IM 05P04D41-11EN page 2/10
nMounting the Instrument Main Unit
Provideaninstrumentedpanelsteelsheetof1to10mmthickness.
Afteropeningthemountingholeonthepanel,followtheproceduresbelowtoinstall
thecontroller:
1) Insertthecontrollerintotheopening from the front of the panelsothatthe
terminalboardontherearisatthefarside.
2) Setthebracketsinplaceonthetopandbottomofthecontrollerasshowninthe
gurebelow,thentightenthescrewsofthebrackets.Takecarenottoovertighten
them.
Bracket
(top mounting hardware)
Terminal board
Bracket
(bottom mounting hardware)
Panel
Insert a screwdriver into the
brackets to tighten the screws.
Direction to insert the
controller
Appropriate
tightening torque:
0.25 N•m
Insert the controller
into the opening at
the front of the panel.
• Tighten the screws with appropriate tightening torque within 0.25
N•m. Otherwise it may cause the case deformation or the bracket
damage.
• Make sure that foreign materials do not enter the inside of the
instrument through the case’s slit holes.
nExternal Dimensions and Panel Cutout Dimensions
(25)
(53) (2.09)
[(N-1)×96+92]
117 (4.61) min.
145 (5.71)
min.
+0.8
0
+0.8
0
92
“N” stands for the number of controllers to be
installed.
However, the measured value applies if N≥5.
65 (2.56)
20 (0.79)
11
(0.43)
1 to 10 mm (0.04 to 0.39 inch) (panel thickness)
Bracket
Bracket
94.6 (3.72)
91.6 (3.61)
105.2 (4.14)
96 (3.78)
96 (3.78)
• General mounting • Side-by-side close mounting
Terminal cover
Normal tolerance:
±(value of JIS B 0401-1998 tolerance class IT18)/2
+0.8
0
92
+0.03
0
(0.98)
+0.03
(3.62 )
+0.8
0
92
+0.03
0
(3.62 )
([(N-1)×3.78+3.62] )
+0.03
0
4. HardwareSpecications
This instrument is for Measurement Category No.1.
Do not use it for measurements in locations falling under Measure-
ment Categories No.2, No.3, and No.4.
Internal Wiring
Outlet
IV
III T
O( I )
II
Category IEC/EN/CSA/UL
61010-1 EN 61010-2-030 Remarks
No.1 Measurement
CategoryI O(Other) For measurements performed on circuits not
directlyconnectedtoMAINS.
No.2 Measurement
CategoryII
Measurement
CategoryII
For measurements performed on circuits directly
connectedtothelow-voltageinstallation.
No.3 Measurement
CategoryIII
Measurement
CategoryIII
Formeasurementsperformedinthebuildinginstal-
lation.
No.4 Measurement
CategoryIV
Measurement
CategoryIV
For measurements performed at the source of the
low-voltageinstallation.
nInputSpecications
●UniversalInput(Equippedasstandard)
• Numberofinputs:1
• Inputtype,instrumentrange,andmeasurementaccuracy:Seethetablebelow,
Input Type Instrument Range Accuracy
ºC ºF
Thermo-
couple
K
-270.0to1370.0ºC -450.0to2500.0ºF ±0.1%ofinstrumentrange±1digitfor
0°Cormore
±0.2%ofinstrumentrange±1digitfor
lessthan0°C
±2%ofinstrumentrange±1digitfor
lessthan-200.0°CofthermocoupleK
±1%ofinstrumentrange±1digitfor
lessthan-200.0°CofthermocoupleT
-270.0to1000.0ºC -450.0to2300.0ºF
-200.0to500.0ºC -200.0to1000.0ºF
J-200.0to1200.0ºC -300.0to2300.0ºF
T
-270.0to400.0ºC -450.0to750.0ºF
0.0to400.0ºC -200.0to750.0ºF
B0.0to1800.0ºC 32to3300ºF
±0.15%ofinstrumentrange±1digit
for400°Cormore
±5%ofinstrumentrange±1digitfor
lessthan400°C
S0.0to1700.0ºC 32to3100ºF ±0.15%ofinstrumentrange±1digit
R 0.0to1700.0ºC 32to3100ºF
N -200.0to1300.0ºC -300.0to2400.0ºF
±0.1%ofinstrumentrange±1digit
±0.25%ofinstrumentrange±1digit
forlessthan0°C
E -270.0to1000.0ºC -450.0to1800.0ºF ±0.1%ofinstrumentrange±1digitfor
0°Cormore
±0.2%ofinstrumentrange±1digitfor
lessthan0°C
±1.5%ofinstrumentrange±1digitfor
lessthan-200.0°CofthermocoupleE.
