manuals.online logo
Brands
  1. Home
  2. •
  3. Brands
  4. •
  5. YOKOGAWA
  6. •
  7. Controllers
  8. •
  9. YOKOGAWA UT52A/MDL series User manual

YOKOGAWA UT52A/MDL series User manual

IM 05P01C81-11EN page 1/6
Contents
1. Safety Precautions
2. ModelandSu󰀩xCodes
3. How to Install
4. HardwareSpecications
5. HowtoConnectWires
6. TerminalWiringDiagrams
7. Setup Procedure
8. Operations
9. Troubleshooting
Introduction
ThankyouforpurchasingtheUT55A/MDL,UT52A/MDLController.(TheUT55Aand
UT52Awithoption/MDLhavenodisplay.)
Thisoperationguidedescribestheinstalling,wirings,setupow,andtroubleshooting
relatedtothesingle-loopcontrolfunctionoftheUT55A/MDLandUT52A/MDL.The
guideshouldbeprovidedtotheenduserofthisproduct.
Besuretoreadthisoperationguidebeforeusing theproductinorder toensure
correct operation.
Fordetailsofeachfunction,refertotheelectronicmanual.Beforeusingtheproduct,
refertothetableofModelandSu󰀩xCodestomakesurethatthedeliveredproduct
isconsistentwiththemodelandsu󰀩xcodesyouordered.Alsomakesurethatthe
followingitemsareincludedinthepackage.
•Controller(themodelyouordered) .........................................................x1
•TerminalCover(L4502XPforUT55A/L4502XQforUT52A) ................x1
•UnitLabel(L4502VZ) ..............................................................................x1
•TagLabel(L4502VE)(Onlywhenordered.) ...........................................x1
•OperationGuideforSingle-loopControl(thisdocument) .......................x3(A3size)
(InstallationandWiring,InitialSettings,Operations,andParameters)
l
TargetReaders
Thisguideisintendedforthefollowingpersonnel;
• Engineersresponsibleforinstallation,wiring,andmaintenanceoftheequipment.
• Personnelresponsiblefornormaldailyoperationoftheequipment.
1. Safety Precautions
Thefollowingsymbolis usedonthe instrument.Itindicatesthepossibilityofinjury
totheuserordamagetotheinstrument,andsigniesthattheusermustrefertothe
operationguideoruser’smanualforspecialinstructions.Thesamesymbolisused
intheoperationguideanduser’smanualonpagesthat theuserneedstorefer to,
togetherwiththeterm“WARNING”or“CAUTION.”
WARNING
Calls attention to actions or conditions that could cause serious
or fatal injury to the user, and indicates precautions that should be
taken to prevent such occurrences.
CAUTION
Calls attention to actions or conditions that could cause injury to
the user or damage to the instrument or property and indicates pre-
cautions that should be taken to prevent such occurrences.
AC
AC/DC
Theequipmentwhollyprotectedbydoubleinsulationorreinforcedinsulation.
Functionalgroundingterminals
  (Donotusethisterminalasaprotectivegroundingterminal).
Note
Identiesimportantinformationrequiredtooperatetheinstrument.
■Warning and Disclaimer
(1) YOKOGAWA makesno warrantiesregardingthe productexceptthosestated in
theWARRANTYthatisprovidedseparately.
(2) Theproductisprovidedonan"asis"basis.YOKOGAWAassumesnoliabilityto
anypersonorentityfor anylossordamage, directorindirect,arising fromthe
use of the product or from any unpredictable defect of the product.
■ Safety,Protection,andModicationoftheProduct
(1)Inorder toprotectthe systemcontrolledbythisproductandthe productitself,
andtoensuresafe operation,observethesafetyprecautionsdescribedinthe
operationguide.Useoftheinstrumentin amannernot prescribedhereinmay
compromise the product's functions and the protection features inherent in the
device.Weassumenoliabilityforsafety,orresponsibilityfortheproduct'squality,
performanceorfunctionalityshouldusersfailtoobservetheseinstructionswhen
operatingtheproduct.
(2)Installation ofprotectionand/or safetycircuitswithrespect toalightning
protector;protectiveequipmentforthesystemcontrolledbytheproductandthe
productitself;foolprooforfail-safedesignofaprocessorlineusingthesystem
controlledbytheproductortheproductitself;and/orthedesignandinstallation
ofotherprotectiveandsafetycircuitsaretobeappropriatelyimplementedasthe
customer deems necessary.
(3) Be sureto usethe spare partsapproved byYOKOGAWAwhen replacingparts
or consumables.
(4) This productis notdesigned or manufacturedto be usedin criticalapplications
thatdirectlyaffectorthreatenhumanlives.Such applicationsincludenuclear
powerequipment,devicesusingradioactivity,railwayfacilities, aviation
equipment,airnavigationfacilities,aviationfacilities, andmedicalequipment.
Ifsoused,it istheuser’sresponsibilityto includeinthe systemadditional
equipmentanddevicesthatensurepersonnelsafety.
(5) Modicationoftheproductisstrictlyprohibited.
(6)
Thisproductisintendedtobehandledbyskilled/trainedpersonnelforelectricdevices.
(7)Thisproductis ULRecognizedComponent. Inordertocomply withUL
standards,end-productsarenecessaryto bedesignedby thosewhohave
knowledgeoftherequirements.
WARNING
l
Power Supply
Ensure that the instrument’s supply voltage matches the voltage
of the power supply before turning ON the power.
lDo Not Use in an Explosive Atmosphere
Do not operate the instrument in locations with combustible
or explosive gases or steam. Operation in such environments
constitutes an extreme safety hazard. Use of the instrument in
environments with high concentrations of corrosive gas (H2S,
SOX, etc.) for extended periods of time may cause a failure.
lDo Not Remove Internal Unit
The internal unit should not be removed by anyone other than
YOKOGAWA's service personnel. There are dangerous high voltage
parts inside. Additionally, do not replace the fuse by yourself.
lDamage to the Protective Construction
Operation of the instrument in a manner not specified in the
operation guide may damage its protective construction.
CAUTION
This instrument is an EMC class A product. In a domestic environ-
ment this product may cause radio interference in which case the
user needs to take adequate measures.
2. ModelandSu󰀩xCodes
■UT55A «Standard Code Model»
Model Su󰀩xcode Option
code Description
UT55A /MDL
(Required)
DigitalIndicatingController(Powersupply:100-240
VAC)(providedwithretransmissionoutputor15V
DClooppowersupply,3DIs,and3DOs)(*4)
Type1:
Basic
control
-0 Standard type
-2 Heating/coolingtype
Type2:
Functions
0None
2
Remote(1additionalaux.analog)input,
1additionalDI,andRS-485communication
(Max.19.2kpbs,2-wire/4-wire)(*1)
35additionalDIsand5additionalDOs
4
Remote(1additionalaux.analog)inputand1additionalDI
5Remote(1additionalaux.analog)input,6additional
DIs,and5additionalDOs
73additionalaux.analoginputsand3additionalDIs
Type3:Open
networks
0None
1
RS-485communication(Max.38.4kbps,2-wire/4-wire)
2
Ethernetcommunication(withserialgatewayfunction)
3
CC-Linkcommunication(withModbusmasterfunction)
4
PROFIBUS-DPcommunication(withModbusmasterfunction)
5
DeviceNetcommunication(withModbusmasterfunction)
Fixedcode -1
Temperatureunit:degC&degF
Casecolor 1Black(Lightcharcoalgray)
Fixedcode -00 Always"-00"(forstandardcodemodel)
Option codes
/MDL
(Required)
MountonDINrail(withoutthedisplaypartsand
keys)
/LP 24VDClooppowersupply(*2)
/DC Powersupply24VAC/DC
/CT Coating(*3)
*1:
Whenthe/LPoptionisspecified,theRS-485communicationoftheType2code“2”is2-wiresystem.
*2: The/MDLoptionand/LPoptioncanbespecifiedinthecombinationofType2code(anyof“0”,
“2”,“3”,or“4”)andType3code“1”.
*3: Whenthe/CToptionisspecified,theUT55Adoesnotconformtothesafetystandards(UL
andCSA)andCEmarking(Productswith/CToptionarenotintendedforEEA-market).
*4: UT55Ahasapanelmounttype(withoutoption/MDL).PleaseseetheOperationGuide(IM
05P01C31-11EN).
■UT52A «Standard Code Model»
Model Su󰀩xcode Option
code Description
UT52A /MDL
(Required)
DigitalIndicatingController(Powersupply:100-240
VAC)(providedwithretransmissionoutputor15V
DClooppowersupply,3DIs,and3DOs)(*3)
Type1:
Basic
control
-0 Standard type
Type2:
Functions
0None
1
Remote(1additionalaux.analog)input,1additional
DI,andRS-485communication(Max.38.4kbps,
2-wire)
Type3:
Open networks
0None
3
CC-Linkcommunication(withModbusmasterfunction)
Fixedcode -1
Temperatureunit:degC&degF
Casecolor 1Black(Lightcharcoalgray)
Fixedcode -00 Always"-00"(forstandardcodemodel)
Option codes
/MDL
(Required)
MountonDINrail(withoutthedisplaypartsand
keys)(*1)
/DC Powersupply24VAC/DC
/CT Coating(*2)
*1: Whenthe/MDLoptionisspecified,themodelandthesuffixcodesareasfollows:
 UT52A-010-11-00/x/MDL,UT52A-003-11-00/x/MDL
*2: Whenthe/CToptionisspecified,theUT52Adoesnotconformtothesafetystandards(UL
andCSA)andCEmarking(Productswith/CToptionarenotintendedforEEA-market).
*3: UT52Ahasapanelmounttype(withoutoption/MDL).PleaseseetheOperationGuide(IM
05P01C31-11EN).
■CustomizedProduct
