manuals.online logo
Brands
  1. Home
  2. •
  3. Brands
  4. •
  5. York Survey Supply
  6. •
  7. Measuring Instrument
  8. •
  9. York Survey Supply 354920 User manual

York Survey Supply 354920 User manual

This manual suits for next models

1

Other York Survey Supply Measuring Instrument manuals

York Survey Supply 343680 User manual

York Survey Supply

York Survey Supply 343680 User manual

York Survey Supply 34302 User manual

York Survey Supply

York Survey Supply 34302 User manual

York Survey Supply 354820 User manual

York Survey Supply

York Survey Supply 354820 User manual

York Survey Supply 343300 User manual

York Survey Supply

York Survey Supply 343300 User manual

York Survey Supply 343090 User manual

York Survey Supply

York Survey Supply 343090 User manual

York Survey Supply 37135 User manual

York Survey Supply

York Survey Supply 37135 User manual

York Survey Supply S-Digit Mini+ 263040 User manual

York Survey Supply

York Survey Supply S-Digit Mini+ 263040 User manual

York Survey Supply 343520 User manual

York Survey Supply

York Survey Supply 343520 User manual

York Survey Supply 33065 User manual

York Survey Supply

York Survey Supply 33065 User manual

York Survey Supply 33235 User manual

York Survey Supply

York Survey Supply 33235 User manual

York Survey Supply 330550 User manual

York Survey Supply

York Survey Supply 330550 User manual

York Survey Supply 263090 User manual

York Survey Supply

York Survey Supply 263090 User manual

York Survey Supply 346010 User manual

York Survey Supply

York Survey Supply 346010 User manual

York Survey Supply Pro Sport 850 User manual

York Survey Supply

York Survey Supply Pro Sport 850 User manual

York Survey Supply 354910 User manual

York Survey Supply

York Survey Supply 354910 User manual

York Survey Supply 33245 User manual

York Survey Supply

York Survey Supply 33245 User manual

York Survey Supply 343000 User manual

York Survey Supply

York Survey Supply 343000 User manual

York Survey Supply 343010 User manual

York Survey Supply

York Survey Supply 343010 User manual

York Survey Supply 354420 User manual

York Survey Supply

York Survey Supply 354420 User manual

York Survey Supply 343660 User manual

York Survey Supply

York Survey Supply 343660 User manual

York Survey Supply 261640 User manual

York Survey Supply

York Survey Supply 261640 User manual

Popular Measuring Instrument manuals by other brands

Powerfix Profi 278296 Operation and safety notes

Powerfix Profi

Powerfix Profi 278296 Operation and safety notes

Test Equipment Depot GVT-427B user manual

Test Equipment Depot

Test Equipment Depot GVT-427B user manual

Fieldpiece ACH Operator's manual

Fieldpiece

Fieldpiece ACH Operator's manual

FLYSURFER VIRON3 user manual

FLYSURFER

FLYSURFER VIRON3 user manual

GMW TG uni 1 operating manual

GMW

GMW TG uni 1 operating manual

Downeaster Wind & Weather Medallion Series instruction manual

Downeaster

Downeaster Wind & Weather Medallion Series instruction manual

Hanna Instruments HI96725C instruction manual

Hanna Instruments

Hanna Instruments HI96725C instruction manual

Nokeval KMR260 quick guide

Nokeval

Nokeval KMR260 quick guide

HOKUYO AUTOMATIC UBG-05LN instruction manual

HOKUYO AUTOMATIC

HOKUYO AUTOMATIC UBG-05LN instruction manual

Fluke 96000 Series Operator's manual

Fluke

Fluke 96000 Series Operator's manual

Test Products International SP565 user manual

Test Products International

Test Products International SP565 user manual

General Sleep Zmachine Insight+ DT-200 Service manual

General Sleep

General Sleep Zmachine Insight+ DT-200 Service manual

Sensa Core Lacto Spark user manual

Sensa Core

Sensa Core Lacto Spark user manual

VOLTCRAFT UTS-1980 operating instructions

VOLTCRAFT

VOLTCRAFT UTS-1980 operating instructions

EBCHQ 94915 Operation manual

EBCHQ

EBCHQ 94915 Operation manual

Balluff BIP LD2-T017-01-EP-S4 Series user guide

Balluff

Balluff BIP LD2-T017-01-EP-S4 Series user guide

Pulsar IMP Lite Series instruction manual

Pulsar

Pulsar IMP Lite Series instruction manual

ETCR 6800 user manual

ETCR

ETCR 6800 user manual

manuals.online logo
manuals.online logoBrands
  • About & Mission
  • Contact us
  • Privacy Policy
  • Terms and Conditions

Copyright 2025 Manuals.Online. All Rights Reserved.