L -200.0to900.0ºC -300.0to1600.0ºF
U
-200.0to400.0ºC -300.0to750.0ºF
0.0to400.0ºC -200.0to1000.0ºF
W 0.0to2300.0ºC 32to4200ºF ±0.2%ofinstrumentrange±1digit
(Note2)
Platinel 2 0.0to1390.0ºC 32.0to2500.0ºF ±0.1%ofinstrumentrange±1digit
PR20-40 0.0to1900.0ºC 32to3400ºF
±0.5%ofinstrumentrange±1digitfor
800°Cormore
Accuracyisnotguaranteedforless
than800°C.
W97Re3-
W75Re25 0.0to2000.0ºC 32to3600ºF ±0.2%ofinstrumentrange±1digit
RTD
JPt100 -200.0to500.0ºC -300.0to1000.0ºF ±0.1%ofinstrumentrange±1digit
(Note1)
-150.00to150.00ºC -200.0to300.0ºF ±0.1%ofinstrumentrange±1digit
Pt100
-200.0to850.0ºC -300.0to1560.0ºF ±0.1%ofinstrumentrange±1digit
(Note1)
-200.0to500.0ºC -300.0to1000.0ºF
-150.00to150.00ºC -200.0to300.0ºF ±0.1%ofinstrumentrange±1digit
Standardsignal
0.400to2.000V
±0.1%ofinstrumentrange±1digit
1.000to5.000V
4.00to20.00mA
DCvoltage/current
0.000to2.000V
0.00to10.00V
0.00to20.00mA
-10.00to20.00mV
0.0to100.0mV
Theaccuracyisthatinthestandardoperatingconditions:23±2°C,55±10%RH,andpower
frequencyat50/60Hz.
Note1: ±0.3°C±1digitintherangebetween0and100°C,±0.5°C±1digitintherange
between-100and200°C.
Note2: W:W-5%Re/W-26%Re(HoskinsMfg.Co.).ASTME988
•Inputsampling(control)period:200ms
•Burnoutdetection:
FunctionsatTC,RTD,andstandardsignal.
Upscale,downscale,andoffcanbespecied.
Forstandardsignal,burnoutisdeterminedtohaveoccurredifitis0.1Vor0.4
mAorless.
•Inputbiascurrent:0.05µA(forTCorRTD)
•Measuredcurrent(RTD):About0.16mA
•Inputresistance:
TCormVinput:1MΩormore
Vinput:About1MΩ
mAinput:About250Ω
•Allowablesignalsourceresistance:
TCormVinput:250Ωorless
Effectsofsignalsourceresistance:0.1µV/Ωorless
DCvoltageinput:2kΩorless
Effectsofsignalsourceresistance:About0.01%/100Ω
• Allowablewiringresistance:
RTDinput:Max.150Ω/wire(Theconductorresistancebetweenthethreewires
shallbeequal.)
Wiringresistanceeffect:±0.1ºC/10Ω
• Allowableinputvoltage/current:
TC,mV,mAandRTDinput:±10VDC
Vinput:±20VDC
mAinput:±40mA
• Noiserejectionratio:
Normalmode:40dBormore(at50/60Hz)
Commonmode:120dBormore(at50/60Hz)
For100-240 VAC,thepowerfrequencycanbesetmanually.Automatic
detectionisalsoavailable.
For24VAC/DC,thepowerfrequencycanbesetmanually.