 Forcustomizedproduct,theproductisidentiedbytheoptioncodeof/S#(where‘#’
isanumber).
 Contactyoursupplier incaseyour instrumenthasoption/S#,andyou arenot
inthepossessionof FX1-[Modelcode]-S#or IM[Modelcode]-S#(where[Model
code]means,forexample,UT55A).
■Accessories (sold separately)
Thefollowingisanaccessorysoldseparately.
• LL50AParameterSettingSoftware
Model Su󰀩xcode Description
LL50A -00 ParameterSettingSoftware
• ExternalPrecisionResistor
Model Su󰀩xcode Description
X010 SeetheGeneralSpecications(*) ResistanceModule
 *:Necessarytoinputthecurrentsignaltothevoltageinputterminal.
• TerminalCover
 ForUT55A/MDL:ModelUTAP001;ForUT52A/MDL:ModelUTAP002
• Manuals
 *Manualscanbedownloadedfromawebsite.URL:http://www.yokogawa.com/ns/ut/im/
• Brackets
 Partnumber:L4502TP(2pcsforupperandlowersides)
•Wallmountbracket
 ForUT52A/MDL:ModelUTAP005
3. How to Install
■Installation Location
Theinstrumentshouldbe installedinindoor locationsmeetingthe following
conditions:
• Instrumented enclosure
 Thisinstrumentisdesigned tobemountedin aninstrumentedenclosure. Mount
theinstrumentinalocationwhereitsterminalswillnotinadvertentlybetouched.
Be sure to mount the instrument in an enclosure with a door.
• Well ventilated locations
 Mounttheinstrumentinwellventilatedlocationstopreventtheinstrument’sinter-
naltemperaturefromrising.
 However,makesurethattheterminalportionsarenotexposedtowind.Exposure
to wind may cause the temperature sensor accuracy to deteriorate. To mount mul-
tipleindicatingcontrollers,see theexternaldimensions whichfollow.Ifmounting
otherinstrumentsadjacent totheinstrument, complywith theseexternaldimen-
sionstoprovidesu󰀩cientclearancebetweentheinstruments.
• Locations with little mechanical vibration
 Installtheinstrumentinalocationsubjecttolittlemechanicalvibration.
• Horizontal location
 Mounttheinstrumenthorizontallyandensurethatitislevel,withnoinclinationto
therightorleft.
Note
Iftheinstrumentismovedfrom alocationwith lowtemperatureand lowhumidity
toaplacewithhigh temperatureandhighhumidity,orifthetemperaturechanges
rapidly,condensationwill result.Moreover,in thecaseof thermocoupleinputs,
measurementerrorswillresult.Toavoidsuchasituation,leavetheinstrumentinthe
newenvironmentunderambientconditionsformorethan1hourpriortousingit.
Donotmounttheinstrumentinthefollowinglocations:
• Outdoors
• Locations subject to direct sunlight or close to a heater
Install the instrument in a location with stable temperatures that remain close to an
averagetemperatureof23°C.Donotmountitinlocationssubjecttodirectsunlight
orclosetoaheater.Doingsoadverselya󰀨ectstheinstrument.
• Locations with substantial amounts of oily fumes, steam, moisture, dust, or
corrosive gases
 Thepresenceof oilyfumes,steam, moisture,dust,or corrosivegases adversely
a󰀨ectstheinstrument.Donotmounttheinstrumentinlocationssubjecttoanyof
these substances.
• Areasnearelectromagneticeldgeneratingsources
 Donotplacemagnetsortoolsthatgeneratemagnetismneartheinstrument.Ifthe
instrumentisusedinlocations closetoastrong electromagneticeldgenerating
source,themagneticeldmaycausemeasurementerrors.
• Areasclosetoammablearticles
 Absolutelydonotplace theinstrumentdirectlyon am-
mablesurfaces.Ifsuch acircumstanceis unavoidable
andtheinstrumentmustbeplacedclosetoaammable
item,provideashieldforitmadeof1.43mmthickplated
steel or 1.6 mm thick unplated steel with a space of at
least150mmbetweenitandtheinstrumentonthetop,
bottom,andsides.
• Areas subject to being splashed with water
WARNING
Be sure to turn OFF the power supply to the controller before in-
stalling it on the enclosure to avoid an electric shock.
www.yokogawa.com/ns
YOKOGAWA ELECTRIC CORPORATION
Network Solutions Business Division
2-9-32, Naka-cho Musashino-shi, Tokyo 180-8750 JAPAN
YOKOGAWA CORPORATION OF AMERICA
Head office and for product sales
2 Dart Road, Newnan, Georgia 30265, USA
YOKOGAWA EUROPE B.V.
Headquarters
Euroweg 2, 3825 HD Amersfoort, THE NETHERLANDS
All Rights Reserved, Copyright © 2015 Yokogawa Electric Corporation
150 mm150 mm
150 mm
150 mm
Operation
Guide
IM 05P01C81-11EN
UT55A/MDL, UT52A/MDL
Digital Indicating Controller (DIN Rail Mounting Type)
Operation Guide for Single-loop Control
This operation guide describes installation, wiring, and other tasks required to make the
controller ready for operation.
4th Edition: Mar. 2018
For details of the each function, refer to the electronic manual. Manuals can be
downloaded or viewed at the following URL.
Functional
Enhancement
http://www.yokogawa.com/ns/ut/im/
«Standard Code Model»
■Protection of Environment
Waste Electrical and Electronic Equipment (WEEE), Directive
ThisisanexplanationofhowtodisposeofthisproductbasedonWasteElectrical
andElectronicEquipment(WEEE),Directive.ThisdirectiveisonlyvalidintheEU.
● Marking
ThisproductcomplieswiththeWEEEDirectivemarking
requirement.Thismarkingindicatesthatyoumustnotdiscard
thiselectrical/electronicproductindomestichouseholdwaste.
● ProductCategory
WithreferencetotheequipmenttypesintheWEEEdirective,
thisproductisclassiedasa“Smallequipment”product.
Donot dispose in domestichouseholdwaste. When disposing
products in the EU, contact your localYokogawa Europe B.V.
o󰀩ce.
IM 05P01C81-11EN page 2/6
■Mounting on a DIN Rail
InserttheDINrailintothetopareaofDINrailgroove(attwolocations)ontherear
panel,andsecureinplacewiththebottomslidelock.
DIN rail
DIN rail
Slide lock
UT55A/MDL: 2, UT52A/MDL: 1
Fit into here
Push
4. HardwareSpecications
WARNING
This instrument is for Measurement Category No.1.
Do not use it for measurements in locations falling under Measure-
ment Categories No.2, No.3, and No.4.
Internal Wiring
Outlet
Entrance
IV
Cable
III T
O( I )
II
Category IEC/EN/CSA/UL
61010-1 EN 61010-2-030 Remarks
No.1 Measurement
CategoryI O(Other) For measurements performed on circuits not direct-
lyconnectedtoMAINS.
No.2 Measurement
CategoryII
Measurement
CategoryII
For measurements performed on circuits directly
connectedtothelow-voltageinstallation.
No.3 Measurement
CategoryIII
Measurement
CategoryIII
Formeasurementsperformedinthebuildinginstal-
lation.
No.4 Measurement
CategoryIV
Measurement
CategoryIV
For measurements performed at the source of the
low-voltageinstallation.
■ InputSpecications
●UniversalInput(Equippedasstandard)
• Numberofinputs:1
• Inputtype,instrumentrange,andmeasurementaccuracy:Seethetablebelow,
Input Type Instrument Range Accuracy
ºC ºF
Thermo-
couple
K
-270.0to1370.0ºC -450.0to2500.0ºF ±0.1%ofinstrumentrange±1digitfor
0°Cormore
±0.2%ofinstrumentrange±1digitfor
lessthan0°C
±2%ofinstrumentrange±1digitfor
lessthan-200.0°CofthermocoupleK
±1%ofinstrumentrange±1digitfor
lessthan-200.0°CofthermocoupleT
-270.0to1000.0ºC -450.0to2300.0ºF
-200.0to500.0ºC -200.0to1000.0ºF
J-200.0to1200.0ºC -300.0to2300.0ºF
T
-270.0to400.0ºC -450.0to750.0ºF
0.0to400.0ºC -200.0to750.0ºF
B0.0to1800.0ºC 32to3300ºF
±0.15%ofinstrumentrange±1digit
for400°Cormore
±5%ofinstrumentrange±1digitfor
lessthan400°C
S0.0to1700.0ºC 32to3100ºF ±0.15%ofinstrumentrange±1digit
R 0.0to1700.0ºC 32to3100ºF
N -200.0to1300.0ºC -300.0to2400.0ºF
±0.1%ofinstrumentrange±1digit
±0.25%ofinstrumentrange±1digit
forlessthan0°C
E -270.0to1000.0ºC -450.0to1800.0ºF ±0.1%ofinstrumentrange±1digitfor
0°Cormore
±0.2%ofinstrumentrange±1digitfor
lessthan0°C
±1.5%ofinstrumentrange±1digitfor
lessthan-200.0°CofthermocoupleE.
L -200.0to900.0ºC -300.0to1600.0ºF
U
-200.0to400.0ºC -300.0to750.0ºF
0.0to400.0ºC -200.0to1000.0ºF
W 0.0to2300.0ºC 32to4200ºF ±0.2%ofinstrumentrange±1digit
(Note2)
Platinel 2 0.0to1390.0ºC 32.0to2500.0ºF ±0.1%ofinstrumentrange±1digit
PR20-40 0.0to1900.0ºC 32to3400ºF
±0.5%ofinstrumentrange±1digitfor
800°Cormore
Accuracyisnotguaranteedforless
than800°C.
W97Re3-
W75Re25 0.0to2000.0ºC 32to3600ºF ±0.2%ofinstrumentrange±1digit
RTD
JPt100 -200.0to500.0ºC -300.0to1000.0ºF ±0.1%ofinstrumentrange±1digit
(Note1)
-150.00to150.00ºC -200.0to300.0ºF ±0.1%ofinstrumentrange±1digit
Pt100
-200.0to850.0ºC -300.0to1560.0ºF ±0.1%ofinstrumentrange±1digit
(Note1)
-200.0to500.0ºC -300.0to1000.0ºF
-150.00to150.00ºC -200.0to300.0ºF ±0.1%ofinstrumentrange±1digit
Standardsignal
0.400to2.000V
±0.1%ofinstrumentrange±1digit
1.000to5.000V
4.00to20.00mA
DCvoltage/current
0.000to2.000V
0.00to10.00V
0.00to20.00mA
-10.00to20.00mV
0.0to100.0mV
Theaccuracyisthatinthestandardoperatingconditions:23±2°C,55±10%RH,andpowerfrequencyat50/60Hz.
Note1: ±0.3°C±1digitintherangebetween0and100°C,±0.5°C±1digitintherangebetween
-100and200°C.
Note2: W:W-5%Re/W-26%Re(HoskinsMfg.Co.).ASTME988
