④. Start and shut off time-delay Click “PDU” in the configuration box which is on the left side of the
interface, display interface as shown below:
Users can start or shut off time-delay of XL-IPM816 8-way output. The picture above is the factory Settings,
it means that the 8 circuit of XL-IPM816 will output from the 1st to the 8th port in sequence in the interval
of one second after connecting with power. When open the 8 output through the network, the starting
delay time will display on the 8 output port. It is important to note that when the user disconnect the input
power of XL-IPM816, shutting off the time-delay function is invalid. Shutting off the time-delay function is
only applicable to control 8-way output through a network.
⑤. Threshold value setting Click “Threshold value” in the configuration box which is on the left side of the
interface, display interface as shown below.
The picture above is the factory Settings, the meaning is:
Current warning value 17A: When the total current exceeds 17A, XL-IPM816 buzzer sends out "beep, beep"
sound alarm
Current overload value 17A: When the total current exceeds 17 a, XL-IPM816 will cut off the power supply
of all output port
Warning voltage 250V: When the input voltage exceeds 250V, XL-IPM816 buzzer sends out "beep, beep"
sound alarm
Current overload value 300V: When the input voltage exceeds 300V, XL-IPM816 cut off the power supply of
all output port
Temperature is under 5 ℃, or exceed 50 ℃: When XL-IPM816 built-in temperature and humidity sensor
sensing the environment temperature is under 5 ℃or exceed 50 ℃, XL-IPM816 buzzer sends out "beep,
beep" sound alarm
Humidity warning value 80%: When XL-IPM816 built-in temperature and humidity sensor sensing
environment humidity is more than 80%, XL-IPM816 buzzer sends out "beep, beep" sound alarm