13
Commissioning
10
Warning Close the door of a control unit on operating for avoiding electric accidents by high
voltage and hazards caused by the water leakage of pumps and pipes.
Besides, electric appliances around a system should be treated in the same way.
Caution Care not to block the motor ventilator with foreign materials on operating.
It could cause a fire, damages of a product.
10.1)Initial operating order
①Check a main power breaker and a protector capacity
②Check the cable square of main power.
③Check a main power voltage.
④Check connecting state of pipes and electric cables.
⑤Check water level in a suction reservoir.
At each pump, close a isolating valve in the suction and
release a air vent plug and slowly open a isolating valve.
Water and air come out together.
If air vent sufficiently, fasten the plug again and open the isolating valve completely.
(The operation with a isolating valve close could cause dry operation and troubles.
①Supply power ( Pump power / Control power )
②Turn on all breakers (MCCB & CP) in a control unit.
At that time,『Emergency operating key』should be off.
If the emergency operating key turns on, only the selected pump operates continuously.
(it is impossible to operate automatically at this situation.)
By the『Emergency operating key』, check the rotating direction of a pump as operating each pump
in a short term. the rotating direction of a pump is marked on the motor or the pump. If the direction
is reverse, replace two of pump power lines (R.S.T).
(If the『Emergency operating key』is on, the selected pump operates and the control circuit is off.
Therefore, after checking the rotating direction, let the『emergency operating key』be off for the
automatic operation.
Caution When wiring electric lines again from a control unit to motors, must keep the
same order as before. If not, the rotating direction under a Inverter control
could be different from that under manual operation. It will cause troubles.
Set operating data for the automatic operation.
(The setup of operating data for each items refers to『Operating data and Setup』
(★, the mark is adapted to a inverter control type.)
①Essential operating data :
On-pressure, Off-pressure, Minimum speed (★), Shut-off pressure
②Ancillary operating data :
Discharge pressure (For resetting the zero point of a pressure transmitter).
Max. pressure (For stopping a system in order to protect from severe overpressure).
Delay time (For avoiding frequent on/off).
(★) Control type (For changing the inverter control type to the step control type).
If pressing the『AUTO/ STOP』key, the left lamp is on and the system is operated in accordance
with operating data. If pressing again the『AUTO/ STOP』key, the left lamp is off and the system
is stopped. Please, check operating state and whether it work normally or not.
At initial operation, Must vent the air which stayed inside pipes or pumps as opening an air vent plug.
If air does not vent sufficiently, even if opening a tap, water could not come out.
On operating, check whether pressure, vibration, and noise are normal or not.
Fig. 11
Motor
supporter
Air vent
plug
Ready to operate
Air vent
Supply power
Check the direct
of rotation
Install operating
data
Automatic
operating