•Inputsampling(control)period:Selectfrom50,100,and200ms
•Burnoutdetection:
 FunctionsatTC,RTD,andstandardsignal.
 Upscale,downscale,ando󰀨canbespecied.
 Forstandardsignal,burnoutisdeterminedtohaveoccurredifitis0.1Vor0.4mA
or less.
•Inputbiascurrent:0.05µA(forTCorRTD)
•Measuredcurrent(RTD):About0.16mA
•Inputresistance:
 TCormVinput:1MΩormore
 Vinput:About1MΩ
 mAinput:About250Ω
•Allowablesignalsourceresistance:
 TCormVinput:250Ωorless
 E󰀨ectsofsignalsourceresistance:0.1µV/Ωorless
 DCvoltageinput:2kΩorless
 E󰀨ectsofsignalsourceresistance:About0.01%/100Ω
• Allowablewiringresistance:
 RTDinput: Max.150Ω/wire (Theconductor resistancebetween thethreewires
shallbeequal.)
 Wiringresistancee󰀨ect:±0.1ºC/10Ω
• Allowableinputvoltage/current:
 TC,mV,mAandRTDinput:±10VDC
 Vinput:±20VDC
 mAinput:±40mA
• Noiserejectionratio:
 Normalmode:40dBormore(at50/60Hz)
 Commonmode:120dBormore(at50/60Hz)
 For100-240VAC,thepowerfrequencycanbesetmanually.Automaticdetection
isalsoavailable.
 For24VAC/DC,thepowerfrequencycanbesetmanually.
• Referencejunctioncompensationerror:
 ±1.0ºC(15to35ºC)
 ±1.5ºC(-10to15ºCand35to50ºC)
• Applicablestandards:JIS/IEC/DIN(ITS-90)forTCandRTD
●AuxiliaryAnalogInput
• Use:Remotesetpointsetting,externalcompensatinginput,auxiliaryinputforcom-
putation,etc.
• Numberofinputs:SeethetableofModelandSu󰀩xCodes.
• Inputtype,instrumentrange,andmeasurementaccuracy:Seethetablebelow.
Input Type Instrument Range Accuracy
Standardsignal 0.400to2.000V ±0.2%ofinstrumentrange±1digit
1.000to5.000V ±0.1%ofinstrumentrange±1digit
DCvoltage 0.000to2.000V ±0.2%ofinstrumentrange±1digit
0.00to10.00V ±0.1%ofinstrumentrange±1digit
DCvoltage
forhigh-input
impedance 0.000to1.250V ±0.1%ofinstrumentrange±1digit
• Inputsampling(control)period:Sameasuniversalinput
• Inputresistance:About1MΩ
 However,10MΩormoreforDCvoltageforhigh-inputimpedancerange
•Burnoutdetection:Functionsatstandardsignal
 Burnoutisdeterminedtohaveoccurredifitis0.1Vorless.
●RemoteInputwithDirectInput
• Numberofinputs:SeethetableofModelandSu󰀩xCodes.
• Inputtype,instrumentrange,andmeasurementaccuracy:Sameasuniversalinput
exceptthetablebelow.
Input Type Instrument Range Accuracy
°C °F
4-wireRTD
JPt100 -200.0to500.0°C -300.0to1000.0°F ±0.5°C±1digit
-150.00to150.00°C -200.0to300.0°F ±0.2°C±1digit
Pt100
-200.0to850.0°C -300.0to1560.0°F ±0.1%ofinstrumentrange±1
digit(Note1)
-200.0to500.0°C -300.0to1000.0°F ±0.5°C±1digit
-150.00to150.00°C -200.0to300.0°F ±0.2°C±1digit
Note1: ±0.5°C±1digitintherangebetween-200.0and500.0°C/-300.0and1000.0°F.
• Inputsampling(control)period:Sameasuniversalinput
•Burnoutdetection:Sameasuniversalinput
■ ContactInputSpecications
• Numberofinputs:SeethetableofModelandSu󰀩xCodes.
• Inputtype:No-voltagecontactinputortransistorcontactinput
• Inputcontactrating:12VDC,10mAormore
 Useacontactwithaminimumon-currentof1mAorless.
• ON/OFFdetection:
 No-voltagecontactinput:
 Contactresistanceof1kΩorlessisdeterminedas“ON”andcontactresistance
of50kΩormoreas“OFF.”
 Transistorcontactinput:
 Inputvoltageof2Vorlessisdeterminedas“ON”andleakagecurrentmustnot
exceed100µAwhen“OFF.”
• Minimumstatusdetectionholdtime:Controlperiod+50ms
• Use:SPswitch,operationmodeswitch,andeventinput
■ AnalogOutputSpecications
• Numberofoutputs:
 Controloutput:1
 Cooling-sidecontroloutputofHeating/coolingtype:1
• Outputtype:Currentoutputorvoltagepulseoutput
• Currentoutput:4to20mADCor0to20mADC/loadresistanceof600Ωorless
• Currentoutputaccuracy:±0.1%ofspan(±5%ofspanfor1mAorless)
 Theaccuracyis thatinthe standardoperatingconditions: 23±2°C,55±10%RH,
andpowerfrequencyat50/60Hz.
• Voltagepulseoutput:
 Use:Timeproportionaloutput
 On-voltage:12Vormore/loadresistanceof600Ωormore
 O󰀨-voltage:0.1VDCorless
 Timeresolution:10msor0.1%ofoutput,whicheverislarger
■ RetransmissionOutputSpecications
• Numberofoutputs:Retransmissionoutput;1, sharedwith15 VDCloop power
supply
• Currentoutput:4to20mADCor0to20mADC/loadresistanceof600Ωorless
• Currentoutputaccuracy (conversionaccuracyfrom PVdisplayon thesetscale):
±0.1%ofspan(±5%ofspanfor1mAorless)
 Theaccuracyisthatinthestandardoperatingconditions:23±2°C,55±10%RH,
 andpowerfrequencyat50/60Hz.
 Thisisnotconversion accuracythroughinput andoutputbut theperformanceof
transmission output itself.
■External Dimensions
●UT55A/MDL
37(1.46)
96(3.78)
20(0.79)
100(3.94)
Note:
Trigonometry
General tolerance = ±(JIS B 0401-1998 tolerance class IT18)/2
Unit: mm(inch)
60(2.36)
DIN rail
TH35-75A
Cable for LL50
Minimum cable curvature: R40 (1.57)
4.3(0.17)
4(0.16)
90 (3.54) min.
(required for removing the
instrument from the DIN rail)
120 (4.72) min.
(required for inserting/removing the cable for LL50A)
91.6(3.61)
114(4.49)
100(3.94)
94.6(3.72)
●UT52A/MDL
15(0.59)
48.2(1.90)
20(0.79)
100(3.94)
Unit: mm(inch)
60(2.36)
DIN rail
TH35-75A
Cable for LL50
4.3(0.17)
4(0.16)
91.6(3.61)
114(4.49)
100(3.94)
94.6(3.72)
Note:
Trigonometry
General tolerance = ±(JIS B 0401-1998 tolerance class IT18)/2
Minimum cable curvature: R40 (1.57)
90 (3.54) min.
(required for removing the
instrument from the DIN rail)
120 (4.72) min.
(required for inserting/removing the cable for LL50A)
CAUTION
Make sure that foreign materials do not enter the inside of the
instrument through the case’s slit holes.
■Removing from the DIN Rail
Insertaat-bladescrewdriver(guideline:100 mmshaftlength, 6mmblade width,
0.8mmbladethickness)intothebottomslidelockholeandpulldowntoreleasethe
slidelock.OntheUT55A/MDL, therearetwoslidelocks.Releasetheotherslide
lockafteryourelease therstslide lock.Whenbothslide locksareunlocked, the
instrumentcanberemovedfromtheDINrail.
DIN rail
Slide lock
UT55A/MDL: 2, UT52A/MDL: 1
Pull
Push up
DIN rail
IM 05P01C81-11EN page 3/6
■ 15VDCLoopPowerSupplySpecications
(Sharedwithretransmissionoutput)
• Powersupply:14.5to18.0VDC
• Maximumsupplycurrent:About21mA(withshort-circuitcurrentlimitingcircuit)
■ StepResponseTimeSpecications
Within500ms(whenthecontrolperiodis50msor100ms)
Within1s(whenthecontrolperiodis200ms)
(63%ofanalogoutputresponsetimewhenastepchangeof10to90%ofinputspan
isapplied)
■ RelayContactOutputSpecications
• Contacttypeandnumberofoutputs:
 Controloutput:contactpoint1c;1point
 Cooling-sidecontroloutput ofHeating/coolingtype: contactpoint1c; 1point(for
UT55Aonly)
 ForUT52A,contactpoint1a;2pointsforbothheatingandcoolingsides
 Alarmoutput:contactpoint1a;3points(commonisindependent)
• Contactrating:
 Contactpoint1c(controloutput):250VAC,3Aor30VDC,3A(resistanceload)
 Contactpoint1a(controloutput):240VAC,3Aor30VDC,3A(resistanceload)(for
UT52Aonly)
 Contactpoint1a(alarmoutput):240VAC,1Aor30VDC,1A(resistanceload)
• Use:Timeproportionaloutput,alarmoutput,FAILoutput,etc.
• Timeresolutionofcontroloutput:10msor0.1%ofoutput,whicheverislarger
Note:Thecontroloutputshouldalwaysbeusedwithaloadof10mAormore.
 Thealarmoutputshouldalwaysbeusedwithaloadof1mAormore.
■ TransistorContactOutputSpecications
• Numberofoutputs:SeethetableofModelandSu󰀩xCodes.
• Outputtype:Opencollector(SINKcurrent)
• Outputcontactrating:Max.24VDC,50mA
• Outputtimeresolution:Min.50ms
• Use:Alarmoutput,FAILoutput,etc.
■ 24VDCLoopPowerSupplySpecications
• Use:Powerissuppliedtoa2-wiretransmitter.
• Powersupply:21.6to28.0VDC
• Ratedcurrent:4to20mADC
• Maximumsupplycurrent:About30mA(withshort-circuitcurrentlimitingcircuit.)
■ MaintenacePortSpecications
ThemaintenanceportisusedtoconnectadedicatedcablewhenusingtheLL50A
ParameterSettingSoftware (soldseparately).Throughthisport, youcanset
controllerparameters,downloadladderprograms,andsoon.
Fordetails,seetheLL50AUser’sManual(IM05P05A01-02EN).
Dedicated cable
LL50A Parameter Setting Software
To USB terminal
Note
UseLL50Awiththecontrollerturnedon.(Thededicatedcablemustbeconnected.
LL50ALight-loaderadaptercannotbeused.)
ThemaintenanceportisnotisolatedfromthePVinputterminal.Usetheportonlyfor
maintenancepurposes,suchasforsettingthecontrollerparameters.
■ SafetyandEMCStandards
• Safety:
 CompliantwithIEC/EN61010-1(CE),IEC/EN61010-2-201(CE),IEC/EN61010-
2-030(CE),approvedbyCAN/CSAC22.2No.61010-1(CSA),approvedbyUL
61010-1.
 Installationcategory:II
 Pollutiondegree:2
 Measurementcategory:I(CATI)(UL,CSA)
O(Other)(CE)
 Ratedmeasurementinputvoltage:Max.10VDC
 Ratedtransientovervoltage:1500V(*)
 *ThisisareferencesafetystandardvalueformeasurementcategoryIofCSA/UL61010-
1,andformeasurementcategoryOofIEC/EN61010-2-030.Thisvalueisnotnecessarilya
guaranteeofinstrumentperformance.
• EMCstandards:
 CompliantwithCEmarking
 EN61326-1ClassA,Table2(Foruseinindustriallocations),
 EN61326-2-3
 *Theinstrumentcontinuestooperateatameasurementaccuracyofwithin±20%ofthe