• Referencejunctioncompensationerror:
±1.0ºC(15to35ºC)
±1.5ºC(-10to15ºCand35to50ºC)
• Applicablestandards:JIS/IEC/DIN(ITS-90)forTCandRTD
nStepResponseTimeSpecications
Within1s(63%ofanalogoutputresponsetimewhenastepchangeof10to90%of
inputspanisapplied)
nRelayContactOutputSpecications
• Contacttypeandnumberofoutputs:
Limitcontroloutput:contactpoint1c;1point
Alarmoutput:contactpoint1a;3points(commonisindependent)
• Contactrating:
Contactpoint1c(limitcontroloutput):250VAC,3Aor30VDC,3A(resistanceload)
Contactpoint1a(alarmoutput):240VAC,1Aor30VDC,1A(resistanceload)
• Use:Alarmoutput,FAILoutput,etc.
• Timeresolutionoflimitcontroloutput:10msor0.1%ofoutput,whicheverislarger
Note:Thecontroloutputshouldalwaysbeusedwithaloadof10mAormore.
Thealarmoutputshouldalwaysbeusedwithaloadof1mAormore.
n
RetransmissionOutputSpecications
• Numberofoutputs:Retransmissionoutput;1
• Currentoutput:4to20mADCor0to20mADC/loadresistanceof600Ωorless
• Currentoutputaccuracy(conversionaccuracyfromPVdisplayonthesetscale):
±0.1%ofspan(±5%ofspanfor1mAorless)
Theaccuracyisthatinthestandardoperatingconditions:23±2°C,55±10%RH,
andpowerfrequencyat50/60Hz.
Thisisnotconversion accuracythroughinputandoutputbuttheperformanceof
transmission output itself.
nContactInputSpecications
• Numberofinputs:2points
• Inputtype:No-voltagecontactinputortransistorcontactinput
• Inputcontactrating:12VDC,10mAormore
Useacontactwithaminimumon-currentof1mAorless.
• ON/OFFdetection:
No-voltagecontactinput:
Contactresistanceof1kΩorlessisdeterminedas“ON”andcontact
resistanceof50kΩormoreas“OFF.”
Transistorcontactinput:
Inputvoltageof2Vorlessisdeterminedas“ON”andleakagecurrentmust
notexceed100µAwhen“OFF.”
• Minimumstatusdetectionholdtime:Controlperiod+50ms
• Use:Conrmationoperation,etc.
■ SafetyandEMCStandards
• Safety:
CompliantwithIEC/EN61010-1(CE),IEC/EN61010-2-201(CE),IEC/EN61010-
2-030(CE), approvedbyCAN/CSAC22.2No.61010-1(CSA),approvedby UL
61010-1.
CertiedforFM-3810andFM-3545.
Installationcategory:II
Pollutiondegree:2
Measurementcategory:I(CATI)(UL,CSA)
O(Other)(CE)
Ratedmeasurementinputvoltage:Max.10VDC
Ratedtransientovervoltage:1500V(*)
*ThisisareferencesafetystandardvalueformeasurementcategoryIofCSA/UL61010-
1,andformeasurementcategoryOofIEC/EN61010-2-030.Thisvalueisnotnecessarilya
guaranteeofinstrumentperformance.
• EMCstandards:
CompliantwithCEmarking
EN61326-1ClassA,Table2(Foruseinindustriallocations),
EN61326-2-3
*Theinstrumentcontinuestooperateatameasurementaccuracyofwithin±20%ofthe
rangeduringtesting.
EN55011ClassA,Group1
EN61000-3-2ClassA
EN61000-3-3
EMCRegulatoryArrangementinAustraliaandNewZealand(forallmodelinclud-
ingLL50A)
EN55011ClassA,Group1
• KCmarking:
Electromagneticwaveinterferencepreventionstandard,electromagneticwave
protection standard compliance
■ Construction,Installation,andWiring
• Degreeof protection provided by Enclosure: IP66 (forfrontpanel)(Notavailable
forside-by-sideclosemounting.)
