temperature
scale should be checked. This selection is not available for custom sensor types.
°C°F
0.000 0.00000.000.00
DISPLAY DECIMAL POINT
Select the decimal point location for the Input, MAX and MIN displays. (The
TOT display decimal point is a separate parameter.) This selection also affects
, and parameters and setpoint values.
For the PAXT, these are only
available with Custom Scaling.
PAX-D.QXD 10/11/04 11:38 AM Page 15

PAXT: ICE POINT SLOPE
PAXT: TEMPERATURE DISPLAY OFFSET*
16
DISPLAY ROUNDING*
100502010
521
Rounding selections other than one, cause the Input Display to ‘round’ to the
nearest rounding increment selected (ie. rounding of ‘5’ causes 122 to round to
120 and 123 to round to 125). Rounding starts at the least significant digit of
the Input Display. Remaining parameter entries (scaling point values, setpoint
values, etc.) are not automatically adjusted to this display rounding selection.
The temperature display can be corrected with an offset value. This can be
used to compensate for probe errors, errors due to variances in probe placement
or adjusting the readout to a reference thermometer. This value is automatically
updated after a Zero Display to show how far the display is offset. A value of
zero will remove the affects of offset.
to
FILTER SETTING*
The input filter setting is a time constant expressed in tenths of a second. The
filter settles to 99% of the final display value within approximately 3 time
constants. This is an Adaptive Digital Filter which is designed to steady the
Input Display reading. A value of ‘0’ disables filtering.
to seconds
FILTER BAND*
The digital filter will adapt to variations in the input signal. When the
variation exceeds the input filter band value, the digital filter disengages. When
the variation becomes less than the band value, the filter engages again. This
allows for a stable readout, but permits the display to settle rapidly after a large
process change. The value of the band is in display units, independent of the
Display Decimal Point position. A band setting of ‘0’ keeps the digital filter
permanently engaged.
to display units
* Factor Setting can be used without affecting basic start-up.
This parameter sets the slope value for ice point compensation for the
Custom TC range () only. The fixed thermocouple ranges are
automatically compensated by the meter and do not require this setting. To
calculate this slope, use µ data obtained from thermocouple manufacturers’
tables for two points between 0°C and 50°C. Place this corresponding µ and
°C information into the equation:
slope = (µ2- µ1)/(°C2- °C1).
Due to the nonlinear output of thermocouples, the compensation may show
a small offset error at room temperatures. This can be compensated by the offset
parameter. A value of 0 disables internal compensation when the thermocouple
is externally compensated.
to µV/°C
For the PAXT, the following parameters only apply to Custom
Sensor Scaling.
SCALING POINTS*
Linear - Scaling Points (2
For linear processes, only 2 scaling points are necessary. It is recommended
that the 2 scaling points be at opposite ends of the input signal being applied.
The points do not have to be the signal limits. Display scaling will be linear
between and continue past the entered points up to the limits of the Input Signal
Jumper position. Each scaling point has a coordinate-pair of Input alue ()
and an associated desired Display alue ().
Nonlinear - Scaling Points (Greater than 2
For non-linear processes, up to 16 scaling points may be used to provide a
piece-wise linear approximation. (The greater the number of scaling points
used, the greater the conformity accuracy.) The Input Display will be linear
between scaling points that are sequential in program order. Each scaling point
has a coordinate-pair of Input alue () and an associated desired Display
alue (). Data from tables or equations, or empirical data could be used to
derive the required number of segments and data values for the coordinate pairs.
In the SFPAX software, several linearization equations are available.
to
SCALING STYLE
If Input alues and corresponding Display alues are known, the Key-in
() scaling style can be used. This allows scaling without the presence or
changing of the input signal. If Input alues have to be derived from the actual
input signal source or simulator, the Apply () scaling style must be used.
apply signal
APLY
key-in data
KEY
This parameter does not apply for the PAXT. Scaling values for the PAXT
must be keyed-in.