rangeduringtesting.
 EN55011ClassA,Group1
 EN61000-3-2ClassA
 EN61000-3-3
 EMCRegulatoryArrangementinAustraliaandNewZealand(forallmodelinclud-
ingLL50A)
 EN55011ClassA,Group1
• KCmarking:
 Electromagneticwaveinterference preventionstandard,electromagnetic wave
protection standard compliance
■ Construction,Installation,andWiring
• Construction:DINrailmountingtype
• Material:Polycarbonate(Flameretardancy:UL94V-0)
 DINrailmountingbracketmaterial:Panelsteelsheet
• Casecolor:Black(Lightcharcoalgray)
• Weight:1kgorless
• Externaldimensions(mm):
 UT55A/MDL:96(width)x114(height)x100(depth)
 UT52A/MDL:48.2(width)x114(height)x100(depth)
• CompatibleDINrails:TH35-7.5Fe,TH35-7.5Aℓ,JISC2812
•
Mountingposition:Horizontal.
• Wiring:M3screwterminalwithsquarewasher(forsignalwiringandpowerwiring)
■ PowerSupplySpecicationsandIsolation
• Powersupply:
 Ratedvoltage:100-240VAC(+10%/-15%),50/60Hz
24VAC/DC(+10%/-15%)(for/DCoption)
• Powerconsumption:UT55A:18VA(DC:9VA,AC:14VAif/DCoptionisspecied)
UT52A:15VA(DC:7VA,AC:11VAif/DCoptionisspecied)
• Databackup:Nonvolatilememory
• Powerholduptime:20ms(for100VACdrive)
• Withstandingvoltage
Betweenprimaryterminalsandsecondaryterminals:2300VACfor1minute(UL,CSA)
 Betweenprimaryterminalsandsecondaryterminals:3000VACfor1minute(CE)
 Betweenprimaryterminals:1500VACfor1minute
 Betweensecondaryterminals:500VACfor1minute
 (Primaryterminals:Power*andrelay outputterminals;Secondaryterminals:
AnalogI/Osignalterminals, contactinputterminals,communication terminals
andfunctionalgroundingterminals.)
 *:Powerterminalsfor24VAC/DCmodelsarethesecondaryterminals.
• Insulationresistance:Betweenpowersupply terminalsandagrounding terminal
20MΩormoreat500VDC
• Isolationspecications
PV (universal ) input terminals / maintenance port
Remote input terminals
Aux. analog (AIN2) input terminals
Control relay (contact point c) output terminals
Alarm-1 relay (contact point a) output terminals
Alarm-2 relay (contact point a) output terminals
Alarm-3 relay (contact point a) output terminals
Contact input terminals (all)
RS-485 communication terminals
Contact output (transistor) terminals
Ethernet communication terminal
PROFIBUS-DP/DeviceNet/CC-Link communication terminals
Control, retransmission (analog) output terminals
(not isolated between the analog output terminals)
Internal
circuits
Power
supply
The circuits divided by lines are insulated mutually.
Aux. analog (AIN4) input terminals
■ EnvironmentalConditions
Normal Operating Conditions:
• Ambienttemperature:-10to50°C
 IftheCC-Linkoptionisspecied,0to50°CforUT55A/MDL;0to40°CforUT52A/
MDL.(side-by-sidemounting: 0to50 °CforUT55A/MDL; 0to40 °CforUT52A/
MDL)
• Ambienthumidity:20to90%RH(nocondensationallowed)
• Magneticeld:400A/morless
• Continuousvibrationat5to9Hz:Halfamplitudeof1.5mmorless,1oct/minfor90
minuteseachinthethreeaxisdirections
 Continuousvibrationat9to150Hz:4.9m/s2orless,1oct/minfor90minuteseach
inthethreeaxisdirections
• Short-periodvibration:14.7m/s2,15secondsorless
• Shock:98m/s2orless,11ms
• Altitude:2000morlessabovesealevel
• Warm-uptime:30minutesormoreafterthepoweristurnedon
• Startuptime:Within10seconds
*:TheLCD(aliquidcrystaldisplay)isusedforadisplayportionofthisproduct.TheLCDhasa
characteristicthatthedisplayactionbecomeslateatthelowtemperature.However,the
control fuction is not affected.
Transportation and Storage Conditions:
• Temperature:-25to70ºC
• Temperaturechangerate:20ºC/horless
• Humidity:5to95%RH(nocondensationallowed)
E󰀨ectsofOperatingConditions
• E󰀨ectofambienttemperature:
 VoltageorTCinput:±1µV/ºCor±0.01%ofF.S./ºC,whicheverislarger
 Currentinput:±0.01%ofF.S./ºC
 RTDinput:±0.05ºC/ºC(ambienttemperature)orless
 Analogoutput:±0.02%ofF.S./ºCorless
• E󰀨ectofpowersupplyvoltageuctuation
 Analoginput:±0.05%ofF.S.orless
 Analogoutput:±0.05%ofF.S.orless
 (Eachwithinratedvoltagerange)
5. How to Connect Wires
WARNING
• Wiring work must be carried out by a person with basic electrical
knowledge and practical experience.
•
Be sure to turn OFF the power supply to the controller before
wiring to avoid an electric shock. Use a tester or similar device to
ensure that no power is being supplied to a cable to be connected.
• For the wiring cable, the temperature rating is 75 °C or more.
•
As a safety measure, always install a circuit breaker (an IEC
60947-compatibleproduct,5A,100 Vor220 VAC)inan easily
accessible location near the instrument. Moreover, provide indication
that the switch is a device for turning off the power to the instrument.
• Install the power cable keeping a distance of more than 1 cm
from other signal wires.
•
The power cable is required to meet the IEC standards concerned or
the requirements of the area in which the instrument is being installed.
• Wiring should be installed to conform to NEC (National Electrical
Code: ANSI/NFPA-70) or the wiring construction standards in
countries or regions where wiring will be installed.
• Since the insulation provided to each relay output terminal is
Functional insulation, provide Reinforced insulation to the
external of the device as necessary. (Refer to the drawing below.)
This product
Functional
insulation
A safety
voltage circuit
A safety
voltage circuit
This product
Reinforced insulation
Reinforced insulation
Functional
insulation
A hazardous
voltage circuit
A hazardous
voltage circuit
A safety
voltage circuit
A safety
voltage circuit
This product
Reinforced insulation
Reinforced insulation
Functional
insulation
A hazardous
voltage circuit
A hazardous
voltage circuit
A hazardous
voltage circuit
A hazardous
voltage circuit
CAUTION
• When connecting two or more crimp-on terminal lugs to the
single terminal block, bend the crimp-on terminal lugs before
tightening the screw.
• Note that the wiring of two or more crimp-on terminal lugs to the
single high-voltage terminal of the power supply and relay, etc.
does not comply with the safety standard.
CAUTION
• Provide electricity from a single-phase power supply. If the
power is noisy, install an isolation transformer on the primary
side, and use a line filter on the secondary side. When measures
against noise are taken, do not install the primary and secondary
power cables close to each other.
•
If there is a risk of external lightning surges, use a lightning arrester etc.
• For TC input, use shielded compensating lead wires for wiring.
For RTD input, use shielded wires that have low conductor
resistance and cause no significant differences in resistance
between the three wires.
• Since the control output relay has a life span (resistance load of
100,000 times), use the auxiliary relay to perform ON/OFF control.
• The use of inductance (L) loads such as auxiliary relays, motors
and solenoid valves causes malfunction or relay failure; always
insert a CR filter for use with alternating current or a diode for
use with direct current, as a spark-removal surge suppression
circuit, into the line in parallel with the load.
• After completing the wiring, the terminal cover is recommended
to use for the instrument.
● RecommendedCrimp-onTerminalLugs
(A)
(F)
(ød)
5.5
3.3
 Recommendedtighteningtorque:0.6N·m
 Applicablewiresize:Powersupplywiring1.25mm2or more
Applicable terminal lug Applicable wire size mm2(AWG#) (φd) (A) (F)
M3 0.25to1.65(22to16) 3.3 5.5 4.2
● CableSpecicationsandRecommendedCables
Purpose Name and Manufacturer
Powersupply,relaycontactoutputs 600VGradeheat-resistantPVCinsulatedwires,JISC
3317(HIV),0.9to2.0mm2
Thermocouple Shieldedcompensatingleadwires,JISC1610
Forthermocoupleinput(PVinputandremoteinputwithdirect
input),shieldedcompensatingleadwireofcross-sectionalarea
lessthanorequalto0.75mm2isrecommended.Ifthecross-
sectionalareaiswide,thereferencejunctioncompensation
errormaybelarge.
RTD Shieldedwires(three/fourconductors),UL2482(HitachiCable)
Othersignals(otherthancontactinput/output)
Shielded wires
Othersignals(contactinput/output)
Unshieldedwires
RS-485communication
Shielded wires
Ethernetcommunication
100BASE-TX(CAT-5)/10BASE-T
PROFIBUS-DPcommunication
DedicatedcableforPROFIBUS-DP(Shieldedtwo-wires)
DeviceNetcommunication
DedicatedcableforDeviceNet(Shieldedve-wires)
CC-Linkcommunication
DedicatedcableforCC-Link(Shieldedthree-wires)
PROFIBUS-DP/CC-LinkConnector(wiringside)(Partnumber:A1987JT)
DeviceNetConnector(wiringside)(Partnumber:L4502BW)
Recommendedtighteningtorque:0.5to0.6N·m
DC Relay Wiring
R
External DC power supply
Relay
UT55A, UT52A
UT’s contact
Diode
(Mount it directly
to the relay coil
terminal (socket).)