Code: 354920 - 354930
Operating
Instructions
Ref:.. \operat98\instructions 18\354920.qxp 05-01-18 ©York Survey Supply Centre 2018
Prospect House
George Cayley Drive
Clifton oor
York
England
YO30 4XE
Tel: +44 (0) 1904 692723
Fax: +44 (0) 1904 690385
E- ail: sales@yorksurvey.co.uk
...for secure online ordering of all our products!
Nothing else measures up!
Protimeter
Hygromaster
with Humidity Box or Humidity Sleeves
©York Survey Supply Centre 2018Ref:.. \operat98\instructions 18\354920.qxp 05-01-18
Protimeter Hygromaster
with Humidity Box or Humidity Sleeves
Moistu e Related Damage in Floo s
Excessive moisture in concrete floor slabs and screeds can lead to the following types of failure or
damage:
• Adhesion failure between floor covering and concrete slab. When the critical moisture level for
a given covering/adhesive/concrete is passed, bond strength drops sharply.
• Vinyl floor covering movement. Dampness in concrete may aggravate alkali related
dimensional changes in sheet vinyl.
• Emissions of harmful substances from floor covering materials. Examples include the emission
of ammonia from some screeds, the emission of formaldehyde from chipboard and the
degradation of certain plasticisers in sheet vinyl.
• Excessive expansion of solid wood floor coverings and the decay and degradation of wood
based floorboards.
These problems tend to occur when the moisture content of the concrete or screed exceeds the
critical moisture content of the materials that are in contact with it. A material’s critical moisture
content can be expressed as an equilibrium relative humidity (ERH) value or a moisture content
(%mc) value. ERH values are particularly suitable for this purpose because they convey the
moisture condition of the material in question - its degree of wetness. Whilst the critical moisture
content values vary for different materials, the problems outlined above are avoided when
substrates have an ERH below 75%.
Humidity and Relative Humidity (% h)
Humidity denotes the presence of water vapour - the gaseous form of water - in air and other
gases. The expression relative humidity (rh%) of air expresses the degree of saturation with water
vapour at a given temperature. Saturated air - having 100%rh - contains its full capacity of water
vapour. Relative humidity measurements are particularly appropriate for assessing the moisture
condition of environments. Similarly, equilibrium relative humidity (ERH) measurements are very
useful for assessing if materials are in a wet or dry condition. ERH values of materials are
obtained by measuring the %rh of a pocket of air deemed to be in moisture equilibrium with the
material under investigation.
Guidance fo Measu ing Moistu e in the ERH of Sc eeds and Slabs
The GE Protimeter Hygromaster L and GE Protimeter S instruments may be used to measure
the ERH of screeds and floor slabs when they are used with a GE Protimeter extension lead and a
GE Protimeter humidity box or GE Protimeter humidity sleeves. Please refer to the GE Protimeter
Hygromaster L and S user instructions for specific information on using these instruments.
1. ERH Test P ocedu e - using GE P otimete Humidity Sleeves
i. Drill 16mm (5/8”) diameter clearance holes to a nominal depth of 50mm (2”) at the required
points of measurement (PO s).
ii. Position a plastic membrane over the hole and push a GE Protimeter humidity sleeve through
the membrane and into the hole. Ensure that the flange of the humidity sleeve is flush with the
floor surface and that the humidity sleeve cap is firmly in position, to make an airtight seal.
iii. Leave for at least 24 hours to ensure moisture equilibrium conditions are reached within the
humidity sleeve. If in use, switch off any accelerated drying apparatus at least 4 days before
taking final readings.
iv. The ERH reading is made with the Hygrostick sensor supplied with the GE Protimeter
Hygromaster L instrument. Hygrosticks are fitted with a soft conical sealing sleeve. Ensure that
the tip of the Hygrostick protrudes fully from the narrow end of the sealing sleeve.
v. Remove the humidity sleeve cap and push the Hygrostick assembly into the humidity sleeve
and twist firmly to seal. Ideally, leave the Hygrostick in the hole for at least 30 minutes before
taking the first reading.
vi. Connect the Hygrostick to the Hygrometer L instrument with the GE Protimeter extension lead.
vii. easure the %rh in the hole; this is the ERH value of the floor slab.
2. ERH Test P ocedu e - using GE P otimete Humidity Box
This test procedure follows the guidelines given in the British Standards BS 5325 and BS 8203.
If full BS procedure compliance is required, please refer to these standards for comprehensive
details.
i. Place the humidity box on the surface at the required point of measurement (PO ) and put a
brick or similar object on top to ensure it is not inadvertently moved. Ensure the plug is in the
hole in the side of the box. If the surface is smooth, no additional sealing is required around the
rim of the box. If the surface has a rough texture, seal the box-surface interface with an inert
sealant such as plasticine.
ii. If in use, switch off any accelerated drying apparatus at least 4 days before taking readings.
Thereafter, for un-bonded screeds of thickness 50 - 75mm (2 - 3”) where a damp-proof
membrane has been placed between the base and screed, leave the humidity box in position
for at least 24 hours to ensure moisture equilibrium is reached within the box before taking
readings. For bonded screeds and direct finish base slabs allow a minimum of 72 hours to
pass before taking readings. Note that it may take many weeks for equilibrium conditions to be
reached within a humidity box on the surface when the slab thickness exceeds 200mm (8”)
and/or it has a power floated finish.
iii. The ERH reading is made with the Hygrostick sensor supplied with the GE Protimeter
Hygromaster L instrument. Hygrosticks are fitted with a soft conical sealing sleeve. Ensure that
the tip of the Hygrostick protrudes fully from the narrow end of the sealing sleeve.
iv. Remove the humidity box plug and push the Hygrostick assembly into the hole and twist firmly
to seal. Ideally, leave the Hygrostick in the humidity box for at least 30 minutes before taking
the first reading.
v. Connect the Hygrostick to the Hygrometer L instrument with the GE Protimeter extension lead.
vi. easure the %rh in the humidity box; assuming equilibrium conditions have been reached, this
is the ERH value of the screed or slab.