INPUT VALUE FOR SCALING POINT 1
For Key-in (), enter the known first Input alue by using the arrow keys.
(The Input Range selection sets up the decimal location for the Input alue).
For Apply (), apply the input signal to the meter, adjust the signal source
externally until the desired Input alue appears. In either method, press the
PAR key to enter the value being displayed. The DSP key can be pressed
without changing the previously stored value in the style.
to
DISPLAY VALUE FOR SCALING POINT 1
to
Enter the first coordinating Display alue by using the arrow keys. This is
the same for and scaling styles. The decimal point follows the
selection.
INPUT VALUE FOR SCALING POINT 2
to
For Key-in (), enter the known second Input alue by using the arrow
keys. For Apply (), adjust the signal source externally until the next
desired Input alue appears. (Follow the same procedure if using more than 2
scaling points.)
These bottom selections are not
available for the PAXT.
PAX-D.QXD 10/11/04 11:38 AM Page 16

17
DISPLAY VALUE FOR SCALING POINT 2
to
General Notes on Scaling
1. Input alues for scaling points should be confined to the limits of the Input
Range Jumper position.
2. The same Input alue should not correspond to more than one Display alue.
(Example: 20 mA can not equal 0 and 10.)
This is referred to as read out jumps (vertical scaled segments).
3. The same Display alue can correspond to more than one Input alue.
(Example: 0 mA and 20 mA can equal 10.)
This is referred to as readout dead zones (horizontal scaled segments).
4. The maximum scaled Display alue spread between range maximum and
minimum is limited to 65,535. For example using +20 mA range the
maximum +20 mA can be scaled to is 32,767 with 0 mA being 0 and Display
Rounding of 1. (Decimal points are ignored.) The other half of 65,535 is for
the lower half of the range 0 to -20 mA even if it is not used. With Display
Rounding of 2, +20 mA can be scaled for 65,535 (32,767 x 2) but with even
Input Display values shown.
5. For input levels beyond the first programmed Input alue, the meter extends
the Display alue by calculating the slope from the first two coordinate pairs
( / & / ). If = 4 mA and = 0, then 0 mA
would be some negative Display alue. This could be prevented by making
= 0 mA / = 0, = 4 mA / = 0, with = 20 mA /
= the desired high Display alue. The calculations stop at the limits of
the Input Range Jumper position.
6. For input levels beyond the last programmed Input alue, the meter extends
the Display alue by calculating the slope from the last two sequential
coordinate pairs. If three coordinate pair scaling points were entered, then the
Display alue calculation would be between / & / .
The calculations stop at the limits of the Input Range Jumper position.
Enter the second coordinating Display alue by using the arrow keys. This
is the same for and scaling styles. (Follow the same procedure if
using more than 2 scaling points.)
.2 MODULE 2 - USER INPUT AND FRONT PANEL FUNCTION KEY
PARAMETERS ()
PARAMETER MENU
The three user inputs are individually programmable to perform specific
meter control functions. While in the Display Mode or Program Mode, the
function is executed the instant the user input transitions to the active state.
The front panel function keys are also individually programmable to perform
specific meter control functions. While in the Display Mode, the primary
function is executed the instant the key is pressed. Holding the function key for
three seconds executes a secondary function. It is possible to program a
secondary function without a primary function.
In most cases, if more than one user input and/or function key is programmed
for the same function, the maintained (level trigger) actions will be performed
while at least one of those user inputs or function keys are activated. The
momentary (edge trigger) actions will be performed every time any of those
user inputs or function keys transition to the active state.
Note: In the following explanations, not all selections are available for both
user inputs and front panel function ke s. Alternating displa s are shown
with each selection. Those selections showing both displa s are available for
both. If a displa is not shown, it is not available for that selection.
will represent all three user inputs. will represent all five function ke s.
NO FUNCTION
No function is performed if activated. This is the factory setting for all user
inputs and function keys. No function can be selected without affecting basic
start-up.