Relay
(Use one with a relay coil rating
less than the UT’s contact rating.)
AC Relay Wiring
UT55A, UT52A
R
UT’s contact
CR filter
(Mount it directly
to the relay coil
terminal (socket).)
External AC power supply
Relay
(Use one with a relay coil
rating less than the UT’s
contact rating.)
Transistor Output Wiring
power
+ –
UT
DO
Load
COM
IM 05P01C81-11EN page 4/6
6. Terminal Wiring Diagrams
CAUTION
• Do not use an unassigned terminal as the relay terminal.
• Donotuse a100-240VACpowersupply forthe24 VAC/DC
model; otherwise, the instrument will malfunction.
■ UT55A/MDL
E4-terminal area
E3-terminal area E2-terminal area
PV RET
OUT
DI
ALM
OUT
OUT2
E1-terminal area
Retransmission output
4-20 mA DC or
0-20 mA DC
15 V DC loop power supply
14.5-18.0 V DC
(Max. 21 mA DC)
+
-
+
-
Default: 4-20 mA DC
Default: PV
retransmission
Load resistance 600 Ωor less
Retransmission output
Current/voltage pulse output
0-20 mA DC,
4-20 mA DC,
Voltage pulse (12 V)
+
Retransmission output
+
-
Default: 4-20 mA DC
Default: Undefined
0-20 mA DC,
4-20 mA DC
Control output
PV input
TC input RTD input
Voltage (mV, V) input
A
+
-
+
-
Current (mA) input
+
-
B
b
(Suffix code: Type 1=-2)
(Suffix code: Type1=-0, -1 or -2)
(Suffix code:
Type1=-0 or -2)
(24 V AC/DC power supply: Option code /DC)
(Equipped as standard)
(Equipped
as standard)
(Equipped
as standard)
(Equipped as standard)
Power supply
Contact input
Contact rating: 12 V DC, 10 mA or more
External contact input
DI3
DI2
DI1
COM
AUTO when DI1=ON
MAN when DI1=OFF
STOP when DI2=ON
RUN when DI2=OFF
Common
DI3
DI2
DI1
COM
+5V
+5V
+5V
No-voltage
contact Transistor contact
Factory default: No function
UT UT
Control output
101
102
Relay contact output
103
NC
NO
COM
Contact rating: 250 V AC, 3 A
30 V DC, 3 A (resistance load)
Contact output
101
102
103
104
105
106
107
108
109
110
111
501
502
503
504
505
506
507
508
509
510
511
512
407
401
408
409
410
411
412
301
302
303
304
305
306
307
308
309
310
311
312
201
202
203
204
205
206
207
208
209
210
211
212
Cooling-side control output
Relay contact output
NC
NO
COM
Contact rating: 250 V AC, 3 A
30 V DC, 3 A (resistance load)
101
-112
501
-512
401
-412
301
-312
201
-212
External contact output (relay)
AL3
AL2
AL1
Relay contact rating: 240 V AC, 1 A
30 V DC, 1 A (resistance load)
Alarm-3 output
(PV high limit)
Alarm-2 output
( PV low limit)
Alarm-1 output
(PV high limit)
Common
Common
Common
UT
104
105
106
107
108
109
100-240 V AC power supply
N
L
Allowable range:
100-240 V AC (+10%/-15%)
(free voltage)
50/60 Hz shared
110
111
24 V AC/DC power supply
-
+
110
111
202
203
201
202
203
202
203
203
204
205
206
205
206
15 V DC loop power supply
14.5-18.0 V DC
(Max. 21 mA DC)
+
-
207
208
207
-208
207
208
209
210
211
212
209
210
211
212
507
508
509
OUT2
Current/voltage pulse output
0-20 mA DC,
4-20 mA DC,
Voltage pulse (12V)
+
-
Retransmission output
+
-
Default: 4-20 mA DC
Default: Undefined
0-20 mA DC,
4-20 mA DC
15 V DC loop power supply
14.5-18.0 V DC
(Max. 21 mA DC)
+
-
511
512
511
512
511
512
Factory default: PV input
type is undefined.
In Heating/cooling control,
relay contact output is
heating-side output.
Factory default: Control
output is relay.
Can be used for retransmission output or 15 V DC loop power supply when
current/voltage pulse output is not used for control output.
Current output range can be changed.
Factory default: Cooling-side control output is
relay.
Can be used for retransmission output or 15 V
DC loop power supply when current/voltage
pulse output is not used for control output.
Current output range can be changed.
Can be used for 15 V DC loop
power supply when not used for
retransmission output.
Function can be assigned to the terminals with no function.
112
112 112
N
L
Wiring direction
E1-Terminal Area
301-306 E2-Terminal Area
307-312
(Suffix code: Type 2=3)
Contact input
External contact input
DI11
DI12
DI13
DI14
DI15
COM
Common
DI11
DI12
COM
+5V
+5V
No-voltage contact
Transistor contact
Contact rating: 12 V DC, 10 mA or more
DI13 +5V
DI14 +5V
DI15 +5V
Factory default: No function
Factory default: No function
Factory default: No function
Factory default: No function
Factory default: No function
UT UT
301
302
303
304
305
306
301
302
303
304
305
306
Function can be assigned to the
terminals with no function.
DI
(Suffix code: Type 2=2, 4, 5, or 7)
Remote input
Default: 1-5 V DC
+
-
Remote input / Contact input
External contact input
DI16
COM
Common
DI16
COM
+5V
No-voltage contact
Transistor contact
Contact rating: 12 V DC, 10 mA or more
UT UT
REMOTE when DI16=ON
LOCAL when DI16=OFF
303
304
303
304
305
306
RSP
Specify within a
range of 1-5 V DC,
0-2 V DC,0-10 V DC
Contact output
External contact output
Transistor contact rating: 24 V DC, 50 mA
DO22
DO21
DO23
DO24
DO25
COM
Alarm 4 (PV low limit)
Common
UT
(Suffix code: Type 2=3 or 5)
307
308
309
310
311
312
Function can be assigned
to the terminals with no
function.
DO
Factory default: No function
Factory default: No function
Factory default: No function
Factory default: No function
(Suffix code: Type 2=7)
Aux. analog input
Default: 1-5 V DC
+
-
Aux. analog input / Contact input
External contact input
DI26
COM
Common
DI26
COM
+5V
No-voltage contact
Transistor contact
Contact rating: 12 V DC, 10 mA or more
Factory default: No function
UT UT
309
310
309
310
311
312
Aux. analog input can be used for
feedforward input in Single-loop control.
Function can be assigned
to the terminals with no
function.
AIN2
Specify within a
range of 1-5 V DC,
0-2 V DC,0-10 V DC
E4-terminal area
E3-terminal area
E2-terminal area
E1-terminal area
101
102
103
104
105
106
107
108
109
110
111
501
502
503
504
505
506
507
508
509
510
511
512
407
401
408
409
410
411
412
301
302
303
304
305
306
307
308
309
310
311
312
201
202
203
204
205
206
207
208
209
210
211
212
101
-112
501
-512
401
-412
301
-312
201
-212
112
E3-Terminal Area
401-412 E4-Terminal Area
501-506
(Suffix code: Type 3=2)
Ethernet communication (with gateway function)
10BASE-T/100BASE-TX
RJ45 connector
Color
Lit
Unlit
Amber
100M bps
10M bps
Green
Linked
Active
Link failure
Color
Lit
Blink
Unlit
Upper side LED (baud rate)
Lower side LED (link activity)
RS-485
RSB(+)
RSA(-)
SG
407
408
409
ETHR
RS-485
SDB(+)
SDA(-)
RDB(+)
RDA(-)
SG
RS
-
485
communication
(Suffix code: Type 3=1)
407
408
409
410
411
RS485
Contact input
External contact input
DI41
DI42
DI43
DI44
DI45
COM
DI41
DI42
COM
+5V
+5V
DI43 +5V
DI44 +5V
DI45 +5V
UT UT
(Suffix code: Type 2=5)
Common
No-voltage contact
Transistor contact
Contact rating: 12 V DC, 10 mA or more
Factory default: No function
Factory default: No function
Factory default: No function
Factory default: No function
Factory default: No function
501
502
503
504
505
506
501
502
503
504
505
506
Function can be assigned to the
terminals with no function.
DI
RS-485
SDB(+)
SDA(-)
RDB(+)
RDA(-)
SG
RS
-
485
communication
501
502
503
504
505
RS485
(Suffix code: Type 2=2
and without option code /LP)
RS-485
RSB(+)
RSA(-)
SG
RS
-
485 communication/24 V DC loop power supply
+
24 V DC loop power supply
21.6-28.0 V DC
(Max. 30 mA DC)
-
501
502
503
505
506
RS485/LPS24
(Suffix code: Type 2=2
and with option code /LP)
+
24 V DC loop power supply
21.6-28.0 V DC
(Max. 30 mA DC)
-
24 V DC loop power supply
505
506
LPS24
(Suffix code: Type 2=other than 2, 5, or 7
and with option code /LP)
Aux. analog input
Default: 1-5 V DC
+
-
Aux. analog input/Contact input
External contact input
DI46
COM
DI46
COM
+5V
UT UT
(Suffix code: Type 2=7)
Common
No-voltage contact
Transistor contact
Contact rating: 12 V DC, 10 mA or more
Factory default: No function
503
504
503
504
505
506
Function can be assigned to the
terminals with no function.
AIN4
Aux. analog input can be used for feedforward input in
Single-loop control and Single-loop position proportional
control.
Specify within a
range of 1-5 V DC,
0-2 V DC,0-10 V DC
PROFIBUS-DP communication (with Modbus master)
Pin
1
2
Signal name Description
VP
RxD/TxD-P
3RxD/TxD-N
4DGND
5SHIELD
+5V bus power
Data signal
(positive data receive/transmit)
Data signal
(negative data recive/transmit)
Signal ground
Shield ground
RS-485
RSB(+)
RSA(-)
SG
407
408
409
PROF
If the UT is located at
the end of a segment
for the PROFIBUS
communication wiring,
terminating resistors
are separately
needed.
These are to be
prepared by users.
(390 Ω: 2 pcs. 220 Ω:
1 pc., or an active
terminator.)
VP
RxD/TxD-P
Data
line
Data
line
390Ω
220Ω
390Ω
RxD/TxD-N
DGND
CHK
RDY
ERR
LED
CHK
(red)
RDY
(green)
Lit Unlit
ERR
(red)