• Material:Polycarbonate(Flameretardancy:UL94V-0)
• Casecolor:White(Lightgray)orBlack(Lightcharcoalgray)
• Weight:0.5kgorless
• Externaldimensions(mm):96(W)×96(H)×65(depthfromthepanelface)
(Depthexcepttheprojectionontherearpanel)
• Installation:Directpanelmounting;mountingbracket, one eachforupperand
lowermounting
• Panelcutoutdimensions(mm):92+0.8/0(W)×92+0.8/0(H)
•
Mountingattitude:Upto30degreesabovethehorizontal.Nodownwardtitlingallowed.
• Wiring:M3screwterminalwithsquarewasher(forsignalwiringandpowerwiring)
■ PowerSupplySpecicationsandIsolation
• Powersupply:
Ratedvoltage:100-240VAC(+10%/-15%),50/60Hz
24VAC/DC(+10%/-15%)(for/DCoption)
• Powerconsumption:18VA(DC:9VA,AC:14VAif/DCoptionisspecied)
• Databackup:Nonvolatilememory
• Powerholduptime:20ms(for100VACdrive)
• Withstandingvoltage
Betweenprimaryterminalsandsecondaryterminals:2300VACfor1minute(UL,CSA)
Betweenprimaryterminalsandsecondaryterminals:3000VACfor1minute(CE)
Betweenprimaryterminals:1500VACfor1minute
Betweensecondaryterminals:500VACfor1minute
(Primary terminals:Power*andrelayoutputterminals;Secondaryterminals:
AnalogI/Osignalterminals,contactinputterminals,communicationterminals
andfunctionalgroundingterminals.)
*:Powerterminalsfor24VAC/DCmodelsarethesecondaryterminals.
• Insulationresistance:Betweenpowersupplyterminalsandagroundingterminal
20MΩormoreat500VDC
• Isolationspecications
PV (universal) input terminals
Control relay (contact point c) output terminals
Alarm-1 relay (contact point a) output terminals
Alarm-2 relay (contact point a) output terminals
Alarm-3 relay (contact point a) output terminals
Contact input terminals
RS-485 communication terminals
Ethernet communication terminal
Retransmission (analog) output terminals
Internal
circuits
Power
supply
The circuits divided by lines are insulated mutually.
■ EnvironmentalConditions
Normal Operating Conditions:
• Ambienttemperature:-10to50ºC(-10to40ºCforside-by-sideclosemounting)
• Ambienthumidity:20to90%RH(nocondensationallowed)
• Magneticeld:400A/morless
• Continuousvibrationat5to9Hz:Halfamplitudeof1.5mmorless,1oct/minfor90
minuteseachinthethreeaxisdirections
Continuousvibrationat9to150Hz:4.9m/s2orless,1oct/minfor90minuteseach
inthethreeaxisdirections
• Short-periodvibration:14.7m/s2, 15 seconds or less
• Shock:98m/s2or less, 11 ms
• Altitude:2000morlessabovesealevel
• Warm-uptime:30minutesormoreafterthepoweristurnedon
• Startuptime:Within10seconds
*: TheLCD(aliquidcrystaldisplay)isusedforadisplayportionofthisproduct.
TheLCDhasacharacteristicthatthedisplayactionbecomeslateatthelow
temperature.However,thecontrolfunctionisnotaffected.
Transportation and Storage Conditions:
• Temperature:-25to70ºC
• Temperaturechangerate:20ºC/horless
• Humidity:5to95%RH(nocondensationallowed)
Effects of Operating Conditions
• Effectofambienttemperature:
VoltageorTCinput:±1µV/ºCor±0.01%ofF.S./ºC,whicheverislarger
Currentinput:±0.01%ofF.S./ºC
RTDinput:±0.05ºC/ºC(ambienttemperature)orless
Analogoutput:±0.02%ofF.S./ºCorless
• Effectofpowersupplyvoltageuctuation
Analoginput:±0.05%ofF.S.orless
Analogoutput:±0.05%ofF.S.orless
(Eachwithinratedvoltagerange)