PROGRAMMING MODE LOCK-OUT
Programming Mode is locked-out, as long as activated
(maintained action). A security code can be configured to
allow programming access during lock-out.
ZERO (TARE DISPLAY
The Zero (Tare) Display provides a way to zero the Input Display value at
various input levels, causing future Display readings to be offset. This function
is useful in weighing applications where the container or material on the scale
should not be included in the next measurement value. When activated
(momentary action), flashes and the Display is set to zero. At the same
time, the Display value (that was on the display before the Zero Display) is
subtracted from the Display Offset alue and is automatically stored as the new
Display Offset alue (). If another Zero (tare) Display is performed, the
display will again change to zero and the Display reading will shift accordingly.
RELATIVE/ABSOLUTE DISPLAY
This function will switch the Input Display between Relative and Absolute.
The Relative is a net value that includes the Display Offset alue. The Input
Display will normally show the Relative unless switched by this function.
Regardless of the display selected, all meter functions continue to operate based
on relative values. The Absolute is a gross value (based on Module 1 DSP and
INP entries) without the Display Offset alue. The Absolute display is selected
as long as the user input is activated (maintained action) or at the transition of
the function key (momentary action). When the user input is released, or the
function key is pressed again, the input display switches back to Relative
display. (absolute) or (relative) is momentarily displayed at transition
to indicate which display is active.
PAX-D.QXD 10/11/04 11:38 AM Page 17

18
HOLD DISPLAY
The shown display is held but all other meter functions
continue as long as activated (maintained action).
HOLD ALL FUNCTIONS
The meter disables processing the input, holds all display
contents, and locks the state of all outputs as long as activated
(maintained action). The serial port continues data transfer.
SYNCHRONIZE METER READING
The meter suspends all functions as long as activated
(maintained action). When the user input is released, the
meter synchronizes the restart of the A/D with other
processes or timing events.
STORE BATCH READING IN TOTALIZER
The Input Display value is one time added (batched) to the Totalizer at
transition to activate (momentary action). The Totalizer retains a running sum of
each batch operation until the Totalizer is reset. When this function is selected,
the normal operation of the Totalizer is overridden.
SELECT TOTALIZER DISPLAY
The Totalizer display is selected as long as activated
(maintained action). When the user input is released, the
Input Display is returned. The DSP key overrides the active
user input. The Totalizer continues to function including
associated outputs independent of being displayed.
RESET TOTALIZER
When activated (momentary action), flashes and the Totalizer resets to
zero. The Totalizer then continues to operate as it is configured. This selection
functions independent of the selected display.
RESET AND ENABLE TOTALIZER
When activated (momentary action), flashes and
the Totalizer resets to zero. The Totalizer continues to
operate while active (maintained action). When the user
input is released, the Totalizer stops and holds its value. This
selection functions independent of the selected display.
ENABLE TOTALIZER
The Totalizer continues to operate as long as activated
(maintained action). When the user input is released, the
Totalizer stops and holds its value. This selection functions
independent of the selected display.
SELECT MAXIMUM DISPLAY
The Maximum display is selected as long as activated
(maintained action). When the user input is released, the
Input Display returns. The DSP key overrides the active
user input. The Maximum continues to function
independent of being displayed.
RESET MAXIMUM
When activated (momentary action), flashes and
the Maximum resets to the present Input Display value. The
Maximum function then continues from that value. This
selection functions independent of the selected display.
RESET, SELECT, ENABLE MAXIMUM DISPLAY
When activated (momentary action), the Maximum value
is set to the present Input Display value. Maximum continues
from that value while active (maintained action). When the
user input is released, Maximum detection stops and holds its
SELECT MINIMUM DISPLAY
The Minimum display is selected as long as activated
(maintained action). When the user input is released, the
Input Display is returned. The DSP key overrides the active
user input. The Minimum continues to function
independent of being displayed.
RESET MINIMUM
When activated (momentary action), flashes and
the Minimum reading is set to the present Input Display
value. The Minimum function then continues from that value.