User profile error Normal
Normal
Not connected, or
communication
failure (flashing)
Normal
Communicating
successfully
No power, or
Communication
failure
(Suffix code: Type 3=4)
1
2
3
4
5
(Suffix code: Type 3=3)
CC-Link communication (with Modbus master)
RS-485
RSB(+)
RSA(-)
SG
407
408
409
CC-L
If the UT is located at
the end of a segment
for the CC-Link
communication wiring,
terminating resistors
are separately needed.
These are to be
prepared by users.
(110 Ω: 1 pc.)
DA
DB
110Ω
LED
CHK
(red)
L ERR
(red)
L RUN
(green)
Lit Unlit
CHK
L RUN
L ERR
User profile error/
Address error Normal
Normal
Pin
1
2
Signal name Description
DA
DB
3DG
4
SLD
5
FG
RX/TX + signal
RX/TX - signal
Frame ground
RX/TX signal ground
Shield
Normal
Communicating successfully
Communication failure
(CRC error)
No carrier
detected/
Connection
timeout
1
2
3
4
5
(Suffix code: Type 3=5)
DeviceNet communication (with Modbus master)
RS-485
RSB(+)
RSA(-)
SG
407
408
409
DNET
If the UP is located at the
end of a segment for the
DeviceNet
communication wiring,
terminating resistors are
separately needed.
These are to be
prepared by users. (121
Ω: 1 pc.)
CAN_H
CAN_L
121Ω
LED
CHK
(red)
MNS
(green/
red)
Lit/flashing Unlit
User profile error Normal
Pin
1
2
Signal name Description
CAN_H
CAN_L
3
V+
4
V-5
DRAIN
RX/TX + signal
RX/TX - signal
Shield/Drain wire
DeviceNet power supply 24V
DeviceNet power supply common
Normal. Communicating
successfully (green, lit).
Not connected (green, flashing).
Critical link failure (red, lit).
Communication timeout (red,
flashing)
At power-on/Communication
faulted (green/red, flashing)
No electricity
CHK
MNS
1
2
3
4
5
IM 05P01C81-11EN page 5/6
■ UT52A/MDL
Current/voltage pulse output
0-20 mA DC,
4-20 mA DC,
Voltage pulse (12 V)
+
-
Retransmission output
+
-
Default: 4-20 mA DC
Default: Undefined
0-20 mA DC,
4-20 mA DC
Control output
Retransmission output
4-20 mA DC or
0-20 mA DC
15 V DC loop power supply
14.5-18.0 V DC
(Max. 21 mA DC)
+
-
+
-
Default: 4-20 mA DC
Default: PV retransmission
Load resistance 600 Ωor less
Retransmission output
(Equipped as standard)
PV input
TC input RTD input
Voltage (mV, V) input
A
+
-
+
-
Current (mA) input
+
-
B
b
(Equipped
as standard)
(Equipped
as standard)
(Equipped as standard)
Power supply
24 V AC/DC power supply
-
+
100-240 V AC
power supply
Allowable range:
100-240 V AC (+10%/-15%)
(free voltage)
50/60 Hz shared
N
L
Control output
Relay contact output
NC
NO
COM
Contact rating: 250 V AC, 3 A
30 V DC, 3 A (resistance load)
Contact output
External contact output (relay)
AL3
AL2
AL1
Relay contact rating: 240 V AC, 1 A
30 V DC, 1 A (resistance load)
Alarm-3 output
(PV high limit)
Alarm-2 output
(PV low limit)
Alarm-1 output
(PV high limit)
Common
Common
Common
UT
Contact input
Contact rating: 12 V DC, 10 mA or more
External contact input
DI3
DI2
DI1
COM
AUTO when DI1=ON
MAN when DI1=OFF
STOP when DI2=ON
RUN when DI2=OFF
Common
DI3
DI2
DI1
COM
+5V
+5V
+5V
No-voltage
contact
Transistor contact
Factory default: No function
UT UT
111
301
302
303
304
305
306
307
308
309
310
311
312
201
202
203
204
205
206
207
208
209
210
101
102
103
104
105
106
107
108
109
110
211
212
(24 V AC/DC power supply: Option code /DC)
E1-terminal area
101
-112
301
-312
201
-212
101
102
103
104
105
106
107
108
109
110
111
110
111
202
203
201
202
203
202
203
203
204
205
206
205
206
15 V DC loop power supply
14.5-18.0 V DC
(Max. 21 mA DC)
+
-
207
208
207
208
207
208
209
210
211
212
209
210
211
212
Factory default: Control output is relay.
Function can be assigned to the terminals with no function.
Can be used for retransmission output or 15 V DC loop power suppy when
current/voltage pulse output is not used for control output.
Current output range can be changed.
Can be used for 15 V DC loop
power supply when not used for
retransmission output.
PV RET
OUT
DI
ALM
OUT
Factory default:
PV input type is
undefined.
112
112 112
N
L
Wiring direction
E1-Terminal Area
301-312
(Suffix code: Type 2=1)
RS-485
RSB(+)
RSA(-)
SG
RS
-
485 communication / Remote input / Contact input
Remote input
Default: 1-5 V DC
+
-
External contact input
DI16
COM
Common
DI16
COM
+5V
No-voltage contact
Transistor contact
Contact rating: 12 V DC, 10m A or more
UT UT
REMOTE when DI16=ON
LOCAL when DI16=OFF
301
302
303
303
304
303
304
305
306
RSP/RS485
Specify within a
range of 1-5 V DC,
0-2 V DC,0-10 V DC
CC-Link communication (with Modbus master)
(Suffix code: Type 3=3)
FG:
Flame ground
SLD:
Shield
DG:
TX/RX signal ground
DB:
RX/TX signal
- signal
DA:
RX/TX signal
+ signal
CHK(red)
(Lit: User profile error/Adress error, Unlit: Normal)
L ERR(red)
(Lit: Communication failure(CRC error), Unlit: Normal)
L RUN(green)
(Lit: Normal, Unlit: No carrier detected/Communication timeout)
Not used
301
302
303
304
305
306
307
308
309
RS-485
RSB(+)
RSA(-)
SG
310
311
312
DB
DA
110Ω
CC-L
If the UT is located at the end of a
segment for the CC-Link
communication wiring,terminating
resistors are separately needed.
These are to be prepared by
users. (110 Ω: 1 pc.)
• AuthorisedRepresentativeintheEEA
 YokogawaEurope BV.(Address:Euroweg2, 3825HDAmersfoort,The
Netherlands)istheAuthorisedRepresentativeofYokogawaElectricCorporation
forthisProductintheEEA.
• Printed Manuals
Model Description
UT55A,UT52ADigitalIndicatingController(PanelMountingType)Operation
Guide «StandardCodeModel»
IM05P01C31-11EN
UT55A,UT52ADigitalIndicatingController(PanelMountingType)Operation
Guide «DetailedCodeModel»
IM05P01C31-15EN
UT55A/MDL,UT52A/MDLDigitalIndicatingController(DINRailMountingType)
Operation Guide «StandardCodeModel»
IM05P01C81-11EN
PrecautionsontheUseoftheUTAdvancedSeries IM05P01A01-11EN
UTAP005WallMoountBracketUser'sManual IM05P06A31-02Z1
• ElectronicManuals
 Youcandownloadthelatestmanualsfromthefollowingwebsite:
 URL:http://www.yokogawa.com/ns/ut/im/
Model Description
UT55A,UT52ADigitalIndicatingController(PanelMountingType)Operation
Guide «StandardCodeModel»
IM05P01C31-11EN
UT55A,UT52ADigitalIndicatingController(PanelMountingType)Operation
Guide «DetailedCodeModel»
IM05P01C31-15EN
UT55A/MDL,UT52A/MDLController(DINRailMountingType)OperationGuide
«StandardCodeModel»
IM05P01C81-11EN
UT55A/UT52ADigitalIndicatingControllerUser’sManual IM05P01C31-01EN
UTAdvancedSeriesCommunicationInterface(RS-485,Ethernet)User’sManual IM05P07A01-01EN
UTAdvancedSeriesCommunicationInterface(OpenNetwork)User’sManual IM05P07A01-02EN
LL50AParameterSettingSoftwareInstallationManual IM05P05A01-01EN
LL50AParameterSettingSoftwareUser’sManual IM05P05A01-02EN
PrecautionsontheUseoftheUTAdvancedSeries IM05P01A01-11EN
UTAP005WallMoountBracketUser'sManual IM05P06A31-02Z1
• GeneralSpecication
Model Description
UT55A,UT52ADigitalIndicatingController(PanelMountingType) GS05P01C31-01EN
UT55A/MDL,UT52A/MDLDigitalIndicatingController(DINRailMountingType) GS05P01C81-01EN
LL50AParameterSettingSoftware GS05P05A01-01EN
* Thelasttwocharactersofthemanualnumberandgeneralspecificationnumberindicatethe
languageinwhichthemanualiswritten.
IM 05P01C81-11EN page 6/6
7. Setup Procedure
Thefollowingflowchartshows thesetupprocedure forUT55A/MDLand UT52A/
MDL.
PerformsetupthroughcommunicationortheLL50AParameterSettingSoftware(sold
separately).
Install and wire a controller.
Monitoring and control of regular operations
Adjust PID using auto-tuning or manually for PID control.
(Set parameters through communication.)
Operation
NO
YES
PID tuning
Installation
and wiring
Power ON
Parameter
Settings
Parameter
Settings
Use LL50A
Software?
LL50A: Parameter setting software (sold
separately)
See the LL50A Parameter Setting Software
User’s Manual (IM 05P05A01-01EN).
Use LL50A with the controller turned on.
(The dedicated cable must be connected.
LL50A Light-loader adapter cannot be
used.)
The maintenance port is not isolated from
the PV input terminal. Use the port only for
maintenance purposes, such as for setting
the controller parameters.
To set parameters through
communication, you need to
create a program on the host
device side. For controller
parameter information (registers,
relays), see the following
manuals.
• For setup through RS485 serial
communication or Ethernet
communication, see the
UTAdvanced Series Communi-
cation Interface User’s Manual
(IM 05P07A01-01EN).
• For setup through an open
network, see the UTAdvanced
Series Communication
Interface (Open Network)
User’s Manual (IM 05P07A01-
02EN).
8. Operations
ThecontrollerstatuscanbeveriedwiththeLED.
Status LED Lit/Blinks Description
Normal Green Lit
Communicationerror Green Blinks Checkthecommunicationwiringandsettings.
