CONCERT EX1RM
PREPARATION
EX1SM suspended Exit signs are available with a
selection of ceiling and wall mounting plates. The selected
mounting plate should be fitted to the mounting surface
using fixings appropriate to the application. Supply cables
should be installed according to National Wiring
Regulations and should suit the type of mounting
arrangement chosen. Please note: No strain relief is
provided for supply cables, installer must provide if
necessary.
The EX1SM body is provided with two fixing studs. In the
case of the ceiling and flag mount brackets the two studs
push into key slots and are secured by a screw in the side.
The wall mount bracket is secured by quarter turn twist
locks which are rotated so the blade of the flat hooks
locates into the slots on the mounting studs.
Accessory Part Codes:
Ceiling Mounting Bracket - EX1SCBRK
End Fixing (Flag) Mounting Bracket - EX1SEBRK
Wall Mounting Bracket - EX1SWBRK
Wire Suspension Kit (1m) - EX1SWIR
INSTALL
1. Unscrew the gear box cover and slide out from the gear box
making sure the screw and earthing washer is retained. Set
cover to one side.
2. A support cable has been provided that can be detached
from the fitting and screwed to the ceiling mount brackets. It
can then be re-attached so the fitting hangs on one side for
wiring.
3. Bring the supply cable through the grommet on either side
of the gear box and connect to the terminal block.
4. Replace the gear box cover.
5. Remove the end cap from exit sign housing. Slide away
extruded cover.
6. Connect the batteries.
7. Replace the extruded cover and the end cap.
8. Attach to the mounting bracket as mentioned above.
PREPARATION
EX1RM LED Exit signs utilise adjustable arms so that the
main body can be passed through a suitable cut-out in the
supporting surface (350mm x 95mm) and the arms can be
adjusted to lock the unit against the plasterboard, T-bar or tile.
Ceiling thickness: 10-22mm
Where installing into thin or soft ceiling tiles, an additional
pattress may be required. This should be a support panel, to
be fitted behind the ceiling, cut from suitable sheet material
with a hole drilled to match the luminaire cut aperture.
Please note: No strain relief is provided for supply cables,
installer must provide if necessary.
INSTALL
1. Undo the two screws on the fascia
plate. The fitting is supplied with safety
cables enabling the fascia plate to
hang during installation.
2. Pass the luminaire through the cut
out and adjust the swing arms until the
luminaire is securely located in the
supporting surface.
3. Bring the supply cables through the
top hole and connect to the terminal
block: L1 is for permanent supply to
charge the integral battery; L is for the
switched supply if required.
4. Connect the batteries.
5. Insert the legend blade through the
fascia plate and fix with the two
screws and nuts provided.
6. Replace the fascia plate making
sure all cables are tucked in and not
obscuring LEDs.
N E L1 L2
N- NEUTRAL
E- EARTH
L/L1- SWITCHED LIVE
L2- PERMANENT LIVE
E- EARTH
L1- PERMANENT LIVE
L- SWITCHED LIVE
N- NEUTRAL
E L1 L N
FIG.1 MAINS TERMINAL BLOCK
SUPPORT CABLE
SCREW INTO CEILING BRACKET -
FIXINGS SUPPLIED BY OTHERS.
GEAR BOX COVER
UNSCREW END CAP AND
SLIDE AWAY COVER
CONNECT BATTERIES