This selection functions independent of the selected display.
RESET, SELECT, ENABLE MINIMUM DISPLAY
When activated (momentary action), the Minimum value
is set to the present Input Display value. Minimum continues
from that value while active (maintained action). When the
user input is released, Minimum detection stops and holds
RESET MAXIMUM AND MINIMUM
When activated (momentary action), flashes and the Maximum and
Minimum readings are set to the present Input Display value. The Maximum
and Minimum function then continues from that value. This selection functions
independent of the selected display.
CHANGE DISPLAY INTENSITY LEVEL
When activated (momentary action), the display intensity changes to the next
intensity level (of 4). The four levels correspond to Display Intensity Level (
) settings of 0, 3, 8, and 15. The intensity level, when changed via the User
Input/ Function Key, is not retained at power-down, unless Quick Programming
or Full Programming mode is entered and exited. The meter will power-up at the
last saved intensity level.
its value. This selection functions independent of the selected display. The DSP
key overrides the active user input display but not the Minimum function.
value. This selection functions independent of the selected display. The DSP key
overrides the active user input display but not the Maximum function.
PAX-D.QXD 10/11/04 11:38 AM Page 18

1
SETPOINT SELECTIONS
- Select main or alternate setpoints
- Reset Setpoint 1 (Alarm 1
- Reset Setpoint 2 (Alarm 2
- Reset Setpoint 3 (Alarm 3
- Reset Setpoint 4 (Alarm 4
- Reset Setpoint 3 & 4 (Alarm 3 & 4
- Reset Setpoint 2, 3 & 4 (Alarm 2, 3 & 4
- Reset Setpoint All (Alarm All
The following selections are accessible only with the Setpoint plug-in card
installed. Refer to the Setpoint Card Bulletin shipped with the Setpoint plug-in
card for an explanation of their operation.
Setpoint
Card
Only
PRINT REQUEST
The meter issues a block print through the serial port when activated. The
data transmitted during a print request is programmed in Module 7. If the user
input is still active after the transmission is complete (about 100 msec), an
additional transmission occurs. As long as the user input is held active,
continuous transmissions occur.
PROGRAM MODE SECURITY CODE*
By entering any non-zero value, the prompt will appear when trying
to access the Program Mode. Access will only be allowed after entering a
matching security code or universal code of . With this lock-out, a user input
would not have to be configured for Program Lock-out. However, this lock-out
is overridden by an inactive user input configured for Program Lock-out.
SP-1 SP-2 SP-3 SP-4 SETPOINT ACCESS*
The setpoint displays can be programmed for , or (See the
following table). Accessible only with the Setpoint plug-in card installed.
MAXIMUM DISPLAY LOCK-OUT*
MINIMUM DISPLAY LOCK-OUT*
TOTALIZER DISPLAY LOCK-OUT*
These displays can be programmed for or . When programmed for
, the display will not be shown when the DSP key is pressed regardless of
Program Lock-out status. It is suggested to lock-out the display if it is not needed.
The associated function will continue to operate even if its display is locked-out.
.3 MODULE 3 - DISPLAY AND PROGRAM LOCK-OUT
PARAMETERS ()
PARAMETER MENU
* Factor Setting can be used without affecting basic start-up.
to
Module 3 is the programming for Display lock-out and “Full” and “Quick”
Program lock-out.
When in the Display Mode, the available displays can be read consecutively
by repeatedly pressing the DSP key. An annunciator indicates the display being
shown. These displays can be locked from being visible. It is recommended that
the display be set to when the corresponding function is not used.
“Full” Programming Mode permits all parameters to be viewed and
modified. This Programming Mode can be locked with a security code and/or
user input. When locked and the PAR key is pressed, the meter enters a Quick
Programming Mode. In this mode, the setpoint values can still be read and/or
changed per the selections below. The Display Intensity Level ()
parameter also appears whenever Quick Programming Mode is enabled and the
security code is greater than zero.