Instrument failure Red Lit Parametererror/Hardwarefailure/Ladderprogram
corruption.
Input error Red Blinks Sensorburnout,inputover
Checktheinputwiringandsettings.
LED lamp
UT55A/MDL Front
(with terminal cover)
UT52A/MDL Front
(with terminal cover)
Checktheoperatingstatus(run/stop,auto/manual,remote/local,etc.)of the
controllerthroughcommunicationor theLL50AParameterSetting Software(sold
separately).
Fordetails,seethe (1)UT55A/UT52ADigitalIndicating ControllerUser’sManual
(IM05P01C31-01EN),(2)UTAdvanced SeriesCommunicationInterface(RS-485,
Ethernet)User’sManual(IM05P07A01-01EN),and(3)LL50AParameterSetting
SoftwareUser’sManual(IM05P05A01-02EN).
9. Troubleshooting
Ifaproblemappearstobecomplicated,contactoursalesrepresentatives.
Is the controller
defective?
Contact us for repair.
Problem solved.
The LED lamp
is unlit.
Yes
Yes
No
Yes
No
No
Yes
Check wiring of the
power terminals.
The LED
lamp is flashing
in red.
(I/O signal failure?)
The LED lamp is
lit in red.
Yes
No
Check the
supply voltage.
Check the
specifications and polarity
of connected devices .
Check the communication-
related parameters.
Check the specifications
of communication
devices.
Check the
communication wiring.
(Communication failure?)
Yes
Normal?
Check the specifications
of the controller.
Yes
No Correct?
Correct the error(s).
Check the I/O specifications
of the controller.
The LED
lamp is flashing
in green.
■Errors at Power On
Theerrorsshownbelowmay occurinthefault diagnosiswhenthepower isturnedon.(For detailsofSetpointdisplayand input/outputactionwheneach erroroccurs,seeUser’sManual (IM
05P01C31-01EN).)
YoucanviewthedetailsofeacherrorthroughcommunicationortheLL50AParameterSettingSoftware(soldseparately).(Viewontheregistermonitor.)
Fordetailsoneachregister,seetheUTAdvancedSeriesCommunicationInterface(RS485,Ethernet)User’sManual(IM05P07A01-01EN).
LED display Register that displays error details Error description Cause and diagnosis Remedy
Unlit —FaultyMCURAM/MCUROM MCURAM/MCUROMarefailed. Faulty.Contactusforrepair.
Red,lit
Setupparameter(PA.ER)
(Registerno.:2068)Bit0=1 System data error System data is corrupted. Faulty.Contactusforrepair.
Setupparameter(PA.ER)
(Registerno.:2068)Bit1=1 Calibrationvalueerror
Initializedtocalibrateddefaultvaluebecauseofcorrupted
factorydefaultvalue.
Faulty.Contactusforrepair.
Setupparameter(PA.ER)
(Registerno.:2068)Bit2=1
User(parameter)defaultvalue
error
Userparameteriscorrupted.
Initializedtofactorydefaultvalue. Checkandreconguretheinitializedsetting
parameters.Errorindicationiserasedwhenthe
poweristurnedonagain.
Setupparameter(PA.ER)
(Registerno.:2068)Bit4=1 Setup parameter error Setup parameter data is corrupted.
Initializedtouserdefaultvalue.
Setupparameter(PA.ER)
(Registerno.:2068)Bit5=1 Operation parameter error Operation parameter data is corrupted.
Initializedtouserdefaultvalue.
Setupparameter(PA.ER)
(Registerno.:2068)Bit8=1 FaultyFRAM
Datawriting(storing)toFRAMisimpossible.
Faulty.Contactusforrepair.
Setupparameter(OP.ER)
(Registerno.:2070)
E1-terminal:Bit0=1
E2-terminal:Bit1=1
E3-terminal:Bit2=1
E4-terminal:Bit4=1
Nonrespondinghardwareof
extendedfunction(E1toE4-
terminalareas)
Inconsistenceofsystemdataandhardwareofextended
function.
Nonrespondingcommunicationbetweenhardwareof
extendedfunction(E1toE4-terminalareas).
Faulty.
Contactusforrepair.
Setupparameter(LA.ER)
(Registerno.:2012)Bit0=1 Corruptedladderprogram Ladderprogramiscorrupted.
Operateswithoutladderprogram. Downloadtheladderprogramagain.
Green,blinks Setupparameter(OP.ER)
(Registerno.:2070)Bit10=1 Userproleerror Userproleiscorrupted. Downloadtheuserproleagain.
■Errors during Operation
Theerrorsshownbelowmayoccurduringoperation.(Forinput/outputactionwheneacherroroccurs,seeUser’sManual(IM05P01C31-01EN).)
YoucanviewthedetailsofeacherrorthroughcommunicationortheLL50AParameterSettingSoftware(soldseparately).(Viewontheregistermonitor.)
Fordetailsoneachregister,seetheUTAdvancedSeriesCommunicationInterface(RS485,Ethernet)User’sManual(IM05P07A01-01EN).
Status indicator
(Operation Display) Register that displays error details Error description Cause and diagnosis Remedy
Red,lit
Setupparameter(AD1.E)
(Registerno.:2001)
PVinput:Bit0=1
RSPinput:Bit1=1
AIN2input:Bit2=1
AIN4input:Bit4=1
AnaloginputterminalADCerror
•PVinput
•RSPinput(E1-terminalarea)
•AIN2input(E2-terminalarea)
•AIN4input(E4-terminalarea)
AnaloginputterminalADvalueerror Faulty.Contactusforrepair.
Setupparameter(AD1.E)
(Registerno.:2001)
PVinput:Bit5=1
RSPinput:Bit6=1
UniversalinputterminalRJCerror
•PVinput
•RSPinput(E1-terminalarea)
UniversalinputterminalRJCerror
Faulty.Contactusforrepair.
SettheparameterRJCtoOFFtoeraseerror
indication.
Red,blinks
Setupparameter(AD1.E)
(Registerno.:2001)
PVinput:Bit8=1
RSPinput:Bit9=1
AIN2input:Bit10=1
AIN4input:Bit12=1
Analoginputterminalburnouterror
•PVinput
•RSPinput(E1-terminalarea)
•AIN2input(E2-terminalarea)
•AIN4input(E4-terminalarea)
Analoginputterminalsensorburnout Checkwiringandsensor.
Errorindicationiserasedinnormaloperation.
Setup parameter
Loop-1(PV1.E)(Registerno.:2002)Bit0=1
Loop-2(PV2.E)(Registerno.:2018)Bit0=1
PVinputburnouterror(Loop1,
Loop2) BurnoutofanaloginputconnectedtoPV
Checkwiringandsensorofconnectedanalog
input terminals.
Errorindicationiserasedinnormaloperation.
Setup parameter
Loop-1(PV1.E)(Registerno.:2002)
Over-scale:Bit4=1
Under-scale:Bit5=1
Loop-2(PV2.E)(Registerno.:2018)
Over-scale:Bit4=1
Under-scale:Bit5=1
PVinputover-scale
PVinputunder-scale
(PVvaluesoutof-5to105%)(Loop
1,Loop2)
PVinputisoutof-5to105%.Alsooccurswhenthedataout
ofrangewhichistheladdercalculationresultisinput. Checkanaloginputvalueorladderprogram.
Setup parameter
Loop-1(PV1.E)(Registerno.:2002)Bit1=1
Loop-2(PV2.E)(Registerno.:2018)Bit1=1
RSPinputburnouterror(Loop1,
Loop2) BurnoutofanaloginputconnectedtoRSP Checkwiringandsensor.Errorindicationiserased
in normal operation.
Setup parameter
Loop-1(PV1.E)(Registerno.:2002)Bit2=1
Loop-2(PV2.E)(Registerno.:2018)Bit2=1
BurnouterrorwhenRSPinputis
usedforcontrol(Loop1,Loop2)
BurnoutofanaloginputconnectedtoRSPwhenRSPis
used for control computation
Checkwiringandsensor.Errorindicationiserased
in normal operation.
Checktheerrorin
LL50Asoftware.
Setupparameter(LA.ER)
(Registerno.:2012)
Overow:Bit1=1
Ladderprogramerror:Bit1=1
Loadfactorover100%:Bit4=1
Loadfactorover200%:Bit5=1
Laddercalculationoverow Floatingpointcomputationforladdercalculationisinnite. Checktheladderprogram.
Ladderprogramerror Ladderprogramiscorrupted.
Downloadtheladderprogramagain.Iftheerror
indicationisstillnoterased,thereisafault.
Contactusforrepair.
Loadfactorover100% Computationdoesnotendwithinthecontrolperiod(load
factoris100%ormore).
Changethecontrolperiodorreducethenumberof
stepsfortheladderprogram.
Loadfactorover200%
(Forcedend)
Computationdoesnotendwithinthecontrolperiod(loadfactoris
200%ormore).
Changethecontrolperiodorreducethenumberofsteps
fortheladderprogram.
Green,blinks
Setupparameter(OP.ER)
(Registerno.:2070)
E1-terminal:Bit8=1
E3-terminal:Bit10-=1
E4-terminal:Bit12=1
Peer-to-peercommunicationerror Peer-to-peercommunicationerror
Checkthatthetargetdevicesareconnected
correctly.
Recoveryatnormalreceipt.
Checktheerrorin
LL50Asoftware.
Setup parameter
Loop-1(PV1.E)(Registerno.:2002)Bit14=1
Loop-2(PV2.E)(Registerno.:2018)Bit14=1
Auto-tuningtime-out
(Loop1,Loop2)
Auto-tuningdoesnotendevenwhen24hourshaveelapsed
afterthestartoftuning.
Checktheprocess.Holddownanykeytoerasethe
error indication
Green,blinks
Setupparameter(OP.ER)
(Registerno.:2070)
E1-terminal:Bit8=1
E3-terminal:Bit10-=1
E4-terminal:Bit12=1
Communicationerror
(RS-485communication)
Framingparityerror
Bu󰀨eroverow
Inter-charactertime-out
Checksumerror(PClinkcommunicationwithchecksum)
CRCcheckerror(Modbus/RTU)
LRCcheckerror(Modbus/ASCII)
Checkthecommunicationparameters.
Recoveryatnormalreceipt.
Holddownanykeytostopblinking.
Communicationerror
(coordinatedoperation)
Inconsistence of loop between coordinated master and
slaves
Checkthecommunicationparameters.
Recoveryatnormalreceipt.Changefromremotetolocalmode
tostopblinking.
Whenthemodeischangedfromremotetolocal,SP
trackingdoesnotworkevenifitissettoON.
Communicationfromcoordinatedmasterisinterruptedfor2
seconds.
Userproleerror Userproleiscorrupted. Downloadtheuserproleagain.
Red,lit Setupparameter(PA.ER)
(Registerno.:2068)Bit8=1 FaultyFRAM
Writing(storing)datatoFRAMisimpossible.
Faulty.Contactusforrepair.
Unlit —FaultyMCU/DCU
(ROM/RAMerror,corrupted) MCU/DCUiscorrupted. Faulty.Contactusforrepair.