SELECTION DESCRIPTION
Visible but not changeable in Quick Programming Mode
Visible and changeable in Quick Programming Mode
Not visible in Quick Programming Mode
Immediate access.“Full” ProgrammingNot Active
0
No accessQuick ProgrammingActive
0
Immediate access.“Full” ProgrammingNot Active
>0
After Quick Programming with correct code # at prompt.Quick Programming w/Display IntensityActive
>0
After Quick Programming with correct code # at prompt.Quick Programming w/Display Intensity————
not
>0
Immediate access.“Full” Programming————
not
0
“FULL” PROGRAMMING MODE ACCESS
WHEN PAR KEY IS
PRESSED
USER INPUT
STATE
USER INPUT
CONFIGURED
SECURITY
CODE
PROGRAMMING MODE ACCESS
Throughout this document, Programming Mode (without Quick in front) always refers to “Full” Programming (all meter parameters are accessible).
SELECTION DESCRIPTION
Visible in Display Mode
Not visible in Display Mode
PAX-D.QXD 10/11/04 11:38 AM Page 19

20
MAX CAPTURE DELAY TIME*
When the Input Display is above the present MAX value for the entered
delay time, the meter will capture that display value as the new MAX reading.
A delay time helps to avoid false captures of sudden short spikes.
MIN CAPTURE DELAY TIME*
When the Input Display is below the present MIN value for the entered delay
time, the meter will capture that display value as the new MIN reading. A delay
time helps to avoid false captures of sudden short spikes.
UNITS LABEL BACKLIGHT*
The Units Label Kit Accessory contains a sheet of custom unit overlays
which can be installed in to the meter’s bezel display assembly. The backlight
for these custom units is activated by this parameter.
DISPLAY OFFSET VALUE*
Unless a Zero Display was performed or an offset from Module 1 scaling is
desired, this parameter can be skipped. The Display Offset alue is the
difference from the Absolute (gross) Display value to the Relative (net) Display
value for the same input level. The meter will automatically update this Display
Offset alue after each Zero Display. The Display Offset alue can be directly
keyed-in to intentionally add or remove display offset. See Relative / Absolute
Display and Zero Display explanations in Module 2.
DISPLAY UPDATE RATE*
This parameter determines the rate of display update. When set to 20
updates/second, the internal re-zero compensation is disabled, allowing for the
fastest possible output response.
.4 MODULE 4 - SECONDARY FUNCTION PARAMETERS ()
PARAMETER MENU
* Factor Setting can be used without affecting basic start-up.
to sec.
to sec.
to
updates/sec.
PAXS: AUTO-ZERO TRACKING
to sec.
PAXS: AUTO-ZERO BAND
to
The meter can be programmed to automatically compensate for zero drift.
Drift may be caused by changes in the transducers or electronics, or
accumulation of material on weight systems.
Auto-zero tracking operates when the readout remains within the tracking
band for a period of time equal to the tracking delay time. When these
conditions are met, the meter re-zeroes the readout. After the re-zero operation,
the meter resets and continues to auto-zero track.
The auto-zero tracking band should be set large enough to track normal zero
drift, but small enough to not interfere with small process inputs.
For filling operations, the fill rate must exceed the auto-zero tracking rate.
This avoids false tracking at the start of the filling operation.
Fill Rate ≥tracking band
tracking time
Auto-zero tracking is disabled by setting the tracking band parameter = 0.
PAXT: ICE POINT COMPENSATION*
This parameter turns the internal ice point compensation on or off. Normally,
the ice point compensation is on. If using external compensation, set this
parameter to off. In this case, use copper leads from the external compensation
point to the meter. If using Custom TC range, the ice point compensation can
be adjusted by a value in Module 1 when this is yes.
This parameter does not apply for the PAXT.
PAX-D.QXD 10/11/04 11:38 AM Page 20
Table of contents
Other Weber Measuring Instrument manuals