This manual suits for next models

1

Other YOKOGAWA Controllers manuals

YOKOGAWA UTAdvanced UT32A User manual

YOKOGAWA

YOKOGAWA UTAdvanced UT32A User manual

YOKOGAWA Fluidcom S2 User manual

YOKOGAWA

YOKOGAWA Fluidcom S2 User manual

YOKOGAWA UP35A User manual

YOKOGAWA

YOKOGAWA UP35A User manual

YOKOGAWA DYNASERV DM Series User manual

YOKOGAWA

YOKOGAWA DYNASERV DM Series User manual

YOKOGAWA UT32A-D User manual

YOKOGAWA

YOKOGAWA UT32A-D User manual

YOKOGAWA CX2000 Guide

YOKOGAWA

YOKOGAWA CX2000 Guide

YOKOGAWA STARDOM FCN Manual

YOKOGAWA

YOKOGAWA STARDOM FCN Manual

YOKOGAWA UT35A/MDL User manual

YOKOGAWA

YOKOGAWA UT35A/MDL User manual

YOKOGAWA UTAdvanced UP55A User manual

YOKOGAWA

YOKOGAWA UTAdvanced UP55A User manual

YOKOGAWA UT35A/RSP User manual

YOKOGAWA

YOKOGAWA UT35A/RSP User manual

YOKOGAWA YS80 Series Manual

YOKOGAWA

YOKOGAWA YS80 Series Manual

YOKOGAWA UT350 User manual

YOKOGAWA

YOKOGAWA UT350 User manual

YOKOGAWA UTAdvanced UT32A Manual

YOKOGAWA

YOKOGAWA UTAdvanced UT32A Manual

YOKOGAWA UT750 User manual

YOKOGAWA

YOKOGAWA UT750 User manual

YOKOGAWA FX103 User manual

YOKOGAWA

YOKOGAWA FX103 User manual

YOKOGAWA UTAdvanced UT35A Manual

YOKOGAWA

YOKOGAWA UTAdvanced UT35A Manual

YOKOGAWA UTAdvanced UT52A Manual

YOKOGAWA

YOKOGAWA UTAdvanced UT52A Manual

YOKOGAWA FA-M3 Vitesse Manual

YOKOGAWA

YOKOGAWA FA-M3 Vitesse Manual

YOKOGAWA ProSafe-RS Manual

YOKOGAWA

YOKOGAWA ProSafe-RS Manual

YOKOGAWA UTAdvanced UT32A Manual

YOKOGAWA

YOKOGAWA UTAdvanced UT32A Manual

YOKOGAWA AQ2201 User manual

YOKOGAWA

YOKOGAWA AQ2201 User manual

YOKOGAWA UT320 User manual

YOKOGAWA

YOKOGAWA UT320 User manual

YOKOGAWA Green Series User manual

YOKOGAWA

YOKOGAWA Green Series User manual

YOKOGAWA UT350-01 User manual

YOKOGAWA

YOKOGAWA UT350-01 User manual

Popular Controllers manuals by other brands

Krom Schroder VGBF 15R operating instructions

Krom Schroder

Krom Schroder VGBF 15R operating instructions

TQ TQMxE40C1 user manual

TQ

TQ TQMxE40C1 user manual

Theben JMG 4 T KNX manual

Theben

Theben JMG 4 T KNX manual

Campbell PS150 product manual

Campbell

Campbell PS150 product manual

Tunze 7074/2 Instructions for use

Tunze

Tunze 7074/2 Instructions for use

SUPMEA SUP-DC2000 user manual

SUPMEA

SUPMEA SUP-DC2000 user manual

Honeywell FAST-ACTING, TWO-POSITION ACTUATORS ML4202 installation instructions

Honeywell

Honeywell FAST-ACTING, TWO-POSITION ACTUATORS ML4202 installation instructions

Beck 42-107 instruction manual

Beck

Beck 42-107 instruction manual

Bürkert TopControl ON/OFF operating instructions

Bürkert

Bürkert TopControl ON/OFF operating instructions

FUTABA MCP-2 instruction manual

FUTABA

FUTABA MCP-2 instruction manual

InPOWER DBT-MDF20 quick start guide

InPOWER

InPOWER DBT-MDF20 quick start guide

Metal Work MULTIMACH user manual

Metal Work

Metal Work MULTIMACH user manual

Steren MODLED-010 instruction manual

Steren

Steren MODLED-010 instruction manual

SONBEST SM3260S user manual

SONBEST

SONBEST SM3260S user manual

Magtrol DSP6001 user manual

Magtrol

Magtrol DSP6001 user manual

Aerotech Automation1 SI4 Series Hardware manual

Aerotech

Aerotech Automation1 SI4 Series Hardware manual

Dimplex RXPW4 quick start guide

Dimplex

Dimplex RXPW4 quick start guide

Datakom DKG-325 user manual

Datakom

Datakom DKG-325 user manual

manuals.online logo
manuals.online logoBrands
  • About & Mission
  • Contact us
  • Privacy Policy
  • Terms and Conditions

Copyright 2025 Manuals.Online. All Rights Reserved.